background image

2

INSTALLATION, START--UP OVERVIEW

This instruction covers installation of the Evolution Control

only

.

Physical installation instructions for the indoor and outdoor

equipment, and accessories are provided with each unit.
Setup, commissioning, operation, and troubleshooting of the

Evolution System are covered only in this installation instruction.

It is the guide to connecting the system components and
commissioning the system once all physical components are

installed. Special screen prompts and start--up capabilities are
provided in the Evolution System to simplify and automate the

initial commissioning of the system.

S

Install Evolution Control according to this instruction.

S

Install indoor unit, outdoor unit, and accessories according to
their instructions.

S

Wire complete system according to this instruction.

S

Setup, commission, and operate system according to this
instruction to assure a smooth and trouble free start--up.

INSTALLATION

Check Equipment and Job Site

Inspect equipment. File claim with shipping company prior to

installation if shipment is damaged or incomplete.

Evolution Control Location and Wiring

Considerations

ELECTRICAL OPERATION HAZARD

Failure to follow this warning could result in personal injury

or death.
Disconnect power before routing control wiring.

!

WARNING

All wiring must comply with national, local, and state codes.

Evolution Control Location

The Evolution Control User Interface is the command center for

the Evolution System. It should be located where it is easily
accessible and visible to the adult homeowner or end user.
For accurate temperature measurement, the following guidelines

should be followed:
The Evolution Control and Room Sensors should be mounted:

S

Approximately 5--ft (1.5 m) from the floor.

S

Close to or in a frequently used room, preferably on an inside
partitioning wall.

S

On a section of wall without pipes or ductwork.

The Evolution Control and Room Sensors should

NOT

be

mounted:

S

Close to a window, on an outside wall, or next to a door leading
to the outside.

S

Exposed to direct light or heat from a lamp, sun, fireplace, or
other temperature--radiating objects which could cause a false
reading.

S

Close to or in direct airflow from supply registers.

S

In areas with poor air circulation, such as behind a door or in an
alcove.

Remote Room Sensor Option

A Remote Room Sensor can be used with the Evolution Control to

take the place of the User Interface internal temperature sensor.
This allows the Evolution Control to be mounted in areas with less

than optimal airflow (such as near an exterior door, window or in a
closet). The remote sensor can be wired to the terminal block

connectors labeled S1 and S2 at the User Interface backplate, or the

ZS1 and ZS1C connection at the Damper Control Module. In
either case, the Evolution Control will automatically detect the

Remote Room Sensor and ignore its internal temperature sensor.
Typically, one remote sensor is used but, multiple sensors may be

used and averaged in some applications. Averaging requires a

special series--parallel wiring method with a specific number of
sensors. See Fig. 2. It is also important to note the humidity sensor

cannot be remotely located, so do not locate the Evolution Control
in an area where humidity sensing may not be accurate.

Sensor 1

Sensor 2

Sensor 3

Sensor 4

S1

S2

A07116

Fig. 2 -- Remote Room Sensor -- Parallel Wiring

Wiring Considerations

Ordinary thermostat wire is recommended. Use 22 AWG or larger
for normal wiring applications. Continuous wire lengths over 100

ft. should use 20 AWG or larger.

NOTE

: ABCD bus wiring only requires a four--wire connection;

however, it is good practice to run thermostat cable having more
than four wires in the event of a damaged or broken wire during
installation.
Each communicating device in the Evolution System has a
four--pin connector labeled ABCD. It is recommended that the

following color code be used when wiring each device:
A — Green = Data A
B — Yellow = Data B
C — White = 24VAC (Com)
D — Red = 24VAC (Hot)
It is not mandatory that the above color code be used, but each

ABCD connector in the system MUST be wired consistently.

Shielded Wire

If the thermostat wiring will be located near or in parallel with high
voltage wiring, cable TV, Ethernet wiring, or radio frequency

equipment, then shielded thermostat wire can be used to reduce or
eliminate potential interference.

The shield wire should be

connected to the C terminal, or ground, at the indoor unit. The
shield wire should NOT be connected to any terminal at the user

interface. Connecting the shield to ground at both ends can cause

current loops in the shield, reducing shield effectiveness.

UID

01

--

D

Содержание SYSTXBBUID01--D

Страница 1: ...tential for personal injury Understand the signal words DANGER WARNING and CAUTION These words are used with the safety alert symbol DANGER identifies the most serious hazards which will result in sev...

Страница 2: ...S In areas with poor air circulation such as behind a door or in an alcove Remote Room Sensor Option A Remote Room Sensor can be used with the Evolution Control to take the place of the User Interface...

Страница 3: ...To remove the control from the base insert a flat screw driver into each of the four slots two on each side and pry towards yourself to release the holding tabs Refer to Fig 7 to locate the slots A100...

Страница 4: ...ABCD connector will cause the Evolution System to operate improperly Check to make sure all wiring is correct before proceeding with installation or turning on power CAUTION 9 Push any excess wire int...

Страница 5: ...5 Fig 13 Power Up Sequence NOTE If the variable speed indoor equipment furnace or fan coil cannot be found the User Interface will display CANNOT COMMUNICATE WITH INDOOR UNIT This MUST be corrected be...

Страница 6: ...ress right side button to continue UV Lights Installed This screen will appear to select whether UV lights are installed on the system select YES or NO then press right side button to continue Equipme...

Страница 7: ...g temperature using the RIGHT Up Down button 7 Press the blue COOL button Cooling temperature will be gin flashing 8 Set the cooling temperature using the RIGHT Up Down button 9 Set the remaining peri...

Страница 8: ...ttings S Yes No to reset the user settings in the Advanced Setup to factory default settings Install Settings S Yes No to reset install settings in Install Service menus to factory default settings La...

Страница 9: ...supply products e g fresh air make up air dampers S FAN SPEED select Low Med High for all zones when G terminal is energized S SHUTDOWN shuts off fan and equipment when initiated This function is not...

Страница 10: ...alue limited by the model number of the fan coil If the electric heater is self identifying this value is not shown Elect Heat Lockout S NONE default S 5 to 55_F 15 to 13_C Outside temperature above w...

Страница 11: ...e settings YES NO HP TO FURNACE STAGING TIME Adjust the minimum amount of time the heat pump will run before furnace will be allowed to run S Default 15 MIN S Available settings 15 60 minutes If a dem...

Страница 12: ...own in Fig 28 CHECKOUT FURNACE HEAT PUMP HEATING HEAT PUMP COOLING HUMIDIFIER VENTILATOR BACK SELECT A03204 Fig 28 Checkout Menu Checkout Furnace or Gas PAC Make sure the furnace is properly installed...

Страница 13: ...S Seconds If a lockout timer is active this will show the current time value See furnace manual for details on lockout timers Service Fan Coil Status Electric Heat S OFF LOW MED HIGH Displays stages...

Страница 14: ...he same time for 3 seconds When keys are locked a lock symbol will appear in the upper left corner of screen Follow same procedure to unlock keypad Heat and Cool LED The Heat and Cool LEDs will pulsat...

Страница 15: ...ings ON and OFF If DEHUMIDIFY is set to ON factory default then the cooling unit will be allowed to overcool the space up to 3_F 2_C if the humidity level is above the cooling humidity target setpoint...

Страница 16: ...ectly to indoor unit with a short piece of thermostat wire Add other devices one at a time to determine where the communication issue exists Display says Outdoor Unit Not Found and I have a two stage...

Страница 17: ...e over as the system controller putting the regular system user interface to sleep The screen on the regular user interface will display IN SERVICE MODE The D model user interface will then learn all...

Страница 18: ...hange at any time specifications or designs without notice and without incurring obligations E2011 Bryant Heating Cooling Systems 7310 W Morris St Indianapolis IN 46231 Printed in China Edition Date 0...

Отзывы: