background image

8

SETUP MENU

This menu has several layers, allowing modification of equipment
settings. No settings will need to be made at equipment (i.e. DIP

switches on a furnace). All configuration settings made effective
from this menu will override equipment configuration made by dip

switches. Fig. 22 shows all the information that can be found in the

SETUP

menu.

SETUP

THERMOSTAT

FURNACE

HEAT PUMP

ACCESSORIES

SYSTEM MAINTENANCE

   BACK               SELECT

A03203

Fig. 22 -- Setup Menu

Setup -- Thermostat

Auto Mode Setup:

S

Enable/Disable Auto Changeover mode (default = Enable).

S

Auto Changeover Time may be adjusted 5 to 120 minutes,
(default = 30 minutes).

When Auto mode is enabled (factory default) a change from heat
to cool (or vice versa) will not occur until the current cycle is

satisfied and an opposite mode demand has existed for 30 minutes.

If the setpoint is changed, the 30 minute timer is deleted.

Heat/Cool Deadband:

S

0 to 6

_

F (0 to 3

_

C), (default = 2

_

F)

The minimum difference enforced between heating and cooling
desired temperatures. This can allow one setting to “push” the

other to maintain this difference.

Offsets:

This option allows calibration (or deliberate miscalibration) of the
temperature and humidity sensors. These offsets are added to the

actual temperature/humidity values (default = 0).

S

Temperature Offset: --5

_

F to +5

_

F (--3

_

C to +3

_

C)

S

Outside Temp Offset: --5

_

F to +5

_

F (--3

_

C to +3

_

C)

S

Humidity Offset: --10 to +10%

Elevation:

0 to 10,000 feet. This value is used to correct the static pressure
readings the system performs.

Cycles Per Hour:

S

Maximum cycles per hour = 4 (default) or 6.

Programming:

S

ON (default)-- allows program schedule to be set by user.

S

OFF -- system becomes non--programmable

S

Periods Per Day = 2 or 4 (default = 4)

S

Programmable Fan On/Off (default = Off). If ON is selected, fan
can be set to Auto, Low, Med, or High.

Smart Recovery:

S

On or Off (default = On)

Applies to programmable operation only. Will start recovery 90

minutes prior to schedule change in both heating and cooling

mode. Refer to operational information for more detail.

English/Metric Display:

S _

F or

_

C, (default =

_

F)

Reset Factory Defaults:
Program Schedule:

S

Yes/No to reset back to Energy Star default Time and Temp
schedules.

User Settings:

S

Yes/No to reset the user settings in the Advanced Setup to
factory default settings.

Install Settings:

S

Yes/No to reset install settings in Install/Service menus to factory
default settings.

Last 10 System Events:

S

Yes/No to reset last 10 events under Service Info menu.

Setup -- Furnace

Upon a first time start--up of the Evolution Control, the furnace
DIP switch settings will be copied to the furnace setup menu. Any

changes can then be made from the Evolution Control.

Furnace Airflow:

S

COMFORT (default)

S

EFFICIENCY

Selects the airflow of the furnace when heating.

EFFICIENCY

is

the airflow used to meet specified ratings,

COMFORT

is a

decreased airflow used to increase the output air temperature and

provide increased comfort.

Cooling Airflow:

S

COMFORT (default) -- cooling airflow is varied depending on
humidity and temperature demands settings. This selection
enables the full dehumidify and comfort capabilities of the
system. When COMFORT is not selected, the unit will not run
reduced airflows for dehumidification.

S

EFF 325 -- fixed airflow used to achieve specified ratings -- no
dehumidification airflow reduction. This is nominally 325
CFM/ton, but will vary if a 2--stage outdoor unit is used.

S

EFF 350 -- fixed airflow used to achieve specified ratings -- no
dehumidification airflow reduction. This is nominally 350
CFM/ton, but will vary if a 2--stage outdoor unit is used.

S

MAXIMUM -- 400 CFM/ton. No dehumidification airflow
reduction.

S

QUIET-- minimum cooling airflow that the system can safely
run (typically 300 CFM/ton). Use this setting if duct noise is a
severe problem. Note that duct sweating in high humidity
environments could be an issue.

Heat Pump Heating:

S

COMFORT (default) Heat Pump airflow is varied depending on
outdoor temperature to maximize comfort.

S

EFF 325 -- Fixed airflow used to achieve specified ratings . This
is nominally 325 CFM/ton, but will vary if a 2--stage outdoor
unit is used.

S

EFF 350 -- Fixed airflow used to achieve specified ratings . This
is nominally 350 CFM/ton, but will vary if a 2--stage outdoor
unit is used.

S

MAXIMUM -- 400 CFM/ton.

Heat Pump Cooling:

S

COMFORT (default) -- cooling airflow is varied depending on
humidity and temperature demands settings. This selection
enables the full dehumidify and comfort capabilities of the
system. When COMFORT is not selected, the unit will not run
reduced airflows for dehumidification.

UID

01

--

D

Содержание SYSTXBBUID01--D

Страница 1: ...tential for personal injury Understand the signal words DANGER WARNING and CAUTION These words are used with the safety alert symbol DANGER identifies the most serious hazards which will result in sev...

Страница 2: ...S In areas with poor air circulation such as behind a door or in an alcove Remote Room Sensor Option A Remote Room Sensor can be used with the Evolution Control to take the place of the User Interface...

Страница 3: ...To remove the control from the base insert a flat screw driver into each of the four slots two on each side and pry towards yourself to release the holding tabs Refer to Fig 7 to locate the slots A100...

Страница 4: ...ABCD connector will cause the Evolution System to operate improperly Check to make sure all wiring is correct before proceeding with installation or turning on power CAUTION 9 Push any excess wire int...

Страница 5: ...5 Fig 13 Power Up Sequence NOTE If the variable speed indoor equipment furnace or fan coil cannot be found the User Interface will display CANNOT COMMUNICATE WITH INDOOR UNIT This MUST be corrected be...

Страница 6: ...ress right side button to continue UV Lights Installed This screen will appear to select whether UV lights are installed on the system select YES or NO then press right side button to continue Equipme...

Страница 7: ...g temperature using the RIGHT Up Down button 7 Press the blue COOL button Cooling temperature will be gin flashing 8 Set the cooling temperature using the RIGHT Up Down button 9 Set the remaining peri...

Страница 8: ...ttings S Yes No to reset the user settings in the Advanced Setup to factory default settings Install Settings S Yes No to reset install settings in Install Service menus to factory default settings La...

Страница 9: ...supply products e g fresh air make up air dampers S FAN SPEED select Low Med High for all zones when G terminal is energized S SHUTDOWN shuts off fan and equipment when initiated This function is not...

Страница 10: ...alue limited by the model number of the fan coil If the electric heater is self identifying this value is not shown Elect Heat Lockout S NONE default S 5 to 55_F 15 to 13_C Outside temperature above w...

Страница 11: ...e settings YES NO HP TO FURNACE STAGING TIME Adjust the minimum amount of time the heat pump will run before furnace will be allowed to run S Default 15 MIN S Available settings 15 60 minutes If a dem...

Страница 12: ...own in Fig 28 CHECKOUT FURNACE HEAT PUMP HEATING HEAT PUMP COOLING HUMIDIFIER VENTILATOR BACK SELECT A03204 Fig 28 Checkout Menu Checkout Furnace or Gas PAC Make sure the furnace is properly installed...

Страница 13: ...S Seconds If a lockout timer is active this will show the current time value See furnace manual for details on lockout timers Service Fan Coil Status Electric Heat S OFF LOW MED HIGH Displays stages...

Страница 14: ...he same time for 3 seconds When keys are locked a lock symbol will appear in the upper left corner of screen Follow same procedure to unlock keypad Heat and Cool LED The Heat and Cool LEDs will pulsat...

Страница 15: ...ings ON and OFF If DEHUMIDIFY is set to ON factory default then the cooling unit will be allowed to overcool the space up to 3_F 2_C if the humidity level is above the cooling humidity target setpoint...

Страница 16: ...ectly to indoor unit with a short piece of thermostat wire Add other devices one at a time to determine where the communication issue exists Display says Outdoor Unit Not Found and I have a two stage...

Страница 17: ...e over as the system controller putting the regular system user interface to sleep The screen on the regular user interface will display IN SERVICE MODE The D model user interface will then learn all...

Страница 18: ...hange at any time specifications or designs without notice and without incurring obligations E2011 Bryant Heating Cooling Systems 7310 W Morris St Indianapolis IN 46231 Printed in China Edition Date 0...

Отзывы: