background image

change operating speeds depending on the room tempera-
ture. If the room temperature is below the set point, the
indoor fan will run at ultra-low speed, and the compressor
could run for up to 4 minutes. (Ultra-low speed is a control-
driven speed [not user configurable] used to sample the space
when the fan would normally be off.) The reversing valve
(619E heat pump units only) will be on. The compressor
cannot run for 3 minutes from the time the system starts
up or for 3 minutes from the time the compressor last
operated.

Initial Operation — When the mode is first selected, one of
the following occurs:

1. If the room temperature is above or equal to the se-

lected temperature, the unit will operate for 16 min-
utes, and the compressor and outdoor fan will operate.
The indoor fan will operate as in the cooling mode. Af-
ter 16 minutes of operation (or when the room reaches
2° F below set point), the unit switches to normal dehu-
midification operation.

2. If the room temperature is below the selected tempera-

ture, the unit will operate for 8 minutes as follows: the
compressor and outdoor fan will operate for 3 minutes.
The indoor fan will operate in low speed, and 30 sec-
onds after the compressor stops, the indoor fan stops.
The unit remains off for 1 minute, and then the indoor
fan starts in ultra-low speed for 30 seconds. The unit
then switches to normal dehumidification operation.

Normal Operation — One of the following will take place:

1. When the temperature of the room is equal to or greater

than the selected temperature (by not more than 3° F),
the unit will operate for 8 minutes as follows: the com-
pressor and outdoor fan will operate for 3 minutes. The
indoor fan will operate in low speed, and 30 seconds af-
ter the compressor stops, the indoor fan stops. The unit
remains off for 1 minute, and then the indoor fan starts
in ultra-low speed for 30 seconds. The normal dehumidi-
fication operation is repeated for the newly sensed room
temperature.

2. If the room temperature is equal to or greater than the

selected temperature, but not by more than between
4° F and 6° F, the compressor and outdoor fan operate
for 4 minutes. The indoor fan will run at ultra-low speed
and will stop 30 seconds after the compressor stops. Af-
ter 3 minutes, the indoor fan runs at ultra-low speed for
30 seconds. The normal dehumidification operation is re-
peated for the newly sensed room temperature.

3. When the room temperature is equal to or greater than

4° F below the selected temperature, the system oper-
ates as follows: The compressor and outdoor fan oper-
ate for 3 minutes. The indoor fan will operate at ultra-
low speed and will stop 30 seconds after the compressor
stops. After 4 or 5 minutes, the indoor fan starts in ultra-
low speed for 30 seconds. The normal dehumidification
operation is repeated for the newly sensed room
temperature. If the room temperature is still 4° F below
the selected temperature, the compressor, outdoor fan,
and indoor fan remain off. After 7

1

2

minutes, the indoor

fan operates at ultra-low speed for 30 seconds. The nor-
mal dehumidification operation is repeated for the newly
sensed room temperature.

• Heat Pump Heating Mode (Heat Pump Systems Only) —

When the heat pump mode is selected, the indoor fan will
operate at the selected speed if the speed is high, medium,
or low, unless overridden by the coil temperature (to pre-
vent cold drafts). If the indoor fan is in auto. mode, the fan
will change operating speeds depending on the difference
between the room temperature, the set point, and the coil

temperature. The reversing valve will be off. The compres-
sor cannot run for 3 minutes from the time the system starts
up or for 3 minutes from the time it last operated. When
the temperature of the room is 8° F below the selected tem-
perature, the unit will operate in heat pump mode until
the temperature is 6° F above the selected temperature, or
the compressor runs for 40 minutes (whichever comes first).
If the temperature of the room is less than 7° F below or
equal to the selected temperature, the unit operates in heat
pump mode until the selected set point temperature plus
2° F is reached.

• Demand Defrost Mode (Heat Pump Systems Only) — This

unit uses a demand defrost system to remove frost from
the outdoor coil during heating operation. The indoor and
outdoor fans are shut off during defrost mode.

• Sleep Mode — The sleep mode timer will turn the unit off

when the timer reaches zero minutes. During the first
1

1

2

hours from the time the sleep mode timer starts, the

room temperature is set back from the selected tempera-
ture a total of 4° F in cooling and 6° F in heating (538B only).

• Awake Mode — The awake timer will turn the unit on when

the timer reaches zero minutes. The unit will start in the
same mode and at the same selected temperature as when
the system shut off.

• Automatic Operation Mode for Cooling Only Systems (538A

and 538S) — The unit samples the air in the room. Based
on the room temperature, the unit selects one of the fol-
lowing modes:

1. Cooling Mode — If the room temperature is more than

82.4 F with a preset temperature of 78.8 F.

2. Dry Mode — If the room temperature is more than 75.2 F

and less than 82.4 F with a preset temperature of 77 F.

3. Fan Only Mode — If the room temperature is less than

75.2 F.

The preset temperature can be changed by ±4 F using the
remote control.

• Automatic Operation Mode for Heat Pump Systems (538B)

— The operation mode will be determined after 20 seconds
of room monitoring (to determine the room temperature
and the outdoor air temperature).

• Test Mode — The test mode can be selected by setting the

slide switch on the fan coil unit to TEST position. The slide
switch is located on the front of the unit as shown in
Fig. 20. The fan coil unit will start immediately (there is
no compressor time delay when using test mode) in cool-
ing mode with an infinitely low set point. The indoor fan
speed will be at the high setting, and the swing louvers
will be on (moving up and down).

NOTE:

The unit cannot be controlled by the remote control-

ler until the slide switch is returned to the REMOTE
position.

• Emergency Mode — This mode is only to be used if the re-

mote controller is lost, damaged, or the batteries are dis-
charged. To initiate emergency mode, manually move the
slide switch on the fan coil unit to the EMER position
(Fig. 20). The unit is automatically operated in cooling or
heating (538B units only) mode according to room tem-
perature. Emergency operation settings are as follows:

1. Operation mode: AUTO.
2. Fan Speed: AUTO.
3. Cooling set point: 77 F
4. Timer mode: Continuous

NOTE:

The unit cannot be controlled by the remote control-

ler until the slide switch is returned to the REMOTE
position.

—11—

Содержание 619E Series

Страница 1: ...Danger identifies the most serious hazards which will result in severe personal injury or death Warning indicates a situation that could result in personal injury Caution is used to identify unsafe pr...

Страница 2: ...in indicate quantities of more than 1 Table 2 Application Ranges COOLING MODE Maximum Minimum Indoor Unit Outdoor Unit Indoor Unit Outdoor Unit 95 F DB 71 F WB 115 F DB 67 F DB 57 F WB 55 F DB 0 F DB...

Страница 3: ...ons may be made in unit rear bottom left side or right side 4 Refrigerant is metered by AccuRater device in the fan coil unit on 538A and 538B applications A thermostatic expan sion valve is used in t...

Страница 4: ...l be mounted unevenly and con densate drainage water may drip onto the floor Also a gap between the bracket and the wall may result in vi bration and noise from the indoor section 5 Mark and cut conde...

Страница 5: ...d slide insulation over the piping Insulation can also be cut and placed over piping 2 Run liquid and gas refrigerant piping a Run pipes as directly as possible and avoid any un necessary turns and be...

Страница 6: ...at a downward slope of at least 1 4 in per foot Refer to Fig 12 IMPORTANT Be sure the drain piping has no slack which might form a trap Do not insert a trap in the drain line the drain is internally...

Страница 7: ...x strain relief clamp see Fig 13 3 Remove any factory test leads still connected to the power terminal box These leads are for factory testing only and cannot be used for power connections 4 Route the...

Страница 8: ...ERMISTOR CABLE IN THE SAME CONDUIT AS THE POWER WIRING 1 One thermistor connection cord with a lead length of 24 ft is shipped with the 619E heat pump fan coil unit Run the connection cord from the lo...

Страница 9: ...system operation to the owner I 619E CONTROL SYSTEM The 619E unit is equipped with a microprocessor control which operates the system This control is located in the control box of the fan coil unit wi...

Страница 10: ...in the green UNIT ON light will flash an error code IX MICROPROCESSOR CONTROL OPERATION This system is controlled by a microprocessor designed to give optimum levels of comfort and operating efficienc...

Страница 11: ...operate at the selected speed if the speed is high medium or low unless overridden by the coil temperature to pre vent cold drafts If the indoor fan is in auto mode the fan will change operating spee...

Страница 12: ...visable to remove the batteries Consult distributor if any other equipment is turned on or shows signs of disrupted operation if you use the wireless re mote controller or if the system is turned on o...

Страница 13: ...not use abrasive or petroleum based cleaners damage to unit appearance will result VI TO CLEAN INDOOR COIL To clean the coil remove indoor unit front panel and vacuum the coil fins Use care not to ben...

Страница 14: ...ndicated then the system allows only limited operation until the problem is resolved If the problem resolves itself then the code is cleared and opera tion resumes A Thermistor Tests Each thermistor i...

Страница 15: ...e replaced with type 90 C wire or its equivalent 2 Wire in accordance with National Electrical Code NEC and local codes 3 The CLO locks out the compressor to prevent short cy cling on compressor overl...

Страница 16: ...ling Only System 538A Shown RELAY CHART Compressor K13 THERMISTOR EQUIVALENCE Temperature Resistance F C V 95 35 6 500 72 22 11 400 32 0 32 500 All thermistors in the 619E systems are identical to eac...

Страница 17: ...ystem RELAY CHART Compressor K13 Rev Valve K11 Outdoor Fan K12 THERMISTOR EQUIVALENCE Temperature Resistance F C V 95 35 6 500 72 22 11 400 32 0 32 500 All thermistors in the 619E systems are identica...

Страница 18: ...Copyright 1996 Carrier Corporation CATALOG NO BDP 3361 904...

Страница 19: ...AS GROUND WIRE BEEN CONNECTED HAS THE CORRECT SIZE FUSE OR HACR BREAKER BEEN PROVIDED ARE POWER WIRES TO THE UNIT SIZED AND INSTALLED PROPERLY IS THE DISCONNECT SWITCH INSTALLED IN SIGHT FROM THE UNIT...

Страница 20: ...UNIT WITH UNIT OPERATING OUTDOOR INDOOR START UP IF UNIT HAS A CRANKCASE HEATER HAS IT BEEN ON FOR 24 HOURS MEASURE AND RECORD THE AIR ENTERING OUTDOOR UNIT F AIR ENTERING INDOOR UNIT F DISCHARGE LIN...

Отзывы: