Display information
8
Logamax plus GB162-65/80/100 - Subject to modifications resulting from technical improvements!
25
Display code
z
Main
display
code
z
Sub
display
code
z
Key to display code
[\/-/\|
Operating phase:
Communication test while starting up. This display code flashes five times within
5 seconds while starting up to indicate that the communication between the UBA 3 and the
BC10 basic controller is being tested. If a new UBA 3 or a new KIM was fitted, this code
will flash for max. 10 seconds.
e
[-/a/\]
2)
e
[2/0/8|
1)
Operating phase:
The boiler is in flue gas test or service mode.
e
[-/h/\|
e
[2/0/0|
1)
Operating phase:
The boiler is in heating mode.
e
[-/h/}
3)
e
[2/0/0|
1)
Operating phase:
The boiler is in manual operation mode.
e
[=/h/\|
e
[2/0/1|
1)
Operating phase:
The boiler is in DHW mode.
e
[=/h/\|
e
[2/0/1|
1)
Operating phase:
Pump run-over time via the external hot water cylinder 130 seconds at the minimum
speed. The "Burner" LED (On/Off) is off.
e
[0/a/\|
e
[2/0/2|
1)
Operating phase:
The switch optimisation program is activated. This program is activated if there has been
a DHW request from an RC regulator more frequently than once every 10 minutes. This
means that the boiler cannot be restarted until at least ten minutes have elapsed since in-
itial burner start-up.
e
[0/a/\|
e
[3/0/5|
1)
Operating phase:
The boiler cannot start up temporarily after a DHW request has ended.
e
[0/c/\|
e
[2/8/3|
1)
Pre-operative phase:
The boiler prepares for a burner start-up whenever a heat demand or a DHW request aris-
es.
e
[0/e/\|
e
[2/6/5|
1)
Readiness for operation:
The boiler is in ready mode. There is a current heat demand, but too much energy has
been supplied.
e
[0/h/\|
e
[2/0/3|
1)
Readiness for operation:
The boiler is in ready mode. There is no current heat demand.
e
[0/l/\|
e
[2/8/4|
1)
Ignition phase:
The gas valve is activated.
e
[0/u/\|
e
[2/7/0|
1)
Start-up phase:
The boiler starts up after activation of the mains power supply or completion of a system
reset. This code is displayed for a maximum of 4 minutes.
e
[0/y/\|
e
[2/0/4|
1)
Operating phase:
The flow temperature sensor has detected that the current flow temperature is higher than
the flow temperature setting on the BC10, or that it is higher than the flow temperature.
Calculated according to heating requirements, or that it is higher than the flow temperature
calculated for the DHW mode.
e
[2/e/\|
e
[2/0/7|
e
Fault:
The system pressure is too low (less than 0.2 bar).
[8/8/8|
Function test:
Display test during start-up phase. The display code is displayed for a maximum of
1 second.
e
[a/1/1|
e
[8/0/2|
e
Fault:
Time not set. Failing time setting, e.g. due to a long power cut.
e
[a/1/1|
e
[8/0/3|
e
Fault:
Date not set. Failing date setting, e.g. due to a long power cut.
[h/\/7|
Operating phase:
The system pressure is too low (less than 1.0 bar).