3
Specifications
Logano G615 - Subject to technical modifications
13
Flue gas
mass flow
rate oil, full
load
2)
lbs./s
(kg/s)
0.5115 –
0.5765
(0.232 –
0.2615)
0.5714 –
0.6676
(0.2592 –
0.3028)
0.6616 –
0.7487
(0.3001 –
0.3396)
0.7416 –
0.8296
(0.3364 –
0.3763)
0.8217 –
0.9308
(0.3727 –
0.4222)
0.9218 –
1.0313
(0.4181 –
0.4678)
1.0218 –
1.1228
(0.4635 –
0.5093)
1.1118 –
1.2136
(0.5043 –
0.5505)
Flue gas
mass flow
rate, gas,
partial load
60%
lbs./s
(kg/s)
0.34
(0.1542)
0.3935
(0.1785)
0.4414
(0.2002)
0.4883
(0.2215)
0.5485
(0.2488)
0.6085
(0.276)
00.662
(0.3003)
0.7156
(0.3246)
Flue gas
mass flow,
gas, full
load
2)
lbs./s
(kg/s)
0.5132 –
0.5787
(0.2328 –
0.2625)
0.5736 –
0.67
(0.2602 –
0.3039)
0.664 –
0.7513
(0.3012 –
0.3408)
0.7443 –
0.8325
(0.3376 –
0.3776)
0.8247 –
0.9341
(0.3741 –
0.4237)
0.9251 –
1.0348
(0.4196 –
0.4694)
1.0256 –
1.127
(0.4652 –
0.5112)
1.1158 –
1.2181
(0.5061 –
0.5525)
CO
2
content,
oil
%
13
CO
2
content,
gas
%
10
Required flue
pressure
(draft
requirement)
PSI
(Pa)
0
(0)
Fireside
pressure
drop
in
W.C.
(mbar)
0.9624
(2.4)
1.3634
(3.4)
1.6842
(4.2)
1.6842
(4.2)
1.6441
(4.1)
1.8045
(4.5)
2.1654
(5.4)
2.3258
(5.8)
Permissible
supply
temperature
3)
°F
( °C)
212 – 248
(100 – 120
4)
Allowable
operating
water
pressure
PSI
(bar)
87
(6)
1) Weight not incl. packaging material approx. 4 – 5 % less.
2) The details relate to the upper and lower rated output range.
3) Safety limit (high limit safety cut-out). Maximum possible supply temperature = safety limit (STB) – 32 °F ( – 18 K).
Example: Safety limit (STB) = 212 °F (100 °C), max. possible supply temperature = 212 – 32 = 180 °F (100 – 18 = 82 °C).
4) Observe all gas regulations and requirements for your country.
Logano G615
Boiler
capacity
Unit
570
660
740
820
920
1020
1110
1200
Tab. 4
Technical data and dimensions