LRV-1 lift control valve
5 Operation
67/86
300-I-9010050-E-28/02.2012
Note
Effect
By default
Setting range
Parameter name
(Miniterminal)
I sol. dynamic
Effective in
dynamic control
processes
(acceleration,
deceleration)
100…1000ms
LRV175-1*:
=
450ms
O
350ms
LRV 175-1
120bar:
=
350ms
O
350ms
LRV350-1,
LRV700-1:
=
450ms
O
500ms
Increasing values:
S
Longer solenoid integral
time
S
Greater control deviation
in dynamic processes
* all types except for
LRV175-1120bar
Low values:
Oscillations possible
Calibr. factor
0.90…1.30
=
1.00
O
1.00
Valve calibration (actual
value)
The DELCON board delivered
with the valve is adjusted to the
valve.
If the DELCON board is ex
changed, transfer the content of
the “Calibr. factor” to the new
board!
5.5.2
Options menu
Parameter name
(Miniterminal)
Setting range
By default
Effect
Note
Valve type
(P2.01)
Handterminal (Miniterminal)
LRV 175-1 (1)
LRV 350-1 (2)
LRV 700-1 (3)
LRV 175-A (4)
LRV 350-A (5)
LRV 175 (6)
LRV 350 (7)
LRV 700 (8)
VF-LRV 350 (9)
VF-LRV 700 (10)
C-LRV 175 (11)
C-LRV 350 (12)
C-LRV 700 (13)
LRV 175-1 120bar (14)
LRV 350-1 PM (15)
LRV 700-1 PM (16)
VF C-LRV 175 (17)
VF C-LRV 350 (18)
Valve type selection
The current control
parameters (PID) will be
overwritten with factory
settings for the selected
valve