13
We reserve the right to make any changes due to technical modifications.
Installation and maintenance instructions Logano GE315 • Issue 02/2006
2
Installation
Keep the packing grooves (Fig. 10,
) clean and
dry to enable the packing cord to adhere to the groove.
z
Coat the packing groove with primer marked as
(Buderus Haftgrund primer 181).
z
Insert the elastic sealing cord (KM string: Fig. 11,
Item 2
) into the packing groove at the front of the rear
section, beginning in the hub area (Fig. 11,
)
and lightly press home. Overlap the sealing string by
2 cm and press firmly together.
Unroll the required length of packing cord (KM string)
from the roll supplied. Separate the backing paper from
the cord (but do not stretch), as you insert the cord into
the packing groove.
Preparation of the first middle section:
z
Remove any burrs from the hub using a file (see
Fig. 7).
z
Ensure the sealing grooves are clean and dry; clean
where necessary.
z
Clean the hub sealing faces with a cloth soaked in
white spirit.
z
Coat the hubs with the orange sealing compound
(Marked as (LEINOMENNIGE)) (Fig. 12,
).
z
Coat the sealing grooves with primer (Fig. 12,
Item 2
).
ATTENTION!
For health and safety reasons, ensure
adequate ventilation at the workplace
when applying primer!
Fig. 10
Coating the packing grooves with adhesive
Fig. 11
Fitting the sealing cord (KM string)
Fig. 12
Preparation of the central section
1
2
1
1
2