background image

—10—

IV. STEP 4 — COMPLETE REFRIGERANT PIPING
CONNECTIONS

IMPORTANT: 

During unit installation make the refrigerant

connections first and then the electrical connections. If the

unit is uninstalled, disconnect the electrical cables first and

then the refrigerant connections. Refer to the outdoor unit

installation instructions for tube sizing and limitations.
Use field-supplied refrigerant grade piping designed for use

with R-410A refrigerant.

A. Flaring the Ends of Pipes

Remove the protective caps from the copper pipe ends. Hold-

ing the tube downward, cut the extreme end off, removing

any copper shavings with a deburring blade. Remove the

flare nuts from the “FLARE” connection body of the indoor

unit  and  insert  them  into  the  pipes.  Make  the  flare  to  the

pipe end with the proper flaring tool. The flare end must not

have any burrs or imperfections. The length of the flared

walls must be uniform. See Fig. 18 and 19.
Lubricate the end of pipe and the thread of the flare connec-

tion with anti-freeze oil. Tighten by hand and then use two

wrenches to tighten all connections fully, applying the tight-

ening torque shown in Table 5. Refer to Fig. 20.

Table 5 — Tightening Torque

B. Piping Connection to the Unit

Use two wrenches to tighten all connections.

Once all connections have been completed, check for leaks

using soapy water. If no leaks were found, wrap connections

with anti-condensate insulation and tighten with tape, with-

out exerting excessive pressure on the insulation. Repair and

cover any possible cracks in the insulation.

If either refrigerant tubing or indoor coil is exposed to the

atmosphere, the system must be evacuated following good

refrigeration practices.

TUBE DIAMETER 

(in.)

TORQUE

 (ft-lb)

3

/

8

 in.

31

5

/

8

 in.

48

3

/

4

 in.

74

CAUTION: 

 

Insufficient tightening torque could

cause a refrigerant leak from the connection. Excessive

tightening torque will damage the pipe flare.

CAUTION: 

 

DO NOT BURY MORE THAN 36 IN.

OF REFRIGERANT PIPE IN THE GROUND. If any

section of pipe is buried, there must be a 6-in. vertical

rise to the valve connections on the outdoor unit. If

more than the recommended length is buried, refriger-

ant may migrate to cooler, buried section during

extended periods of system shutdown. This causes

refrigerant slugging and could possibly damage the

compressor at start-up.

L

L

Adjustable wrench or torque wrench

Outdoor end
Indoor end

3

1

2

Fig. 18 — Removing Burrs

Fig. 19 — Flared Walls are Equal

Fig. 20 — Tightening Connections

Содержание 619FNF

Страница 1: ...llow all safety codes Wear safety glasses and work gloves Use quenching cloth for brazing operations Have fire extin guisher available Read these instructions thoroughly Con sult local building codes...

Страница 2: ...charged or under charged from the factory NAME SPECIFICATIONS Connection Pipe 619FNF018 024 FNQ01824 5 8 in Mixed Phase 3 8 in Liquid 619FNF FNQ03036 3 4 in Mixed Phase 3 8 in Liquid Wall Sleeve Wall...

Страница 3: ...4 8 7 3 15 16 100 5 29 32 150 1 10 5 8 575 0 2 1 4 3 4 0 8 2 1 1 5 2 2 4 6 5 5 8 2 0 1 4 3 5 1 6 3 4 6 1 1 1 1 2 13 64 56 2 52 1 10 5 8 575 8 5 1 2 3 7 7 0 3 8 9 0 5 1 2 3 9 2 5 2 3 14 70 8 9 2 4 3 1...

Страница 4: ...18 18 18 Circuits 5 6 10 10 FILTERS Cleanable Quantity Size in 1 17 x 16 AIRSWEEP Horizontal Auto Preset OPERATING LIMITS Cooling Min Max 55 F 125 F CONTROLS Integrated Microprocessor Remote Controlle...

Страница 5: ...4 6 4 6 No of Rows 2 2 3 3 Fins in 18 18 18 18 Circuits 6 6 10 10 FILTERS Cleanable Quantity Size in 1 24 x 235 16 AIRSWEEP Horizontal Auto Preset OPERATING LIMITS Heating Min Max 15 F 75 F Cooling M...

Страница 6: ...ith the unit may be used as a guide Depending on the type of ceiling the hangers can be fixed as shown in Fig 5 Once the threaded hangers have been positioned do not tighten the nuts Insert the washer...

Страница 7: ...the frame in to position See Fig 12 Ensure that the frame is not distorted by excessive tighten ing that it is aligned with the false ceiling and that there is a seal between the air inlet and outlet...

Страница 8: ...e or other tem perature radiating object that may cause a false reading Do not locate close to or in direct airflow of a heating or cooling supply Do not locate in areas with poor circulation such as...

Страница 9: ...extend through the hole in the mounting base Adjust the length and routing of each wire to reach the proper terminal in the connector block on the mounting base with 1 4 in of extra wire strip only 1...

Страница 10: ...able 5 Refer to Fig 20 Table 5 Tightening Torque B Piping Connection to the Unit Use two wrenches to tighten all connections Once all connections have been completed check for leaks using soapy water...

Страница 11: ...e unit shall be fuse or equipped with a breaker Table 6B 619FNQ Fan Coil Electrical Data LEGEND Permissible limits of the voltage range at which unit will operate satisfactorily NOTE In compliance wit...

Страница 12: ...Room Controller Connections Ground Connection Outdoor Unit Connections Low Voltage High Voltage Power Connections Fig 21 619FNF Unit Matched to 538ENF Outdoor Unit Wiring Connection Cooling Only Syst...

Страница 13: ...ltage High Voltage Room Controller Connections Outdoor Unit Connections Power Connections Ground Connection Fig 22 619FNQ Unit Matched to 538ENF Outdoor Unit Wiring Connection Cooling with Electric He...

Страница 14: ...14 Low Voltage High Voltage Room Controller Connections Ground Connection Outdoor Unit Connections Power Connections Fig 23 619FNQ Unit Matched to 538QNF Outdoor Unit Wiring Connection Heat Pump Syste...

Страница 15: ...ch OFM Outdoor Fan Motor OL Overload S Emergency TB Terminal Block TM Sensor TRAN Transformer Terminal Marked Terminal Unmarked Splice Terminal Block Factory Wiring Field Control Wiring Field Power Wi...

Страница 16: ...Louver Motor LMS Louver Micro Switch OFM Outdoor Fan Motor OL Overload S Emergency ST Safety Thermostat TB Terminal Block TM Sensor TRAN Transformer Terminal Marked Terminal Unmarked Splice Terminal...

Страница 17: ...est Point LLPS Liquid Low Pressure Switch LM Louver Motor LMS Louver Micro Switch OAS Outdoor Air Sensor OFM Outdoor Fan Motor OFR Outdoor Fan Relay OL Overload RVS Reversing Valve Solenoid S Emergenc...

Страница 18: ...ctric heater Transformer Holes for fixing panel in position Emergency push button Fan connector LED RECEIVER connector Float connector Pump connector Louver connector CP CG CA CV CLR INTERNAL CONTROL...

Страница 19: ...orrugated aluminum externally covered with anti condensate material fiberglass from 1 4 in to 1 in thickness 5 Use Fig 31 to determine the allowable static pres sure loss for the ductwork airflow The...

Страница 20: ...m C 2 3 4 70 mm 3 15 16 100 mm 4 14 105 1 93 49 8 50 216 Note Dimensions in are in mm Fig 30 Installation Options NOTE Dimensions in are in mm Supply air duct to adjacent room Airflow cfm e r u s s e...

Страница 21: ...C Temperatures will be displayed in degrees Celsius F Temperatures will be displayed in degrees Fahrenheit IV LOUVER MODE SELECTION To enter louver mode selection ensure the room controller is on and...

Страница 22: ...unit is configured as a Heat Pump unit the louver will operate according to user selected position If user selected louver is Auto louver operates according to auto heat or cool louver based on operat...

Страница 23: ...shes at intervals of 0 5 sec onds The fault code is deduced from the number of times the green LED flashes blocking unit operation Between one flash cycle and the next one a pause of 5 seconds elapses...

Страница 24: ...right 2006 Bryant Heating Cooling Systems Printed in U S A CATALOG NO 02 619F0001 II Green LED Red LED Yellow LED Remote control signal receiver Emergency Button Fig 35 Warning Lamps and Emergency But...

Отзывы: