Commissioning the heating system
5
Logamax plus GB162-65/80/100 - Subject to modifications resulting from technical improvements!
15
5.2
Boiler settings
Proceed as follows to complete the commissioning pro-
cedure:
Slowly open the gas valve by pushing on the gas
valve and turning it ¼ rotation in an anticlockwise
direction (fig. 15). The gas valve is open when it is in
its vertical position.
Turn both dials on the BC10 basic controller (fig. 16,
items 2
and
3)
to their required positions
(
section 5.2.1 and 5.2.2, from page 15).
Switch on the mains switch (fig. 16,
item 1
) on the
BC10 (position "1").
5.2.1 Setting the CH (boiler) flow temperature
Set the dial for the maximum CH (boiler) flow
temperature (fig. 16,
item 2
) to set the required
temperature according to table 3.
fig. 15
Opening the gas valve
1
fig. 16
BC10 basic controller
1
3
2
If you are using a room controller both dials
must be on "Aut" (automatic operation) to
enable all settings to be made using the
room controller.
If the temperature setting is too low, there is
a risk that the required room temperature
will not be reached.
Dial
Function
Settings for
Description
0
Off
No heating operation (summer)
40 °C
Required CH (boiler) flow temperature in °C
underfloor heating
Heating mode on
75 °C – 90 °C
Radiators
90 °C
Convectors
Aut
Setting via Logamatic control (e.g. RC35/Logamatic 4121)
table 3 CH (boiler) flow temperature