background image

—11—

V. STEP 5 — MAKE ELECTRICAL CONNECTIONS  

See Tables 6A and 6B for electrical information.

A. Units With Electric Heater

The unit is equipped with two thermostats: one with auto-

matic reset and one with manual (electric) reset that can be

reactivated by switching the power supply off and then

back on.

B. Power Wiring (Fig. 21-26)

The unit is factory wired for voltage shown on nameplate.

Provide adequate, fused disconnect switch within sight from

unit, readily accessible, but out of reach of children. Provi-

sion for locking the switch open (off) is advisable to prevent

power from being turned on while unit is being serviced. Dis-

connect switch, fuses, and field wiring must comply with the

NEC and local code requirements. Use copper wire only

between the disconnect switch and unit. Use minimum 60 C

wire for the field power connection.
Remove the external box cover. Route the low voltage wires

from the outdoor unit to the indoor unit: 

1. Place wiring through 

7

/

8

 in. knockouts on the left or

right hand side of external control box (low voltage

side). 

2. Connect the R and Y wires to the 2 pin terminal block

for cooling only units (619FNF) and heat pump units

(619FNQ) that are matched to 538ENF outdoor units.

3. Connect the R, Y, O, G, DT, A, and B wires to the

(PGB-1) 1 terminal for 619FNQ indoor units matched

with 538QNF outdoor units.

Route the line power leads from the indoor disconnect to the

fan coil unit.

1. Place wiring through 

7

/

8

 in. or 1

1

/

8

 in. knockouts on

the left and on the right hand side of external control

box (high voltage side).

2. Connect L1 to the black wire and L2 to the red wire

using wire nuts and fix the ground wire between the

2 washers.

See Fig. 27 for a view of the internal control panel. The inter-

nal control panel can be accessed by opening the grille and

removing the metal cover attached by four screws.

NOTE:

 The internal control panel does not need to be

accessed during the installation process unless there is a

need for service.

Table 6A — 619FNF Fan Coil Electrical Data

LEGEND

*Permissible limits of the voltage range at which unit will operate

satisfactorily.

NOTE:

 In compliance with NEC requirements for multimotor and combina-

tion load equipment (refer to NEC Articles 430 and 440), the overcurrent pro-
tective device for the unit shall be fuse or equipped with a breaker.

Table 6B — 619FNQ Fan Coil Electrical Data

LEGEND

*Permissible limits of the voltage range at which unit will operate

satisfactorily.

NOTE:

 In compliance with NEC requirements for multimotor and combina-

tion load equipment (refer to NEC Articles 430 and 440), the overcurrent pro-
tective device for the unit shall be fuse or equipped with a breaker.

WARNING: 

 

Unit cabinet must have an uninter-

rupted, unbroken electrical ground to minimize the

possibility of personal injury if an electrical fault

should occur. This ground may consist of electrical

wire connected to unit ground lug in control compart-

ment, or conduit approved for electrical ground when

installed in accordance with NEC, and local electrical

codes. Failure to follow this warning could result in the

installer being liable for the personal injury of others.

CAUTION: 

 

Unit failure as a result of operation on

improper line voltage or excessive phase imbalance

constitutes abuse and may cause damage to electrical

components. Such operation would invalidate any

applicable Bryant warranty.

WARNING: 

 

Electrical shock can cause personal

injury and death. Shut off all power to this equipment

during installation. There may be more than one dis-

connect switch. Tag all disconnect locations to alert

others not to restore power until work is completed.

SYSTEM  

SIZE

V-PH-Hz

VOLTAGE 

RANGE*

FAN

CONDENSATE 

PUMP FLA

LOUVER 

MOTOR FLA

POWER

MIN WIRE 

SIZE

AWG

Min

Max

FLA

Motor  Power

(Watts)

MCA

MOCP

018

208/230-1-60

187

253

0.55

120

0.06

0.01

0.8

15

14

024

208/230-1-60

187

253

0.50

110

0.06

0.01

0.7

15

14

030

208/230-1-60

187

253

0.95

210

0.06

0.01

1.3

15

14

036

208/230-1-60

187

253

0.95

210

0.06

0.01

1.3

15

14

AWG

American Wire Gage

FLA

Full Load Amps

MCA

Minimum Circuit Amps per NEC Section 430-24

MOCP —

Maximum Overcurrent Protection

NEC

National Electrical Code

 SYSTEM 

SIZE

V-PH-Hz

VOLTAGE 

RANGE*

FAN

CONDENSATE 

PUMP FLA

LOUVER 

MOTOR FLA

ELECTRIC 

HEATERS

POWER

MIN 

WIRE 

SIZE

AWG

Min

Max

FLA

Motor Power

(Watts)

kW

FLA

MCA

MOCP

018

208/230-1-60

187

253

0.50

110.0

0.06

0.01

3

12.5

16.3

20

12

024

208/230-1-60

187

253

0.50

110.0

0.06

0.01

3

12.5

16.3

20

12

030

208/230-1-60

187

253

0.95

210.0

0.06

0.01

3

12.5

16.9

20

12

036

208/230-1-60

187

253

0.95

210.0

0.06

0.01

3

12.5

16.9

20

12

AWG

American Wire Gage

FLA

Full Load Amps

MCA

Minimum Circuit Amps per NEC Section 430-24

MOCP —

Maximum Overcurrent Protection

NEC

National Electrical Code

Содержание 619FNF

Страница 1: ...llow all safety codes Wear safety glasses and work gloves Use quenching cloth for brazing operations Have fire extin guisher available Read these instructions thoroughly Con sult local building codes...

Страница 2: ...charged or under charged from the factory NAME SPECIFICATIONS Connection Pipe 619FNF018 024 FNQ01824 5 8 in Mixed Phase 3 8 in Liquid 619FNF FNQ03036 3 4 in Mixed Phase 3 8 in Liquid Wall Sleeve Wall...

Страница 3: ...4 8 7 3 15 16 100 5 29 32 150 1 10 5 8 575 0 2 1 4 3 4 0 8 2 1 1 5 2 2 4 6 5 5 8 2 0 1 4 3 5 1 6 3 4 6 1 1 1 1 2 13 64 56 2 52 1 10 5 8 575 8 5 1 2 3 7 7 0 3 8 9 0 5 1 2 3 9 2 5 2 3 14 70 8 9 2 4 3 1...

Страница 4: ...18 18 18 Circuits 5 6 10 10 FILTERS Cleanable Quantity Size in 1 17 x 16 AIRSWEEP Horizontal Auto Preset OPERATING LIMITS Cooling Min Max 55 F 125 F CONTROLS Integrated Microprocessor Remote Controlle...

Страница 5: ...4 6 4 6 No of Rows 2 2 3 3 Fins in 18 18 18 18 Circuits 6 6 10 10 FILTERS Cleanable Quantity Size in 1 24 x 235 16 AIRSWEEP Horizontal Auto Preset OPERATING LIMITS Heating Min Max 15 F 75 F Cooling M...

Страница 6: ...ith the unit may be used as a guide Depending on the type of ceiling the hangers can be fixed as shown in Fig 5 Once the threaded hangers have been positioned do not tighten the nuts Insert the washer...

Страница 7: ...the frame in to position See Fig 12 Ensure that the frame is not distorted by excessive tighten ing that it is aligned with the false ceiling and that there is a seal between the air inlet and outlet...

Страница 8: ...e or other tem perature radiating object that may cause a false reading Do not locate close to or in direct airflow of a heating or cooling supply Do not locate in areas with poor circulation such as...

Страница 9: ...extend through the hole in the mounting base Adjust the length and routing of each wire to reach the proper terminal in the connector block on the mounting base with 1 4 in of extra wire strip only 1...

Страница 10: ...able 5 Refer to Fig 20 Table 5 Tightening Torque B Piping Connection to the Unit Use two wrenches to tighten all connections Once all connections have been completed check for leaks using soapy water...

Страница 11: ...e unit shall be fuse or equipped with a breaker Table 6B 619FNQ Fan Coil Electrical Data LEGEND Permissible limits of the voltage range at which unit will operate satisfactorily NOTE In compliance wit...

Страница 12: ...Room Controller Connections Ground Connection Outdoor Unit Connections Low Voltage High Voltage Power Connections Fig 21 619FNF Unit Matched to 538ENF Outdoor Unit Wiring Connection Cooling Only Syst...

Страница 13: ...ltage High Voltage Room Controller Connections Outdoor Unit Connections Power Connections Ground Connection Fig 22 619FNQ Unit Matched to 538ENF Outdoor Unit Wiring Connection Cooling with Electric He...

Страница 14: ...14 Low Voltage High Voltage Room Controller Connections Ground Connection Outdoor Unit Connections Power Connections Fig 23 619FNQ Unit Matched to 538QNF Outdoor Unit Wiring Connection Heat Pump Syste...

Страница 15: ...ch OFM Outdoor Fan Motor OL Overload S Emergency TB Terminal Block TM Sensor TRAN Transformer Terminal Marked Terminal Unmarked Splice Terminal Block Factory Wiring Field Control Wiring Field Power Wi...

Страница 16: ...Louver Motor LMS Louver Micro Switch OFM Outdoor Fan Motor OL Overload S Emergency ST Safety Thermostat TB Terminal Block TM Sensor TRAN Transformer Terminal Marked Terminal Unmarked Splice Terminal...

Страница 17: ...est Point LLPS Liquid Low Pressure Switch LM Louver Motor LMS Louver Micro Switch OAS Outdoor Air Sensor OFM Outdoor Fan Motor OFR Outdoor Fan Relay OL Overload RVS Reversing Valve Solenoid S Emergenc...

Страница 18: ...ctric heater Transformer Holes for fixing panel in position Emergency push button Fan connector LED RECEIVER connector Float connector Pump connector Louver connector CP CG CA CV CLR INTERNAL CONTROL...

Страница 19: ...orrugated aluminum externally covered with anti condensate material fiberglass from 1 4 in to 1 in thickness 5 Use Fig 31 to determine the allowable static pres sure loss for the ductwork airflow The...

Страница 20: ...m C 2 3 4 70 mm 3 15 16 100 mm 4 14 105 1 93 49 8 50 216 Note Dimensions in are in mm Fig 30 Installation Options NOTE Dimensions in are in mm Supply air duct to adjacent room Airflow cfm e r u s s e...

Страница 21: ...C Temperatures will be displayed in degrees Celsius F Temperatures will be displayed in degrees Fahrenheit IV LOUVER MODE SELECTION To enter louver mode selection ensure the room controller is on and...

Страница 22: ...unit is configured as a Heat Pump unit the louver will operate according to user selected position If user selected louver is Auto louver operates according to auto heat or cool louver based on operat...

Страница 23: ...shes at intervals of 0 5 sec onds The fault code is deduced from the number of times the green LED flashes blocking unit operation Between one flash cycle and the next one a pause of 5 seconds elapses...

Страница 24: ...right 2006 Bryant Heating Cooling Systems Printed in U S A CATALOG NO 02 619F0001 II Green LED Red LED Yellow LED Remote control signal receiver Emergency Button Fig 35 Warning Lamps and Emergency But...

Отзывы: