12

If YES, indicates to the system whether a humidifier is installed
and enables humidification functions.
CHANGE PAD INTERVAL: 1 to 24 months (default = 12
months)
Interval at which the Change Humidify Pad notification will be

displayed.
HUMIDIFY WITH FAN: (Heating Mode Only)

S

NO (default)

S

YES

If YES, the humidifier will turn on if there is a humidify demand

present. The fan will turn on to Low speed if the fan setting is
Auto.

Ventilator:
NOTE

: Only appears if ventilator is installed.

CLEAN INTERVAL:

S

60 to 180 days of actual operation (default = 90)

Interval at which the Clean Ventilator Pre--filter notification will

turn on.

UV Lights Installed

S

NO

S

YES

If YES, indicates to the system whether UV lights are installed.
CHANGE INTERVAL:

S

6 to 48 months operation time (default = 12 months)

Interval at which the Change UV Lights notification will be
displayed.

Setup -- System Maintenance

Remind Owner of Routine Maintenance Every:

This setup is used to adjust the timer interval in which the normal

System Maintenance notification is turned on for the homeowner.
(See Fig. 30.)
Range =

S

OFF

S

6 to 24 months, (default = 12 months)

 

SYSTEM  MAINTENANCE

< BACK

REMIND OWNER OF
MAINTENANCE EVERY:

12  MONTHS

% USED:

50%

RESET >

A07033

Fig. 27 -- System Maintenance

Pressing the right side button will reset the timer. Pop--up

confirmation will be shown.

Setup -- Utility Saver

Cooling/Heat Pump Heating: (Hybrid Heat & Hydronic Heat
Only)

S

Turn off, Low Stage

Utility Saver is used to force the equipment to a lower stage (low
or off) when activated by the utility company, typically during

peak load times.
This setup is available only if the equipment has a utility saver
input (refer to outdoor equipment Installation Instructions). This

setup controls the response of the equipment when the utility saver
input is active.
The choices include:

S

Turn Off , (equipment turns off)

S

Low Stage (available if the AC/heat pump is a 2--stage model,
runs low speed only)

CHECKOUT MENUS

The Checkout menu will show the equipment installed in the

system. A sample checkout menu is shown in Fig. 28.

CHECKOUT

FURNACE

HEAT PUMP HEATING

HEAT PUMP COOLING

HUMIDIFIER

VENTILATOR

   BACK               SELECT

A03204

Fig. 28 -- Checkout Menu

Checkout -- Furnace or Gas PAC

Make sure the furnace is properly installed before continuing.

S

LOW HEAT RUNTIME: 5 min.

S

HIGH HEAT RUNTIME: 5 min.

This menu item allows the furnace to be exercised. First, a low heat

runtime and high heat runtime are selected. Range = 5 -- 120 min.
If only the low heat is to be exercised:
The furnace will execute its ignition start--up sequence. This

sequence will be displayed on the Evolution Control screen. After
the gas valve and blower motor turn on, the screen will

automatically change to “

FURNACE CHECK

” and show the

current operating status of the furnace.

Checkout -- Electric Heat

S

ELECTRIC HEAT RUNTIME: 5 min., Default time = 5 min.,
Range = 0 -- 120 min.

If you have a fan coil with electric heaters, this menu item will

allow the heaters to be exercised.
With self--identifying electric heaters, three stages of electric heat

are available to be exercised in any combination. Non--identifying
heaters will only provide one stage of heat.
Enter the run time (in minutes) of each stage of heat to be exercised

then press START (right--side button). The display will change to
show the fan coil’s operating status.

Checkout -- Heat Pump Heating

S

HIGH HEAT RUNTIME: 5 min.

S

LOW HEAT RUNTIME: 5 min.

S

DEFROST: NO

The heat pump heating mode can be exercised with this menu

option. With a 2--stage heat pump, a low heat runtime and a high
heat runtime are independently selectable to exercise. A defrost

cycle is also selectable. Default time = Fixed 5 min. minimum,
range = 5 -- 120 min.

NOTE

:

Airflows during Checkout modes are fixed to the

Efficiency setting and are independent of other airflow settings. To
view airflows for normal heat pump heating mode, exit the
Checkout screen and apply a heating demand to the system.

Checkout -- Heat Pump Cooling or AC Cooling

S

HIGH COOL RUNTIME: 5 min.

S

LOW COOL RUNTIME: 5 min.

The heat pump cooling mode (or AC cooling mode) can be

exercised with this menu option. With a 2--stage heat pump or AC

unit, a low cool runtime and a high cool runtime are independently
selectable to exercise. The display will change to show the heat

pump or AC operating status.

UID

01

--

D

Содержание SYSTXBBUID01--D

Страница 1: ...tential for personal injury Understand the signal words DANGER WARNING and CAUTION These words are used with the safety alert symbol DANGER identifies the most serious hazards which will result in sev...

Страница 2: ...S In areas with poor air circulation such as behind a door or in an alcove Remote Room Sensor Option A Remote Room Sensor can be used with the Evolution Control to take the place of the User Interface...

Страница 3: ...To remove the control from the base insert a flat screw driver into each of the four slots two on each side and pry towards yourself to release the holding tabs Refer to Fig 7 to locate the slots A100...

Страница 4: ...ABCD connector will cause the Evolution System to operate improperly Check to make sure all wiring is correct before proceeding with installation or turning on power CAUTION 9 Push any excess wire int...

Страница 5: ...5 Fig 13 Power Up Sequence NOTE If the variable speed indoor equipment furnace or fan coil cannot be found the User Interface will display CANNOT COMMUNICATE WITH INDOOR UNIT This MUST be corrected be...

Страница 6: ...ress right side button to continue UV Lights Installed This screen will appear to select whether UV lights are installed on the system select YES or NO then press right side button to continue Equipme...

Страница 7: ...g temperature using the RIGHT Up Down button 7 Press the blue COOL button Cooling temperature will be gin flashing 8 Set the cooling temperature using the RIGHT Up Down button 9 Set the remaining peri...

Страница 8: ...ttings S Yes No to reset the user settings in the Advanced Setup to factory default settings Install Settings S Yes No to reset install settings in Install Service menus to factory default settings La...

Страница 9: ...supply products e g fresh air make up air dampers S FAN SPEED select Low Med High for all zones when G terminal is energized S SHUTDOWN shuts off fan and equipment when initiated This function is not...

Страница 10: ...alue limited by the model number of the fan coil If the electric heater is self identifying this value is not shown Elect Heat Lockout S NONE default S 5 to 55_F 15 to 13_C Outside temperature above w...

Страница 11: ...e settings YES NO HP TO FURNACE STAGING TIME Adjust the minimum amount of time the heat pump will run before furnace will be allowed to run S Default 15 MIN S Available settings 15 60 minutes If a dem...

Страница 12: ...own in Fig 28 CHECKOUT FURNACE HEAT PUMP HEATING HEAT PUMP COOLING HUMIDIFIER VENTILATOR BACK SELECT A03204 Fig 28 Checkout Menu Checkout Furnace or Gas PAC Make sure the furnace is properly installed...

Страница 13: ...S Seconds If a lockout timer is active this will show the current time value See furnace manual for details on lockout timers Service Fan Coil Status Electric Heat S OFF LOW MED HIGH Displays stages...

Страница 14: ...he same time for 3 seconds When keys are locked a lock symbol will appear in the upper left corner of screen Follow same procedure to unlock keypad Heat and Cool LED The Heat and Cool LEDs will pulsat...

Страница 15: ...ings ON and OFF If DEHUMIDIFY is set to ON factory default then the cooling unit will be allowed to overcool the space up to 3_F 2_C if the humidity level is above the cooling humidity target setpoint...

Страница 16: ...ectly to indoor unit with a short piece of thermostat wire Add other devices one at a time to determine where the communication issue exists Display says Outdoor Unit Not Found and I have a two stage...

Страница 17: ...e over as the system controller putting the regular system user interface to sleep The screen on the regular user interface will display IN SERVICE MODE The D model user interface will then learn all...

Страница 18: ...hange at any time specifications or designs without notice and without incurring obligations E2011 Bryant Heating Cooling Systems 7310 W Morris St Indianapolis IN 46231 Printed in China Edition Date 0...

Отзывы: