Table 5 — Electrical Data
INDOOR
UNIT
619E
V (Single-
Ph, 60 Hz)
OPERATING VOLTAGE*
FAN
WATTS
MCA
MAX FUSE
OR HACR TYPE
CKT BKR AMPS
Max
Min
LRA
FLA
018†
208/230
253
187
3.2
0.53
94
0.66
15
024†
018**
024**
LEGEND
FLA
— Full Load Amps
HACR — Heating, Air Conditioning, and Refrigeration
LRA
— Locked Rotor Amps
MCA
— Minimum Circuit Amps per NEC Section 430-24
NEC
— National Electrical Code
*Permissible limits of the voltage range at which unit will operate
satisfactorily.
†Cooling only units.
**Heat pump units.
VII. MAKE CONNECTIONS TO THE OUTDOOR UNIT
A. Cooling-Only Systems
To connect the 538A or 538S condensing unit to the fan coil
unit(s) so that the system will operate correctly:
Route 2 field-supplied wires of 18-gage AWG (American Wire
Gage) thermostat cable between the low-voltage terminal block
of the fan coil unit (TB2) and the 538A or 538S unit low-
voltage terminal block. Connect the wires between terminals
Y and Y and between terminals C and C.
B. Heat Pump Systems
To connect the 538B heat pump unit to the fan coil unit so
that the system will operate correctly:
IMPORTANT:
DO NOT RUN THE THERMISTOR CABLE IN
THE SAME CONDUIT AS THE POWER WIRING.
1. One thermistor connection cord with a lead length of
24 ft is shipped with the 619E heat pump fan coil unit.
Run the connection cord from the low-voltage terminal
board in the control box in the fan coil unit (TB3) to the
heat pump unit. Route the wire carefully so that it will
not be damaged.
2. For cooling operation, route 2 field-supplied wires of
18-gage AWG (American Wire Gage) thermostat cable
between the low-voltage terminal block of the fan coil
unit (TB2) and the 538B unit low-voltage terminal block.
Connect the wires between terminals Y and Y and be-
tween terminals C and C.
3. For heating operation, route 3 additional wires of
18-gage AWG thermostat cable between the low-voltage
terminal block of the fan coil unit (TB2) and the 538B
unit low-voltage terminal block. Connect the wires be-
tween terminals R and R, O and O, and G and G.
VIII. INSTALL FAN COIL UNIT ONTO MOUNTING BRACKET
1. Hook the fan coil unit onto the top of the mounting bracket.
See Fig. 16.
2. Snap the fan coil unit onto the mounting bracket as shown
in Fig. 16.
IMPORTANT:
An audible snapping sound will be heard as the
hook on the unit is secured into the hole on the mounting
bracket. Be sure unit is correctly mounted.
Fig. 15 — High Voltage Connections
—8—