Operation of the flame detektor
IFC 10
6.1 Test of the flame detektor
To ensure the proper operation, the flame detector has to be testet several times by starting
and stopping the burner. As long as there is no flame in all cases the flame relays has to be
switched off solid. The test should be repeat for differnt operation situations ( see also da-
tasheet ). This is a essential condition for a safe and proper operation.
6.2 Operating indicator LED
Via the built-in LED the flame detector is indicating the fol-lowing operating conditions:
LED
Meaning
off
IFC 10 is without connection or there is no detected
flame
Blinking
Flame is detected
The blinking of the LED representes the flame signal
intensity
Increasing blinking = higher intensity
on
The flame is detected with highest intensity
OPERATING OF THE FLAME DETECTOR IFC 10