background image

538S unit, note that for cooling operation below 55 F (538A,
538B) or 0°F (538S), it is necessary to equip the outdoor unit
with the low ambient control (538A, 538B) or winter start
(538S) accessory.

To install this system, you will need:

• 619E cooling only or heat pump fan coil unit(s)* with

standard wireless remote controller

• 538A, 538B, or 538S outdoor unit

• accessory low-ambient control or winter start kit (if re-

quired for your application)

* More than one fan coil unit may be used with the 538S

multi-split units. Refer to 538S system Trade Prices for full
details.

NOTE:

Refrigerant pipe, drain pipe, wire, etc., are also re-

quired to install unit and are field supplied.

Be sure you have the required parts before beginning instal-
lation. The 619E unit utilizes a microprocessor control sys-
tem to deliver optimum levels of comfort and efficiency. Be
sure to follow these instructions carefully to obtain proper
functioning of the unit.

I. COMPLETE PRE-INSTALLATION CHECKS

A. Unpack Unit

Store unit in the original packaging until it is moved to the
final site for installation. When removing unit from carton,
lift by its 4 corners. Also, note that there is a plastic bag con-
taining mounting screws taped to the mounting bracket.

B. Inspect Shipment

Upon receipt of shipment, check unit (Fig. 1) for damage. For-
ward claim papers directly to the transportation company.
Manufacturer is not responsible for damage incurred in
transit.

Check all items. If any item is missing, notify your distribu-
tor. To prevent loss or damage, leave all parts in original pack-
ages until installation.

II. SELECT LOCATION

Consult local building codes and National Electrical Code (NEC)
for special installation requirements.

Table 1 — System Combinations for Indoor

and Outdoor Units

INDOOR UNIT

OUTDOOR UNIT

High Wall Cooling Only Systems*

619E 018
619E 024

(2)619E 018

(4) 619E 018

619E 024, (2) 619E 018

(2) 619E 024

538A 018
538A 024
538S 024†
538S 048†
538S 048†
538S 048†

High Wall Heat Pump Systems**

619E 018
619E 024

538B 018
538B 024

*Using cooling-only fan coil units.

†Multi-split systems can accommodate up to 4 fan coil units of various

types with one condensing unit. The combinations listed in Table 1
are those which use only high-wall units (not in combination with any
other type of fan coil unit). Refer to system presale literature or Trade
Prices for more details.

**Using heat pump fan coil units.

NOTE: Numbers in (

) indicate quantities of more than 1.

Table 2 — Application Ranges

COOLING MODE

Maximum

Minimum

Indoor

Unit

Outdoor

Unit

Indoor

Unit

Outdoor

Unit

95 F DB

71 F WB

115 F DB

67 F DB

57 F WB

55 F DB*

0°F DB†

HEATING MODE (538B Systems Only)

Maximum

Minimum

Indoor

Unit

Outdoor

Unit

Indoor

Unit

Outdoor

Unit

80 F DB

71 F WB

75 F DB

65 F WB

55 F DB

0°F DB

LEGEND

DB

— Dry Bulb

WB — Wet Bulb

*538A and 538B systems only.

†538S systems only.

NOTE: Unit may be equipped with an accessory low-ambient control
(538A, 538B) or a winter start kit (538S) that will allow operation down
to −20 F.

There are several ways the unit may be installed to different
types of wall construction. These instructions do not cover all
installation methods. As a typical installation, these instruc-
tions focus primarily on mounting the unit to wall studs in
new construction. See Fig. 2 for unit dimensions and Fig. 3
for required clearances. Plan your installation carefully be-
fore you begin. Listed below are some guidelines that should
be followed when determining location for the unit.

1. Center unit (horizontally) on the wall selected.

2. Place the unit so it faces normal location of room

occupants.

3. Allow sufficient space for airflow clearance, wiring, re-

frigerant piping, and servicing unit. See Fig. 2 and 3.

4. Select walls that are:

a. Strong enough to support weight of the unit.

b. Accessible to convenient condensate drainage.

c. Free of obstacles that may block air circulation to the

fan coils.

d. Outside walls (if possible) to make piping easier.

5. Place top of fan coil unit as high on the wall as possible

making sure the unit is at least 10 in. down from ceiling
to permit proper air intake. Also, make sure that the
unit is not placed directly over anything which would
prevent filter removal or block airflow.

6. Make sure units are easily accessible to electrical power.

7. Refrigerant piping can enter the unit through the

prepunched holes. Refrigerant piping can run up or down
along the wall, to the right or left along the wall, straight
through the wall, or into the wall (Fig. 4). Once the pip-
ing is through the wall, it can run inside walls, in ceil-
ings, between floors, or straight to the outside. See
Fig. 5 for maximum line lengths.

NOTE:

Run refrigerant piping as directly as possible, and avoid

any unnecessary turns or bends.

8. Condensate piping can be directed through the inside

wall to an approved drain or directed straight outside.

NOTE:

The piping hole for condensate line must be made at

a downward slope to ensure proper drainage. See Mount Mount-
ing Bracket on wall section on page 4 for details.

—2—

Содержание 619E Series

Страница 1: ...Danger identifies the most serious hazards which will result in severe personal injury or death Warning indicates a situation that could result in personal injury Caution is used to identify unsafe pr...

Страница 2: ...in indicate quantities of more than 1 Table 2 Application Ranges COOLING MODE Maximum Minimum Indoor Unit Outdoor Unit Indoor Unit Outdoor Unit 95 F DB 71 F WB 115 F DB 67 F DB 57 F WB 55 F DB 0 F DB...

Страница 3: ...ons may be made in unit rear bottom left side or right side 4 Refrigerant is metered by AccuRater device in the fan coil unit on 538A and 538B applications A thermostatic expan sion valve is used in t...

Страница 4: ...l be mounted unevenly and con densate drainage water may drip onto the floor Also a gap between the bracket and the wall may result in vi bration and noise from the indoor section 5 Mark and cut conde...

Страница 5: ...d slide insulation over the piping Insulation can also be cut and placed over piping 2 Run liquid and gas refrigerant piping a Run pipes as directly as possible and avoid any un necessary turns and be...

Страница 6: ...at a downward slope of at least 1 4 in per foot Refer to Fig 12 IMPORTANT Be sure the drain piping has no slack which might form a trap Do not insert a trap in the drain line the drain is internally...

Страница 7: ...x strain relief clamp see Fig 13 3 Remove any factory test leads still connected to the power terminal box These leads are for factory testing only and cannot be used for power connections 4 Route the...

Страница 8: ...ERMISTOR CABLE IN THE SAME CONDUIT AS THE POWER WIRING 1 One thermistor connection cord with a lead length of 24 ft is shipped with the 619E heat pump fan coil unit Run the connection cord from the lo...

Страница 9: ...system operation to the owner I 619E CONTROL SYSTEM The 619E unit is equipped with a microprocessor control which operates the system This control is located in the control box of the fan coil unit wi...

Страница 10: ...in the green UNIT ON light will flash an error code IX MICROPROCESSOR CONTROL OPERATION This system is controlled by a microprocessor designed to give optimum levels of comfort and operating efficienc...

Страница 11: ...operate at the selected speed if the speed is high medium or low unless overridden by the coil temperature to pre vent cold drafts If the indoor fan is in auto mode the fan will change operating spee...

Страница 12: ...visable to remove the batteries Consult distributor if any other equipment is turned on or shows signs of disrupted operation if you use the wireless re mote controller or if the system is turned on o...

Страница 13: ...not use abrasive or petroleum based cleaners damage to unit appearance will result VI TO CLEAN INDOOR COIL To clean the coil remove indoor unit front panel and vacuum the coil fins Use care not to ben...

Страница 14: ...ndicated then the system allows only limited operation until the problem is resolved If the problem resolves itself then the code is cleared and opera tion resumes A Thermistor Tests Each thermistor i...

Страница 15: ...e replaced with type 90 C wire or its equivalent 2 Wire in accordance with National Electrical Code NEC and local codes 3 The CLO locks out the compressor to prevent short cy cling on compressor overl...

Страница 16: ...ling Only System 538A Shown RELAY CHART Compressor K13 THERMISTOR EQUIVALENCE Temperature Resistance F C V 95 35 6 500 72 22 11 400 32 0 32 500 All thermistors in the 619E systems are identical to eac...

Страница 17: ...ystem RELAY CHART Compressor K13 Rev Valve K11 Outdoor Fan K12 THERMISTOR EQUIVALENCE Temperature Resistance F C V 95 35 6 500 72 22 11 400 32 0 32 500 All thermistors in the 619E systems are identica...

Страница 18: ...Copyright 1996 Carrier Corporation CATALOG NO BDP 3361 904...

Страница 19: ...AS GROUND WIRE BEEN CONNECTED HAS THE CORRECT SIZE FUSE OR HACR BREAKER BEEN PROVIDED ARE POWER WIRES TO THE UNIT SIZED AND INSTALLED PROPERLY IS THE DISCONNECT SWITCH INSTALLED IN SIGHT FROM THE UNIT...

Страница 20: ...UNIT WITH UNIT OPERATING OUTDOOR INDOOR START UP IF UNIT HAS A CRANKCASE HEATER HAS IT BEEN ON FOR 24 HOURS MEASURE AND RECORD THE AIR ENTERING OUTDOOR UNIT F AIR ENTERING INDOOR UNIT F DISCHARGE LIN...

Отзывы: