Display information
8
Logamax plus GB162-65/80/100 - Subject to modifications resulting from technical improvements!
24
8
Display information
8.1
Display readings
8.2
Display settings
8.3
Display codes
The display shows the operating condition (e. g. a fault)
by means of two three-digit codes.
Refer to section 8.4, "Identifying and resetting faults" on
page 26 for further instructions on how to remedy certain
faults.
Please contact your heating engineer if you cannot rem-
edy a fault yourself or if the display shows a code which
is not listed in the table.
Display readings
Display
reading
Key to display reading
Unit
Range
[\/2/4|
Current CH (boiler) flow temperature.
°C
[\/\/0|
–
[1/3/0|
[p/1.6|
Current system pressure.
bar
[p/0.0|
–
[p/4.0|
Display settings
Display
setting
Meaning of display setting
Unit
Range
Factory-
adjusted
setting
[l/9/9|
Configured target load (100 kW).
%
[l/2/0|
–
[l/9/9|
/
[l/??/|
100 %
[l/??/|
[l/9/9|
Configured target load (65 and 80 kW).
%
[l/2/5|
–
[l/9/9|
/
[l/??/|
100 %
[l/??/|
[f/\/5|
Configured target value of the pump run-
over time.
Note
: Do not set a pump run-
over time of less than
[f/\/5|
(= 5 minutes).
min.
[f/0/0|
–
[f/6/0|
/
[f/1/d|
24 h
[f/\/5|
[c/\/1|
DHW supply operating condition setting.
Please note:
If the setting
[c/\/0|
is
displayed, the frost protection of the heat
exchanger or the external hot water
cylinder has also been switched off.
not
applicable
[c/\/0|
„Off“ /
[c/\/1|
„On“
[c/\/1|
Footnotes with the table below:
1) Only visible on the Service Tool or a specific RC regulator.
2) Any indication with a permanent dot in the bottom right-hand corner
3) Any indication with a flashing dot in the bottom right-hand corner.