background image

Installation Instructions

SYSTXBBUID01--D

EVOLUTION

t

CONTROL

Deluxe 

User Interface

® 

A09436

Fig. 1 -- Evolution

t

Control

NOTE

: Read the entire instruction manual before starting the

installation.

TABLE OF CONTENTS

PAGE

SAFETY CONSIDERATIONS

1

. . . . . . . . . . . . . . . . . . . . . . . . .

INTRODUCTION

1

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

INSTALLATION AND START--UP OVERVIEW

2

. . . . . . . . . .

INSTALLATION

2

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

INSTALLING EVOLUTION CONTROL

3

. . . . . . . . . . . . . . . . .

INITIAL POWER--UP

5

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

QUICK START

7

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

INSTALL / SERVICE MENUS

8

. . . . . . . . . . . . . . . . . . . . . . . . .

EQUIPMENT SUMMARY MENU

8

. . . . . . . . . . . . . . . . . . . . . .

INSTALL MENU

8

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

SETUP MENU

8

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

CHECKOUT MENUS

13

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

SERVICE MENUS

14

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

OPERATIONAL INFORMATION

15

. . . . . . . . . . . . . . . . . . . . .

TROUBLESHOOTING

17

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

SYSTEM MALFUNCTION SCREEN

18

. . . . . . . . . . . . . . . . . .

SAFETY CONSIDERATIONS

Improper installation, adjustment, alteration, service, maintenance,
or use can cause explosion, fire, electrical shock, or other

conditions which may cause death, personal injury or property
damage. Consult a qualified installer, service agency or your

distributor or branch for information or assistance. The qualified

installer or agency must use factory--authorized kits or accessories
when modifying this product. Refer to the individual instructions

packaged with the kits or accessories when installing.
Follow all safety codes. Wear safety glasses, protective clothing,

and work gloves. Have a fire extinguisher available. Read these
instructions thoroughly and follow all warnings and cautions

included in literature and attached to the unit. Consult local

building codes and the current edition of the National Electrical
Code (NEC) NFPA 70.
In Canada, refer to the current editions of the Canadian Electrical
Code CSA C22.1.

Recognize safety information. When you see this symbol

on

the unit and in instructions or manuals, be alert to the potential for
personal injury. Understand the signal words

DANGER

,

WARNING

, and

CAUTION

. These words are used with the

safety--alert symbol.

DANGER

identifies the most serious hazards,

which

will

result in severe personal injury or death.

WARNING

signifies hazards, which

could

result in personal injury or death.

CAUTION

is used to identify unsafe practices, which

may

result

in minor personal injury or product and property damage.

NOTE

is used to highlight suggestions which

will

result in enhanced

installation, reliability, or operation.

INTRODUCTION

The

Evolution

System

consists

of

several

intelligent

communicating components which includes the Evolution Control

(or User Interface), variable speed furnace or FE fan coil, 2--stage
AC or HP and Evolution Packaged Products, which continually

communicate with each other via a four--wire connection called the

ABCD bus. Commands, operating conditions, and other data are
passed continually between components over the ABCD bus. The

result is a new level of comfort, versatility, and simplicity.
All Evolution furnaces or fan coils are variable--speed and multi

stage for maximum flexibility, efficiency, and comfort. They

support controlled ventilation, humidification, dehumidification,
and air quality control. Either an Evolution (communicating), or a

standard 24VAC controlled outdoor unit may be used.
When using conventional outdoor units, the Evolution furnace or

fan coil provides the 24 volt signals needed to control them. Also,
the Evolution Network Interface Module (P/N SYSTXBBNIM01)

allows connection of a Bryant HRV or ERV without the need for a

separate wall control.
All system components are controlled through the wall mounted

Evolution Control, which replaces the conventional thermostat and
provides the homeowner with a single wall control for all features

of the system.

Содержание SYSTXBBUID01--D

Страница 1: ...tential for personal injury Understand the signal words DANGER WARNING and CAUTION These words are used with the safety alert symbol DANGER identifies the most serious hazards which will result in sev...

Страница 2: ...S In areas with poor air circulation such as behind a door or in an alcove Remote Room Sensor Option A Remote Room Sensor can be used with the Evolution Control to take the place of the User Interface...

Страница 3: ...To remove the control from the base insert a flat screw driver into each of the four slots two on each side and pry towards yourself to release the holding tabs Refer to Fig 7 to locate the slots A100...

Страница 4: ...ABCD connector will cause the Evolution System to operate improperly Check to make sure all wiring is correct before proceeding with installation or turning on power CAUTION 9 Push any excess wire int...

Страница 5: ...5 Fig 13 Power Up Sequence NOTE If the variable speed indoor equipment furnace or fan coil cannot be found the User Interface will display CANNOT COMMUNICATE WITH INDOOR UNIT This MUST be corrected be...

Страница 6: ...ress right side button to continue UV Lights Installed This screen will appear to select whether UV lights are installed on the system select YES or NO then press right side button to continue Equipme...

Страница 7: ...g temperature using the RIGHT Up Down button 7 Press the blue COOL button Cooling temperature will be gin flashing 8 Set the cooling temperature using the RIGHT Up Down button 9 Set the remaining peri...

Страница 8: ...ttings S Yes No to reset the user settings in the Advanced Setup to factory default settings Install Settings S Yes No to reset install settings in Install Service menus to factory default settings La...

Страница 9: ...supply products e g fresh air make up air dampers S FAN SPEED select Low Med High for all zones when G terminal is energized S SHUTDOWN shuts off fan and equipment when initiated This function is not...

Страница 10: ...alue limited by the model number of the fan coil If the electric heater is self identifying this value is not shown Elect Heat Lockout S NONE default S 5 to 55_F 15 to 13_C Outside temperature above w...

Страница 11: ...e settings YES NO HP TO FURNACE STAGING TIME Adjust the minimum amount of time the heat pump will run before furnace will be allowed to run S Default 15 MIN S Available settings 15 60 minutes If a dem...

Страница 12: ...own in Fig 28 CHECKOUT FURNACE HEAT PUMP HEATING HEAT PUMP COOLING HUMIDIFIER VENTILATOR BACK SELECT A03204 Fig 28 Checkout Menu Checkout Furnace or Gas PAC Make sure the furnace is properly installed...

Страница 13: ...S Seconds If a lockout timer is active this will show the current time value See furnace manual for details on lockout timers Service Fan Coil Status Electric Heat S OFF LOW MED HIGH Displays stages...

Страница 14: ...he same time for 3 seconds When keys are locked a lock symbol will appear in the upper left corner of screen Follow same procedure to unlock keypad Heat and Cool LED The Heat and Cool LEDs will pulsat...

Страница 15: ...ings ON and OFF If DEHUMIDIFY is set to ON factory default then the cooling unit will be allowed to overcool the space up to 3_F 2_C if the humidity level is above the cooling humidity target setpoint...

Страница 16: ...ectly to indoor unit with a short piece of thermostat wire Add other devices one at a time to determine where the communication issue exists Display says Outdoor Unit Not Found and I have a two stage...

Страница 17: ...e over as the system controller putting the regular system user interface to sleep The screen on the regular user interface will display IN SERVICE MODE The D model user interface will then learn all...

Страница 18: ...hange at any time specifications or designs without notice and without incurring obligations E2011 Bryant Heating Cooling Systems 7310 W Morris St Indianapolis IN 46231 Printed in China Edition Date 0...

Отзывы: