background image

—22—

Table 8 — Modular Platform D Unit Configuration Values

Only the current value being displayed is transmitted. Once

the Fan button is pressed, the room controller will switch to

displaying the configuration item number. To move to the

next setting, press the Mode button again and the “20” will

be displayed. Press the Up button and the display will

change to “21.” The Mode button will toggle the display

between the software configuration item number (i.e., “20,”

“21,” etc.) and the configuration value. The Up and Down

buttons will change either the item number or the value,

whichever is displayed at the time.
This mode will exit automatically after 30 seconds of

inactivity.

NOTE

: If units are grouped to one room controller, all units

will have the same configuration value.

VI. SERVICE TEST MODE

Prior to start-up, conduct the Service Test mode to ensure

the unit is ready for start-up.
There is a hidden Service Test mode that is initiated through

a combination of button presses when the remote is off. The

following buttons need to be pressed, in sequence, within

6 seconds: 

1. Down arrow
2. Fan button
3. Up arrow
4. Fan button
5. Mode button

Once in Service Test mode, the Service Test mode message

will be sent, and 

Sr

 will be displayed in the temperature

icons until the Down button is pressed. During Service Test

mode all the icons are off, and the only button that is active

is the Down button. To cancel Service Test mode, press the

Down button to send a message of Off mode to the unit. Ser-

vice Test mode automatically times out after 30 minutes and

the remote will operate normally.
When test mode is selected, the unit will operate as

described below:
• The Unit Status (Green) and Timer (Yellow) LEDs blink

every 2 seconds.

• The indoor fan will operate according to user-selected

speed. If user-selected speed is Auto, the fan will run in

High speed.

• If the unit is configured as an A/C Only unit, it will oper-

ate in cool mode with demand.

• If the unit is configured as a Heat Pump unit, the louver

will operate according to user-selected position. If user

selected louver is Auto, louver operates according to auto

heat or cool louver based on operating mode.

• The unit will run in cool mode for 3 minutes, then it will

run in heat mode for 2 minutes, or until the indoor coil is

greater than 104 F. The unit will run in cool mode until

test mode is exited.

Any of the following will cancel the Service Test mode:
• When the unit is turned off by the controller.

• If the power is cycled during the Test Mode, the unit will

return to its normal operating mode.

• After 30 minutes of receiving the last valid test request

message.

• Fail  Mode.

START-UP

The following checks should be made before system start-up.

Refer to outdoor unit Installation, Start-Up, and Service

manual for system start-up instructions and refrigerant

charging methods. Be sure to use the refrigerant charge

shown in Table 3.

1. Check condensate drainage system.

a. Remove grille and frame from the unit.
b. On the opposite side of the drain connection,

insert a water bottle up into the fan coil unit and

fill drain pan. Refer to Fig. 34. Water must flow

regularly with condensate pump energized. If

water does not, check the pipe slope or see if

there are any pipe restrictions.
NOTE: The unit is equipped with a safety float

switch to deenergize the compressor if the drain

water level gets too high.

2. Make sure that all wiring connections are correct and

that they are tight.

3. Make sure that all barriers, covers, and panels are in

place.

ITEM

VALUE

COMMENT

20

1: Heat Pump
0: AC only (indoor unit with 
or without electric heaters)

Unit Configuration 
defaults to heat pump

21

1-199 in increments of 1

CCN Address of the unit.
Defaults to 1.
To display the hundreds, 

push .

22

0-199 in increments of 1

Zone number - 
Communications zone 
the system is located in
Defaults to 0
To display the hundreds, 

push  

.

24

0: Start in Off mode
1: Start in last active mode

Auto Restart
Defaults to “On”

Room Controller
ON

up

down

Keep it pressed
for 5 seconds

To change
the value

Automatic
(AUTO)

Or

Continuous
movement
(swing)

Fig. 33 — Selecting the Louver Mode

Содержание 619FNF

Страница 1: ...llow all safety codes Wear safety glasses and work gloves Use quenching cloth for brazing operations Have fire extin guisher available Read these instructions thoroughly Con sult local building codes...

Страница 2: ...charged or under charged from the factory NAME SPECIFICATIONS Connection Pipe 619FNF018 024 FNQ01824 5 8 in Mixed Phase 3 8 in Liquid 619FNF FNQ03036 3 4 in Mixed Phase 3 8 in Liquid Wall Sleeve Wall...

Страница 3: ...4 8 7 3 15 16 100 5 29 32 150 1 10 5 8 575 0 2 1 4 3 4 0 8 2 1 1 5 2 2 4 6 5 5 8 2 0 1 4 3 5 1 6 3 4 6 1 1 1 1 2 13 64 56 2 52 1 10 5 8 575 8 5 1 2 3 7 7 0 3 8 9 0 5 1 2 3 9 2 5 2 3 14 70 8 9 2 4 3 1...

Страница 4: ...18 18 18 Circuits 5 6 10 10 FILTERS Cleanable Quantity Size in 1 17 x 16 AIRSWEEP Horizontal Auto Preset OPERATING LIMITS Cooling Min Max 55 F 125 F CONTROLS Integrated Microprocessor Remote Controlle...

Страница 5: ...4 6 4 6 No of Rows 2 2 3 3 Fins in 18 18 18 18 Circuits 6 6 10 10 FILTERS Cleanable Quantity Size in 1 24 x 235 16 AIRSWEEP Horizontal Auto Preset OPERATING LIMITS Heating Min Max 15 F 75 F Cooling M...

Страница 6: ...ith the unit may be used as a guide Depending on the type of ceiling the hangers can be fixed as shown in Fig 5 Once the threaded hangers have been positioned do not tighten the nuts Insert the washer...

Страница 7: ...the frame in to position See Fig 12 Ensure that the frame is not distorted by excessive tighten ing that it is aligned with the false ceiling and that there is a seal between the air inlet and outlet...

Страница 8: ...e or other tem perature radiating object that may cause a false reading Do not locate close to or in direct airflow of a heating or cooling supply Do not locate in areas with poor circulation such as...

Страница 9: ...extend through the hole in the mounting base Adjust the length and routing of each wire to reach the proper terminal in the connector block on the mounting base with 1 4 in of extra wire strip only 1...

Страница 10: ...able 5 Refer to Fig 20 Table 5 Tightening Torque B Piping Connection to the Unit Use two wrenches to tighten all connections Once all connections have been completed check for leaks using soapy water...

Страница 11: ...e unit shall be fuse or equipped with a breaker Table 6B 619FNQ Fan Coil Electrical Data LEGEND Permissible limits of the voltage range at which unit will operate satisfactorily NOTE In compliance wit...

Страница 12: ...Room Controller Connections Ground Connection Outdoor Unit Connections Low Voltage High Voltage Power Connections Fig 21 619FNF Unit Matched to 538ENF Outdoor Unit Wiring Connection Cooling Only Syst...

Страница 13: ...ltage High Voltage Room Controller Connections Outdoor Unit Connections Power Connections Ground Connection Fig 22 619FNQ Unit Matched to 538ENF Outdoor Unit Wiring Connection Cooling with Electric He...

Страница 14: ...14 Low Voltage High Voltage Room Controller Connections Ground Connection Outdoor Unit Connections Power Connections Fig 23 619FNQ Unit Matched to 538QNF Outdoor Unit Wiring Connection Heat Pump Syste...

Страница 15: ...ch OFM Outdoor Fan Motor OL Overload S Emergency TB Terminal Block TM Sensor TRAN Transformer Terminal Marked Terminal Unmarked Splice Terminal Block Factory Wiring Field Control Wiring Field Power Wi...

Страница 16: ...Louver Motor LMS Louver Micro Switch OFM Outdoor Fan Motor OL Overload S Emergency ST Safety Thermostat TB Terminal Block TM Sensor TRAN Transformer Terminal Marked Terminal Unmarked Splice Terminal...

Страница 17: ...est Point LLPS Liquid Low Pressure Switch LM Louver Motor LMS Louver Micro Switch OAS Outdoor Air Sensor OFM Outdoor Fan Motor OFR Outdoor Fan Relay OL Overload RVS Reversing Valve Solenoid S Emergenc...

Страница 18: ...ctric heater Transformer Holes for fixing panel in position Emergency push button Fan connector LED RECEIVER connector Float connector Pump connector Louver connector CP CG CA CV CLR INTERNAL CONTROL...

Страница 19: ...orrugated aluminum externally covered with anti condensate material fiberglass from 1 4 in to 1 in thickness 5 Use Fig 31 to determine the allowable static pres sure loss for the ductwork airflow The...

Страница 20: ...m C 2 3 4 70 mm 3 15 16 100 mm 4 14 105 1 93 49 8 50 216 Note Dimensions in are in mm Fig 30 Installation Options NOTE Dimensions in are in mm Supply air duct to adjacent room Airflow cfm e r u s s e...

Страница 21: ...C Temperatures will be displayed in degrees Celsius F Temperatures will be displayed in degrees Fahrenheit IV LOUVER MODE SELECTION To enter louver mode selection ensure the room controller is on and...

Страница 22: ...unit is configured as a Heat Pump unit the louver will operate according to user selected position If user selected louver is Auto louver operates according to auto heat or cool louver based on operat...

Страница 23: ...shes at intervals of 0 5 sec onds The fault code is deduced from the number of times the green LED flashes blocking unit operation Between one flash cycle and the next one a pause of 5 seconds elapses...

Страница 24: ...right 2006 Bryant Heating Cooling Systems Printed in U S A CATALOG NO 02 619F0001 II Green LED Red LED Yellow LED Remote control signal receiver Emergency Button Fig 35 Warning Lamps and Emergency But...

Отзывы: