background image

CLEANING AND MAINTENANCE

CAUTION:

To avoid the possibility of electric shock,

before performing any cleaning and maintenance op-
erations always turn off power to the system by press-
ing the orange ON/OFF button on the remote control-
ler. Turn off the outdoor disconnect switch located near
the outdoor unit. If the indoor unit is on a separate switch,
be sure it is also disconnected.

For proper system operation, perform the cleaning and main-
tenance operations in Table 6.

I. LUBRICATION

The indoor-fan automatic air sweep motor, and the outdoor
fan motor are factory lubricated and require no oiling.

II. TO INSTALL OR REPLACE REMOTE CONTROLLER
BATTERIES

CAUTION:

Do not drop the remote controller — dam-

age to the device may result. Avoid getting the control-
ler wet.

NOTE:

Before replacing the batteries, note that the remote

controller signal can be affected if electronic fluorescent
lights are installed nearby. The batteries may not need to be
replaced. If you suspect this is the problem, consult your
distributor.

Batteries should be replaced once a year. Use 2 batteries (1.5 v,
dc-type, AAA alkaline batteries). Never use old or recharged
batteries together with new ones.

To replace batteries:

1. Slide the battery cover off from the back of the remote

controller. See Fig. 21.

2. Insert the 2 batteries in accordance with the markings

on the remote controller, so that the poles are correct (+
and −).

3. Press the RST button using an instrument screw-

driver or similar small, pointed tool.

4. Replace the cover securely.

It is time to replace the remote controller batteries when the
remote controller function becomes irregular, or the system
no longer responds to commands given close to the unit.

When shutting down the system for an extended period of
time, it is advisable to remove the batteries.

Consult distributor if any other equipment is turned on or
shows signs of disrupted operation if you use the wireless re-
mote controller, or if the system is turned on or shows signs
of disrupted operation when the remote controller of any other
equipment is used.

III. TO SET THE CURRENT TIME

1. Press the TA button (located on the back of the remote

controller; see Fig. 22) with an instrument screwdriver
or similar small, pointed tool, and the current time in-
dication symbol flashes.

NOTE:

That the controller comes preset from the factory set

for 6:00 a.m.

2. Set the current time with the hour and minute buttons

on the front of the remote controller (see Fig. 22) while
the current time indication is flashing. Note that a.m.
and p.m. are also indicated as the times are scrolled
through.

3. Press TA again. The flashing will stop and the current

time will be reset to the new setting.

IV. TO REMOVE AND CLEAN OR REPLACE AIR FILTERS

CAUTION:

Operating your system with dirty air fil-

ters may damage the indoor unit and can also cause re-
duced cooling performance, intermittent system opera-
tion, frost build-up on the indoor coil, and blown fuses.
Inspect and clean or replace the air filters monthly.

A. To Remove Air Filters

1. Open fan coil unit front panel (lift). See Fig. 23.

2. Pull the filters down to remove.

Table 6 — Cleaning and Maintenance Schedule

TASK

MONTHLY

QUARTERLY

YEARLY

INDOOR UNIT

Clean Air Filters

X

Clean Drain Pipe

X

Clean Condensate Drain Pan

X

Replace Batteries in the Remote Controller*

X

Clean Indoor Unit Front Panel

X

OUTDOOR UNIT

Clean the Fins From Outside

X

Open the Unit and Clean Fins Inside

X

Remove Dust From Electrical Parts

X

Check Electrical Connections are Tight

X

Clean Outdoor Fan

X

Check that Outdoor Fan Assembly is Tight

X

Clean Drain Pan

X

NOTE: Maintenance procedures for the outdoor unit are in the 538A, 538B, and 538S installation instructions.

EMER — Emergency Mode

Fig. 20 — Slide Switch

—12—

Содержание 619E Series

Страница 1: ...Danger identifies the most serious hazards which will result in severe personal injury or death Warning indicates a situation that could result in personal injury Caution is used to identify unsafe pr...

Страница 2: ...in indicate quantities of more than 1 Table 2 Application Ranges COOLING MODE Maximum Minimum Indoor Unit Outdoor Unit Indoor Unit Outdoor Unit 95 F DB 71 F WB 115 F DB 67 F DB 57 F WB 55 F DB 0 F DB...

Страница 3: ...ons may be made in unit rear bottom left side or right side 4 Refrigerant is metered by AccuRater device in the fan coil unit on 538A and 538B applications A thermostatic expan sion valve is used in t...

Страница 4: ...l be mounted unevenly and con densate drainage water may drip onto the floor Also a gap between the bracket and the wall may result in vi bration and noise from the indoor section 5 Mark and cut conde...

Страница 5: ...d slide insulation over the piping Insulation can also be cut and placed over piping 2 Run liquid and gas refrigerant piping a Run pipes as directly as possible and avoid any un necessary turns and be...

Страница 6: ...at a downward slope of at least 1 4 in per foot Refer to Fig 12 IMPORTANT Be sure the drain piping has no slack which might form a trap Do not insert a trap in the drain line the drain is internally...

Страница 7: ...x strain relief clamp see Fig 13 3 Remove any factory test leads still connected to the power terminal box These leads are for factory testing only and cannot be used for power connections 4 Route the...

Страница 8: ...ERMISTOR CABLE IN THE SAME CONDUIT AS THE POWER WIRING 1 One thermistor connection cord with a lead length of 24 ft is shipped with the 619E heat pump fan coil unit Run the connection cord from the lo...

Страница 9: ...system operation to the owner I 619E CONTROL SYSTEM The 619E unit is equipped with a microprocessor control which operates the system This control is located in the control box of the fan coil unit wi...

Страница 10: ...in the green UNIT ON light will flash an error code IX MICROPROCESSOR CONTROL OPERATION This system is controlled by a microprocessor designed to give optimum levels of comfort and operating efficienc...

Страница 11: ...operate at the selected speed if the speed is high medium or low unless overridden by the coil temperature to pre vent cold drafts If the indoor fan is in auto mode the fan will change operating spee...

Страница 12: ...visable to remove the batteries Consult distributor if any other equipment is turned on or shows signs of disrupted operation if you use the wireless re mote controller or if the system is turned on o...

Страница 13: ...not use abrasive or petroleum based cleaners damage to unit appearance will result VI TO CLEAN INDOOR COIL To clean the coil remove indoor unit front panel and vacuum the coil fins Use care not to ben...

Страница 14: ...ndicated then the system allows only limited operation until the problem is resolved If the problem resolves itself then the code is cleared and opera tion resumes A Thermistor Tests Each thermistor i...

Страница 15: ...e replaced with type 90 C wire or its equivalent 2 Wire in accordance with National Electrical Code NEC and local codes 3 The CLO locks out the compressor to prevent short cy cling on compressor overl...

Страница 16: ...ling Only System 538A Shown RELAY CHART Compressor K13 THERMISTOR EQUIVALENCE Temperature Resistance F C V 95 35 6 500 72 22 11 400 32 0 32 500 All thermistors in the 619E systems are identical to eac...

Страница 17: ...ystem RELAY CHART Compressor K13 Rev Valve K11 Outdoor Fan K12 THERMISTOR EQUIVALENCE Temperature Resistance F C V 95 35 6 500 72 22 11 400 32 0 32 500 All thermistors in the 619E systems are identica...

Страница 18: ...Copyright 1996 Carrier Corporation CATALOG NO BDP 3361 904...

Страница 19: ...AS GROUND WIRE BEEN CONNECTED HAS THE CORRECT SIZE FUSE OR HACR BREAKER BEEN PROVIDED ARE POWER WIRES TO THE UNIT SIZED AND INSTALLED PROPERLY IS THE DISCONNECT SWITCH INSTALLED IN SIGHT FROM THE UNIT...

Страница 20: ...UNIT WITH UNIT OPERATING OUTDOOR INDOOR START UP IF UNIT HAS A CRANKCASE HEATER HAS IT BEEN ON FOR 24 HOURS MEASURE AND RECORD THE AIR ENTERING OUTDOOR UNIT F AIR ENTERING INDOOR UNIT F DISCHARGE LIN...

Отзывы: