7
Boiler block assembly
Logano G615 - Subject to technical modifications
30
Fig. 32 Insert the flue gas baffles (boiler block with
13 sections)
1
Flue gas baffles with sickle profile (sectional baffle)
2
Flue gas baffles with sickle profile (sectional baffle)
3
Flue gas baffle with wave profile
Fig. 33 Insert the flue gas baffles (boiler block with
15 sections)
1
Flue gas baffle with wave profile
7.10
Installation of the boiler jacket
7.10.1 Fitting the thermal insulation
The thermal insulation provided corresponds to the boiler
size.
B
Arrange the thermal insulation on the boiler block as
shown in the diagram in
Æ
Fig. 35 (the figures to the
left of the boiler blocks represent the number of boiler
sections).
B
Push thermal insulation under the boiler block. The
boiler feet are placed in the cut-outs in the thermal
insulation.
Fig. 34 Boiler block with thermal insulation
1
Thermal insulation
2
1
3
6 720 642 625-29.1o
6 720 642 625-30.1o
Number of sections
Number of flue gas baffles
top left
top right
bottom left
bottom right
9
2 × sickle profile
2 × sickle profile
2 × sickle profile
2 × sickle profile
10
2 × sickle profile
2 × sickle profile
2 × sickle profile
2 × sickle profile
11
2 × sickle profile
2 × sickle profile
2 × sickle profile
2 × sickle profile
12
1 × wave profile
1 × wave profile
2 × sickle profile
2 × sickle profile
13
2 × sickle profile
2 × sickle profile
1 × wave profile
1 × wave profile
14
1 × wave profile
1 × wave profile
1 × wave profile
1 × wave profile
15
–
–
1 × wave profile
1 × wave profile
16
–
–
–
–
Tab. 11 Number of flue gas baffles
1
6 720 642 625-31.1o