background image

—21—

III. ROOM CONTROLLER CONFIGURATION SETUP

To configure the room controller, press the Mode button for

5 seconds. After 5 seconds, “10” will appear. This indicates

that the user is setting the first software configuration item.

To display the value of configuration item 10, press the Mode

button again. The value of the Heat/Cool vs Cooling only

remote configuration will be displayed along with the “Set

Temp” icon to indicate that the number displayed is the con-

figuration data. Refer to Table 7 for configuration values. To

change the Heat/Cool vs Cooling only remote Configuration,

press the Up and Down buttons. To move to the next setting,

press the Mode button again and the “10” will be displayed.

Press the up button and the display will change to “11.”

Refer to Fig. 32. The Mode button will toggle the display

between the items and the configuration value. The Up and

Down buttons will change either the index or the value,

whichever is displayed at the time. Press the Fan button to

exit the Configuration Setup Mode. This mode will exit auto-

matically after 10 seconds of inactivity. Once a configuration

value is changed, the last value displayed will be the new

configuration value for the room controller.

NOTE

: The only way to abort a configuration change is to

change the value back to its original value.

Table 7 — Room Controller Configuration Values

* Factory default.

1. Configuration Item 10: Heat Pump vs Cooling Mode

H — The Room Controller will allow and display the

following modes:

•Off

•Fan

•Auto

•Cool

•Dry

•Heat

C — The Room Controller will allow and display the

following modes: 

•Off

•Fan

•Cool

•Dry

2. Configuration Item 11: Room Thermistor Override

On — Room Thermistor Override is active. Units will

be controlled to the air temperature displayed via the

Room Controller.
Of (Off) — Room Thermistor Override is not active.

All units will be controlled to the room air ther-

mistors located on the units.

3. Configuration Item 12: Celsius vs Fahrenheit

C — Temperatures will be displayed in degrees

Celsius.
F — Temperatures will be displayed in degrees

Fahrenheit.

IV. LOUVER MODE SELECTION

To enter louver mode selection, ensure the room controller is

on and then press the Fan button for 5 seconds. After 5 sec-

onds, the selected louver setting will be displayed. Press the

up and down arrows to modify the louver setting between

swing and auto. Refer to Fig. 33. The two settings will be dis-

played as follows:

The fan icon will also be displayed in the louver mode. Press

Fan button to exit the Louver Mode selection. This mode will

exit automatically after 10 seconds of inactivity. The only

way to abort a louver change is to change the value back to

its original value.

NOTE:

 If units are grouped to one room controller, all units

will have the same louver value. Louver Mode selection is

not available during OFF mode.

V. MAIN BOARD CONFIGURATION

To configure the main electronic board, push the Up and

Down arrows for 5 seconds while the room controller is off.
After 5 seconds, a “20” will appear. This indicates that the

user is setting the first software configuration item. To check

the value of configuration item “20,” press the Mode button.

The value for the Heat Pump/AC Only configuration will be

displayed. To change the value, use the Up and Down

buttons. Once the desired value is selected, press the Fan

button to send that configuration data to the unit. Refer to

Table 8.

ITEM

VALUE

DESCRIPTION

10

H*

Heat/Cool Remote

C

Cooling Only Remote

11

On

Room Thermistor Override 
Active.

Of*

Control and display room air 
temperature at the room con-
troller. Room Thermistor Over-
ride Inactive. Do not display 
room air temperature at the 
room controller and control to 
unit room air thermistor(s).

12

C*

Temperatures displayed in 
degrees Celsius.

F

Temperatures displayed in 
degrees Fahrenheit.

S with Swing Louver Icon

Represents the swing louver

A with Auto Louver Icon

Represents the auto louver

Keep it pressed for
at least 5 seconds

Check the
value

Change the
value

up

down

Next
item

up

down

To check/change
the values of items
11 and 12 go back
to point 

A

A

Fig. 32 — Room Controller Configuration Steps

Содержание 619FNF

Страница 1: ...llow all safety codes Wear safety glasses and work gloves Use quenching cloth for brazing operations Have fire extin guisher available Read these instructions thoroughly Con sult local building codes...

Страница 2: ...charged or under charged from the factory NAME SPECIFICATIONS Connection Pipe 619FNF018 024 FNQ01824 5 8 in Mixed Phase 3 8 in Liquid 619FNF FNQ03036 3 4 in Mixed Phase 3 8 in Liquid Wall Sleeve Wall...

Страница 3: ...4 8 7 3 15 16 100 5 29 32 150 1 10 5 8 575 0 2 1 4 3 4 0 8 2 1 1 5 2 2 4 6 5 5 8 2 0 1 4 3 5 1 6 3 4 6 1 1 1 1 2 13 64 56 2 52 1 10 5 8 575 8 5 1 2 3 7 7 0 3 8 9 0 5 1 2 3 9 2 5 2 3 14 70 8 9 2 4 3 1...

Страница 4: ...18 18 18 Circuits 5 6 10 10 FILTERS Cleanable Quantity Size in 1 17 x 16 AIRSWEEP Horizontal Auto Preset OPERATING LIMITS Cooling Min Max 55 F 125 F CONTROLS Integrated Microprocessor Remote Controlle...

Страница 5: ...4 6 4 6 No of Rows 2 2 3 3 Fins in 18 18 18 18 Circuits 6 6 10 10 FILTERS Cleanable Quantity Size in 1 24 x 235 16 AIRSWEEP Horizontal Auto Preset OPERATING LIMITS Heating Min Max 15 F 75 F Cooling M...

Страница 6: ...ith the unit may be used as a guide Depending on the type of ceiling the hangers can be fixed as shown in Fig 5 Once the threaded hangers have been positioned do not tighten the nuts Insert the washer...

Страница 7: ...the frame in to position See Fig 12 Ensure that the frame is not distorted by excessive tighten ing that it is aligned with the false ceiling and that there is a seal between the air inlet and outlet...

Страница 8: ...e or other tem perature radiating object that may cause a false reading Do not locate close to or in direct airflow of a heating or cooling supply Do not locate in areas with poor circulation such as...

Страница 9: ...extend through the hole in the mounting base Adjust the length and routing of each wire to reach the proper terminal in the connector block on the mounting base with 1 4 in of extra wire strip only 1...

Страница 10: ...able 5 Refer to Fig 20 Table 5 Tightening Torque B Piping Connection to the Unit Use two wrenches to tighten all connections Once all connections have been completed check for leaks using soapy water...

Страница 11: ...e unit shall be fuse or equipped with a breaker Table 6B 619FNQ Fan Coil Electrical Data LEGEND Permissible limits of the voltage range at which unit will operate satisfactorily NOTE In compliance wit...

Страница 12: ...Room Controller Connections Ground Connection Outdoor Unit Connections Low Voltage High Voltage Power Connections Fig 21 619FNF Unit Matched to 538ENF Outdoor Unit Wiring Connection Cooling Only Syst...

Страница 13: ...ltage High Voltage Room Controller Connections Outdoor Unit Connections Power Connections Ground Connection Fig 22 619FNQ Unit Matched to 538ENF Outdoor Unit Wiring Connection Cooling with Electric He...

Страница 14: ...14 Low Voltage High Voltage Room Controller Connections Ground Connection Outdoor Unit Connections Power Connections Fig 23 619FNQ Unit Matched to 538QNF Outdoor Unit Wiring Connection Heat Pump Syste...

Страница 15: ...ch OFM Outdoor Fan Motor OL Overload S Emergency TB Terminal Block TM Sensor TRAN Transformer Terminal Marked Terminal Unmarked Splice Terminal Block Factory Wiring Field Control Wiring Field Power Wi...

Страница 16: ...Louver Motor LMS Louver Micro Switch OFM Outdoor Fan Motor OL Overload S Emergency ST Safety Thermostat TB Terminal Block TM Sensor TRAN Transformer Terminal Marked Terminal Unmarked Splice Terminal...

Страница 17: ...est Point LLPS Liquid Low Pressure Switch LM Louver Motor LMS Louver Micro Switch OAS Outdoor Air Sensor OFM Outdoor Fan Motor OFR Outdoor Fan Relay OL Overload RVS Reversing Valve Solenoid S Emergenc...

Страница 18: ...ctric heater Transformer Holes for fixing panel in position Emergency push button Fan connector LED RECEIVER connector Float connector Pump connector Louver connector CP CG CA CV CLR INTERNAL CONTROL...

Страница 19: ...orrugated aluminum externally covered with anti condensate material fiberglass from 1 4 in to 1 in thickness 5 Use Fig 31 to determine the allowable static pres sure loss for the ductwork airflow The...

Страница 20: ...m C 2 3 4 70 mm 3 15 16 100 mm 4 14 105 1 93 49 8 50 216 Note Dimensions in are in mm Fig 30 Installation Options NOTE Dimensions in are in mm Supply air duct to adjacent room Airflow cfm e r u s s e...

Страница 21: ...C Temperatures will be displayed in degrees Celsius F Temperatures will be displayed in degrees Fahrenheit IV LOUVER MODE SELECTION To enter louver mode selection ensure the room controller is on and...

Страница 22: ...unit is configured as a Heat Pump unit the louver will operate according to user selected position If user selected louver is Auto louver operates according to auto heat or cool louver based on operat...

Страница 23: ...shes at intervals of 0 5 sec onds The fault code is deduced from the number of times the green LED flashes blocking unit operation Between one flash cycle and the next one a pause of 5 seconds elapses...

Страница 24: ...right 2006 Bryant Heating Cooling Systems Printed in U S A CATALOG NO 02 619F0001 II Green LED Red LED Yellow LED Remote control signal receiver Emergency Button Fig 35 Warning Lamps and Emergency But...

Отзывы: