Page 27
5.5. Installation & Operational Troubleshooting
The table below is intended for problems related to the fire and its gas controls. It is a guide
only and does not take into account every eventuality. Servicing must be carried out in
accordance with the current Gas Safety (Installation and Use) Regulations, by a competent
person.
It is recommended that the purchaser seek the advice of the original installer in case of
encountering any problems.
Symptom
Cause
Remedy
No spark appears at
the electrode
a)
Electrode cracked or broken Replace pilot assembly
b)
HT lead shorting out on
burner body
Establish where spark is
occurring and insulate or re-
route lead accordingly.
c)
Faulty spark generator
Replace valve
Spark Generator
operates normally but
pilot will not light
a)
No gas supply
Check isolation valve/supply
d) Spark Generator Battery Flat Replace Battery
b)
Pilot jet blocked
Replace pilot assembly
Pilot lights, but goes
out when control is
released
a)
Loose thermocouple
connetion at control valve
end
Remake thermocouple
ensuring the connection is
firm
b)
Faulty Thermocouple
Replace complete pilot
assembly
Pilot and main burner
go out when control is
set to high position
a)
Gas supply partially blocked
Locate restrict and remove
faulty section
b)
Too many bends on gas inlet
pipe
Increase diameter and/or
reduce the number of bends
c)
Pilot jet partially blocked
Replace complete pilot
assembly
d)
Restriction at Isolation valve
Ensure valve is fully open
and that internal diameter is
sufficient and free from
grease
Fumes enter room
when the fire is in
operation
a)
Blocked flue
Remove blockage in flue
b)
Insufficient replacement air
Check air vents are free of
obstructions