Type MS08
General Settings - Parameter
54
12.3
Enter the location of the product
The entered location will be shown on any display connected to büS.
To enter the information where the product is located, do the following procedure:
Make sure that the login user level is
Installer
. Refer to chapter
.
Go to device
SAC254 Sensor
> function
General settings
> tab
Parameter
.
Select
büS
>
Location
and enter a location.
Validate with
Apply
.
The location is set.
12.4
Enter a description for the product
The description allows you to precisely identify the product. It will be displayed e.g. in tooltips.
To enter a description for the product, do the following procedure:
Make sure that the login user level is
Installer
. Refer to chapter
.
Go to device
SAC254 Sensor
> function
General settings
> tab
Parameter
.
Select
büS
>
Description
and enter the description.
Validate with
Apply
.
The description is set.
12.5
Enter a unique name for the product
The unique name of the product is used by the other fieldbus participants. The fieldbus participants can use
the data provided by the product on the fieldbus. For example, a Type ME25 controller-module can display
the water SAC254 value, given by the product.
If the unique name is changed, then the participant loses the link to the product and the participant gener-
ates the error
büS event: producer not found
. The link between the participant and the product must then
be restored.
Bürkert recommends not to change the unique name of the product. By default, the unique name is com-
posed with product article-number and serial number.
To change the unique name, do the following procedure:
Make sure that the login user level is
Installer
. Refer to chapter
.
Go to device
SAC254 Sensor
> function
General settings
> tab
Parameter
.
Select
büS
>
Advanced
>
Unique device name
and enter the name (max. 19 characters).
Save the name with
Apply
.
The unique name is set.
Restart the product to take the unique name into account.
If a participant was linked to the product, restore the link in the settings of the participant.
12.6
Change the transmission speed of the product
The transmission speed for the communication on the fieldbus (büS or CANopen) must be the same for all
the participants of the fieldbus.
By default, the transmission speed of the product is set to 500 kbit/s.
To change the transmission speed, do the following procedure: