background image

TROUBLESHOOTING

See Table 8 and Fig. 24 and 25 to assist in troubleshooting the 619E fan coil units.

Table 8 — Troubleshooting

PROBLEM

POTENTIAL SOURCE

ACTION

Unit does not
operate

Circuit breaker has tripped or fuse is blown

Reset the circuit breaker or replace the fuse.

Power failure

Restart fan coil unit operation when power is restored.

Voltage is too low

Confirm the available voltage.

Insufficient Cooling

Air filter is blocked with dust

Clean the air filter.

Temperature is not set properly

Check and reset if necessary.

Window(s) and/or door(s) are open

Close window(s) and door(s).

Outdoor unit is obstructed

Remove the obstruction.

Fan speed is too low

Change the fan speed

Operation mode is set to fan or auto. mode

Change to cooling operation or reset temperature
(using remote controller).

Insufficient Heating*

Air filter is blocked with dust

Clean the air filter.

Temperature is not set properly

Check and reset if necessary.

Window(s) and/or door(s) are open

Close window(s) and door(s).

Outdoor unit is obstructed

Remove the obstruction.

Unit stops during
operation

Off timer is operating

Turn off the off timer function.

Room temperature has reached the programmed
set point

Normal unit operation.

*Heat pump systems only.

LEGEND AND NOTES FOR FIG. 24 AND 25

NOTES FOR FIG. 24 AND 25

1. If any of the original wire furnished must be replaced,

it must be replaced with type 90 C wire or its equivalent.

2. Wire in accordance with National Electrical Code (NEC)

and local codes.

3. The CLO locks out the compressor to prevent short cy-

cling on compressor overloads and safety devices. Be-
fore replacing CLO, check these other devices. A mini-
mum 1 amp turn is required to hold contacts closed.

4. A 24-ft long thermistor wiring cable is provided with the

fan coil unit.

5. Compressor and fan motors are protected by internal ther-

mal overloads.

6. Transformer has an internal 2 amp thermal fuse on the

primary side.

AGING

— For the Burn-In Test

(short terminals)

AS

— Assembly

C

— Contactor

CAP

— Capacitor

CH

— Crankcase Heater

CLO

— Compressor Lockout

CN

— Connector

COMP

— Compressor

CT

— Current Transformer

DFB

— Defrost Board

DFT

— Defrost Thermostat

EQUIP GND — Equipment Ground
FMC

— Fan Motor Capacitor

GND

— Ground

HA

— Home Automation

HPS

— High-Pressure Switch

IDC TH

— Indoor-Coil Thermistor

IDFM

— Indoor Fan Motor

JEM-A

— Japan Electric Manufacturing

Industry Association

LLPS

— Liquid Low Pressure Switch

LPS

— Low-Pressure Switch

OAC TH — Outdoor Coil Thermistor
ODA TH — Outdoor-Air Thermistor
ODC TH — Outdoor-Coil Thermistor
OFM

— Outdoor Fan Motor

OFR

— Outdoor Fan Relay

OL

— Overload

PCB

— Printed Circuit Board

RA TH

— Return Air Thermistor

RC

— Resistor Capacitor

RCV

— Receiver

RVS

— Reversing Valve Solenoid

SC

— Start Capacitor

SR

— Start Relay

STM

— Step Motor

TB

— Terminal Block

TRAN — Transformer
U

— Unloader

Terminal (Marked)

Terminal (Unmarked)

Splice

Terminal Block

Factory Wiring

Field Control Wiring

Field Power Wiring

Accessory or Optional Wiring

—15—

Содержание 619E Series

Страница 1: ...Danger identifies the most serious hazards which will result in severe personal injury or death Warning indicates a situation that could result in personal injury Caution is used to identify unsafe pr...

Страница 2: ...in indicate quantities of more than 1 Table 2 Application Ranges COOLING MODE Maximum Minimum Indoor Unit Outdoor Unit Indoor Unit Outdoor Unit 95 F DB 71 F WB 115 F DB 67 F DB 57 F WB 55 F DB 0 F DB...

Страница 3: ...ons may be made in unit rear bottom left side or right side 4 Refrigerant is metered by AccuRater device in the fan coil unit on 538A and 538B applications A thermostatic expan sion valve is used in t...

Страница 4: ...l be mounted unevenly and con densate drainage water may drip onto the floor Also a gap between the bracket and the wall may result in vi bration and noise from the indoor section 5 Mark and cut conde...

Страница 5: ...d slide insulation over the piping Insulation can also be cut and placed over piping 2 Run liquid and gas refrigerant piping a Run pipes as directly as possible and avoid any un necessary turns and be...

Страница 6: ...at a downward slope of at least 1 4 in per foot Refer to Fig 12 IMPORTANT Be sure the drain piping has no slack which might form a trap Do not insert a trap in the drain line the drain is internally...

Страница 7: ...x strain relief clamp see Fig 13 3 Remove any factory test leads still connected to the power terminal box These leads are for factory testing only and cannot be used for power connections 4 Route the...

Страница 8: ...ERMISTOR CABLE IN THE SAME CONDUIT AS THE POWER WIRING 1 One thermistor connection cord with a lead length of 24 ft is shipped with the 619E heat pump fan coil unit Run the connection cord from the lo...

Страница 9: ...system operation to the owner I 619E CONTROL SYSTEM The 619E unit is equipped with a microprocessor control which operates the system This control is located in the control box of the fan coil unit wi...

Страница 10: ...in the green UNIT ON light will flash an error code IX MICROPROCESSOR CONTROL OPERATION This system is controlled by a microprocessor designed to give optimum levels of comfort and operating efficienc...

Страница 11: ...operate at the selected speed if the speed is high medium or low unless overridden by the coil temperature to pre vent cold drafts If the indoor fan is in auto mode the fan will change operating spee...

Страница 12: ...visable to remove the batteries Consult distributor if any other equipment is turned on or shows signs of disrupted operation if you use the wireless re mote controller or if the system is turned on o...

Страница 13: ...not use abrasive or petroleum based cleaners damage to unit appearance will result VI TO CLEAN INDOOR COIL To clean the coil remove indoor unit front panel and vacuum the coil fins Use care not to ben...

Страница 14: ...ndicated then the system allows only limited operation until the problem is resolved If the problem resolves itself then the code is cleared and opera tion resumes A Thermistor Tests Each thermistor i...

Страница 15: ...e replaced with type 90 C wire or its equivalent 2 Wire in accordance with National Electrical Code NEC and local codes 3 The CLO locks out the compressor to prevent short cy cling on compressor overl...

Страница 16: ...ling Only System 538A Shown RELAY CHART Compressor K13 THERMISTOR EQUIVALENCE Temperature Resistance F C V 95 35 6 500 72 22 11 400 32 0 32 500 All thermistors in the 619E systems are identical to eac...

Страница 17: ...ystem RELAY CHART Compressor K13 Rev Valve K11 Outdoor Fan K12 THERMISTOR EQUIVALENCE Temperature Resistance F C V 95 35 6 500 72 22 11 400 32 0 32 500 All thermistors in the 619E systems are identica...

Страница 18: ...Copyright 1996 Carrier Corporation CATALOG NO BDP 3361 904...

Страница 19: ...AS GROUND WIRE BEEN CONNECTED HAS THE CORRECT SIZE FUSE OR HACR BREAKER BEEN PROVIDED ARE POWER WIRES TO THE UNIT SIZED AND INSTALLED PROPERLY IS THE DISCONNECT SWITCH INSTALLED IN SIGHT FROM THE UNIT...

Страница 20: ...UNIT WITH UNIT OPERATING OUTDOOR INDOOR START UP IF UNIT HAS A CRANKCASE HEATER HAS IT BEEN ON FOR 24 HOURS MEASURE AND RECORD THE AIR ENTERING OUTDOOR UNIT F AIR ENTERING INDOOR UNIT F DISCHARGE LIN...

Отзывы: