background image

IV. CONNECT REFRIGERANT PIPING

Fan coil units may be connected to the outdoor units using
field-supplied refrigerant grade piping. Refer to Table 3 for
the correct size piping. The length of refrigerant pipe de-
pends on the unit placement and building structure; run pipes
as directly as possible. For piping requirements over 50 ft of
total run, or more than 25 ft of lift, consult the long line ap-
plication guidelines available in the product presale litera-
ture, or contact your local representative.

CAUTION:

DO NOT BURY MORE THAN 36 IN. OF

REFRIGERANT PIPE IN THE GROUND. If any sec-
tion of pipe is buried, there must be a 6-in. vertical rise
to the valve connections on the outdoor unit. If more
than the recommended length is buried, refrigerant may
migrate to the cooler, buried section during extended
periods of unit shutdown, causing refrigerant slugging
and possible compressor damage at start-up.

Use the following instructions to connect piping.

1. Install insulation. Insulate

all

refrigerant lines on heat

pumps 538S and systems to prevent condensation. It is
extremely important that all refrigerant lines and the
AccuRater

t

metering device be insulated on heat pumps.

On 538A cooling only units, the liquid line may be left
uninsulated. Use any acceptable heat resistant closed-
cell foam insulation (minimum

3

8

-in. wall thickness). When

insulating piping, cap ends and slide insulation over
the piping. Insulation can also be cut and placed over
piping.

2. Run liquid and gas refrigerant piping.

a. Run pipes as directly as possible and avoid any un-

necessary turns and bends.

b. Suspend refrigerant pipes so that the insulation is

not damaged and vibrations are not transmitted to
the structure.

c. Leave slack in the refrigerant pipe between the struc-

ture and the unit to absorb vibrations.

d. Install factory-supplied flare connection and Accu-

Rater metering device in liquid line at the fan coil
unit on 538A and 538B systems (Fig. 9). Make sure
the arrow on the metering device body points

AWAY

FROM

the fan coil unit. Use Table 4 to verify that

the correct piston for your system has been shipped
with the unit.

NOTE:

No AccuRater is required on 538S systems. The 538S

systems have a TXV (thermostatic expansion valve) in the
condensing unit for refrigerant metering and control.

e. On heat pump installations, install factory-supplied

piston in the AccuRater metering device located in
the service valve on the outdoor unit (Fig. 10). Make
sure Teflon seal on the piston faces toward the out-
door unit. Use Table 4 to verify the correct piston for
your system has been shipped with the unit. Refer to
538B installation instructions for more details.

f. Install a liquid line filter drier near the outdoor unit

(538A and 538B). On heat pump systems, a bi-flow
filter drier must be used. DO NOT install a filter drier
in 538S systems.

Fig. 6 — Bracket Mounting

NOTE: Use either point ‘‘A’’ or point ‘‘B’’.

Fig. 7 — Wall Hole Location for Rear Piping

Fig. 8 — Piping Hole

—5—

Содержание 619E Series

Страница 1: ...Danger identifies the most serious hazards which will result in severe personal injury or death Warning indicates a situation that could result in personal injury Caution is used to identify unsafe pr...

Страница 2: ...in indicate quantities of more than 1 Table 2 Application Ranges COOLING MODE Maximum Minimum Indoor Unit Outdoor Unit Indoor Unit Outdoor Unit 95 F DB 71 F WB 115 F DB 67 F DB 57 F WB 55 F DB 0 F DB...

Страница 3: ...ons may be made in unit rear bottom left side or right side 4 Refrigerant is metered by AccuRater device in the fan coil unit on 538A and 538B applications A thermostatic expan sion valve is used in t...

Страница 4: ...l be mounted unevenly and con densate drainage water may drip onto the floor Also a gap between the bracket and the wall may result in vi bration and noise from the indoor section 5 Mark and cut conde...

Страница 5: ...d slide insulation over the piping Insulation can also be cut and placed over piping 2 Run liquid and gas refrigerant piping a Run pipes as directly as possible and avoid any un necessary turns and be...

Страница 6: ...at a downward slope of at least 1 4 in per foot Refer to Fig 12 IMPORTANT Be sure the drain piping has no slack which might form a trap Do not insert a trap in the drain line the drain is internally...

Страница 7: ...x strain relief clamp see Fig 13 3 Remove any factory test leads still connected to the power terminal box These leads are for factory testing only and cannot be used for power connections 4 Route the...

Страница 8: ...ERMISTOR CABLE IN THE SAME CONDUIT AS THE POWER WIRING 1 One thermistor connection cord with a lead length of 24 ft is shipped with the 619E heat pump fan coil unit Run the connection cord from the lo...

Страница 9: ...system operation to the owner I 619E CONTROL SYSTEM The 619E unit is equipped with a microprocessor control which operates the system This control is located in the control box of the fan coil unit wi...

Страница 10: ...in the green UNIT ON light will flash an error code IX MICROPROCESSOR CONTROL OPERATION This system is controlled by a microprocessor designed to give optimum levels of comfort and operating efficienc...

Страница 11: ...operate at the selected speed if the speed is high medium or low unless overridden by the coil temperature to pre vent cold drafts If the indoor fan is in auto mode the fan will change operating spee...

Страница 12: ...visable to remove the batteries Consult distributor if any other equipment is turned on or shows signs of disrupted operation if you use the wireless re mote controller or if the system is turned on o...

Страница 13: ...not use abrasive or petroleum based cleaners damage to unit appearance will result VI TO CLEAN INDOOR COIL To clean the coil remove indoor unit front panel and vacuum the coil fins Use care not to ben...

Страница 14: ...ndicated then the system allows only limited operation until the problem is resolved If the problem resolves itself then the code is cleared and opera tion resumes A Thermistor Tests Each thermistor i...

Страница 15: ...e replaced with type 90 C wire or its equivalent 2 Wire in accordance with National Electrical Code NEC and local codes 3 The CLO locks out the compressor to prevent short cy cling on compressor overl...

Страница 16: ...ling Only System 538A Shown RELAY CHART Compressor K13 THERMISTOR EQUIVALENCE Temperature Resistance F C V 95 35 6 500 72 22 11 400 32 0 32 500 All thermistors in the 619E systems are identical to eac...

Страница 17: ...ystem RELAY CHART Compressor K13 Rev Valve K11 Outdoor Fan K12 THERMISTOR EQUIVALENCE Temperature Resistance F C V 95 35 6 500 72 22 11 400 32 0 32 500 All thermistors in the 619E systems are identica...

Страница 18: ...Copyright 1996 Carrier Corporation CATALOG NO BDP 3361 904...

Страница 19: ...AS GROUND WIRE BEEN CONNECTED HAS THE CORRECT SIZE FUSE OR HACR BREAKER BEEN PROVIDED ARE POWER WIRES TO THE UNIT SIZED AND INSTALLED PROPERLY IS THE DISCONNECT SWITCH INSTALLED IN SIGHT FROM THE UNIT...

Страница 20: ...UNIT WITH UNIT OPERATING OUTDOOR INDOOR START UP IF UNIT HAS A CRANKCASE HEATER HAS IT BEEN ON FOR 24 HOURS MEASURE AND RECORD THE AIR ENTERING OUTDOOR UNIT F AIR ENTERING INDOOR UNIT F DISCHARGE LIN...

Отзывы: