4.4 Dimensions IFC 10
All dimensions in mm
4.5 Installation
The IFC 10 should be mounted close to the flame with straight alignment. The compact flame
detector should be mounted with the diopter. The diopter guaranties a quick mounting and
demounting of the compact flame controller. A diameter of 1‘‘ is recommended for viewing
tube that is cut down on the port side of the rear sight to ½‘‘. The sight pipe must be ade-
quately dimensioned.
The alignment is to concentrate on the primary zone of the flame (flame root). The distance
from the flame should be less than 2 m. Upon completion of the assembly work the screws
of the rear sight to the flame menwächters are to be tightened down. At high temperature
on the sight glass, which could heat the UV tube to about 60°C, an air connection is to be
provided. To avoid interference, the direct view is to avoid a spark.
The maximum cable length of the cable is to be noted (see „Technical data). The connecting
cable is to run separately from the high-energy ignition and power lines over long distances
and not parallel to transfer it to.
All installation and connection work may be carried out by qualified and approved spe-
cialist staff only! The legal regulations as well as adjustment instructions of the plant
operator have to be observed!
NOTICE
TRANSPORT, INSTALLATION AND CONNECTION
For safety reasons and technical regulations a controlled burner shut down of at least
once per 24 hours must be guaranteed. Check according to EN 298:2012-11 need to
check the UV tube to be used in the burner control to the controlled shutdown on the
presence of a flame signal back.
DANGER
!