Product information
Logano plus GB312 – 6 720 806 273 (2013/01)
11
2.10.2 Specifications
Boiler size (output - no. of heat exchanger sections)
Unit
90 - 4
120 - 4
160 - 5
200 - 6
240 - 7
280 - 8
Width B
Inch
39.1
39.1
47.3
47.3
55.5
55.5
Dimension XAA
Inch
13.1
13.1
15.1
17.2
19.2
21.3
Dimension X
RK
(= X
AL
= X
GAS
)
Inch
10.6
10.6
14.7
10.6
14.7
10.6
Dimension F
Inch
31.5
31.5
39.7
39.7
47.9
47.9
Dimension A
Inch
51.4
51.4
51.4
51.4
51.4
51.4
AA = Vent pipe diameter
Inch
6.3
6.3
6.3
7.9
7.9
7.9
Flue adaptor for desired manufacturer's venting system
6.3" x 5"
6.3" x 6"
6.3" x 6"
7.9" x 8"
7.9" x 8"
7.9" x 8"
Dimension Y
AA
Inch
18.5
18.5
18.5
19.5
19.5
19.5
Dimension Z
AA
Inch
5.7
5.7
5.7
12.2
12.2
12.2
AL = Combustion air pipe diameter (balanced flue only)
Inch
3.94
3.94
3.94
3.94
3.94
3.94
Connections VK and RK
NPT 2½ "
NPT 2½ "
NPT 2½ "
NPT 2½ "
NPT 2½ "
NPT 2½ "
Connection ST (B-kit)
¾" NPT
¾" NPT
¾" NPT
¾" NPT
¾" NPT
¾" NPT
Diameter GAS
1" NPT
1" NPT
1" NPT
1 ¼ " NPT 1 ¼ " NPT 1 ¼ " NPT
Table 3 Dimensions and connection sizes
Observe all standards and guidelines applicable to the
installation and operation of the heating system in your
country. The information on the data plate is binding and
must be observed.
Boiler size (output - no. of heat exchanger sections)
Unit
90 - 4
120 - 4
160 - 5
200 - 6
240 - 7
280 - 8
Natural gas (gas type A)
I-B-R Input
max. load
Btu/hr
328,300
440,500
588,300
732,600
880,700
1,028,800
min. load
Btu/hr
132,200
132,200
176,500
219,800
264,200
308,600
I-B-R gross output 180/80 ° F
max. load
Btu/hr
305,000
409,000
544,000
676,000
810,000
944,000
I-B-R net rating 180/80 ° F
max. load
Btu/hr
265,000
356,000
473,000
588,000
704,000
821,000
Rated heat output 122/86 ° F
max. load
Btu/hr
307,100
409,500
545,900
682,400
819,000
955,400
(50/30 ° C)
min. load
Btu/hr
128,100
127,400
171,200
212,300
255,200
298,100
Flue gas mass flow rate 180/80 ° F
max. load
lb/min
4.85
6.53
9.14
11.40
13.88
16.15
Flue gas mass flow rate 122/86 ° F
max. load
lb/min
5.05
7.12
9.29
11.61
14.02
16.65
Flue gas temperature 180/80 ° F
max. load
° F
83
90
127
138
140
134
Flue gas temperature 122/86 ° F
max. load
° F
120
133
129
131
131
135
CO
2
content, natural gas
max. load
%
9.1
9.1
9.1
9.1
9.1
9.1
(GAS A)
min. load
9.1
9.1
9.1
9.1
9.1
9.1
Available draft
in. W.C.
0.4
(100 Pa)
0.4
(100 Pa)
0.4
(100 Pa)
0.4
(100 Pa)
0.4
(100 Pa)
0.4
(100 Pa)
(flue draft + air supply pressure)
Air supply volumetric flow rate
cfm
95
95
130
160
190
220
Fan
G1G 170
G1G 170
G1G 170
G1G 170
G1G 170
G1G 170
Honeywell gas valve
V4730C1071
V4730C1097
V4730C10
63
Gas orifice diameter
Natural gas (GAS A) calorific value 1075 BTU/ft
3
17.0
17.0
17.0
17.0
17.0
17.0
Heating water circuit
Boiler water capacity
US
gallons
4.2
4.2
5.3
6.3
7.1
7.9
Primary pressure drop
psi
Fig. 4 (graph)
Maximum supply temperature, heating/hot water
mode
° F
180/180
180/180
180/180
180/180
180/180
180/180
High temperature cut-out safety limit (manual reset
high limit setting
)
° F
200
200
200
200
200
200
Table 4 Specifications