background image

IMPORTANT — READ BEFORE INSTALLING

1. Read and become familiar with these installation in-

structions before installing this unit (see Fig. 1).

2. Be sure the installation conforms to all applicable local

and national codes.

3. These instructions contain important information for the

proper maintenance and repair of this equipment. Re-
tain these instructions for future use.

CONTENTS

Page

SAFETY CONSIDERATIONS

. . . . . . . . . . . . . . . . . . . . . . . . 1

GENERAL

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1

INSTALLATION

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-9

I. Complete Pre-Installation Checks

. . . . . . . . . . . . . 2

II. Select Location

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

III. Mount Mounting Bracket on Wall

. . . . . . . . . . . . . . 4

IV. Connect Refrigerant Piping

. . . . . . . . . . . . . . . . . . . 5

V. Connect Condensate Drain Line

. . . . . . . . . . . . . . 6

VI. Make Electrical Connections

. . . . . . . . . . . . . . . . . 7

VII. Make Connections to Outdoor Unit

. . . . . . . . . . . . 8

VIII. Install Fan Coil Unit Onto Mounting

Bracket

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8

START-UP

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-12

I. 619E Control System

. . . . . . . . . . . . . . . . . . . . . . . . 9

II. After Extended Shutdowns

. . . . . . . . . . . . . . . . . . . 9

III. Seasonal Changeovers

. . . . . . . . . . . . . . . . . . . . . . 9

IV. To Turn The Unit On and Off

. . . . . . . . . . . . . . . . . 10

V. Adjusting Airflow

. . . . . . . . . . . . . . . . . . . . . . . . . . 10

VI. Operating Mode Memory

. . . . . . . . . . . . . . . . . . . . 10

VII. Automatic Operation (Auto) Mode

. . . . . . . . . . . . 10

VIII. Operating Fault Diagnosis

. . . . . . . . . . . . . . . . . . 10

IX. Microprocessor Control Operation

. . . . . . . . . . . 10

CLEANING AND MAINTENANCE

. . . . . . . . . . . . . . . . . 12-14

I. Lubrication

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12

II. To Install or Replace Remote Controller

Batteries

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12

III. To Set the Current Time

. . . . . . . . . . . . . . . . . . . . 12

IV. To Remove and Clean or Replace

Air Filters

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12

V. To Clean Indoor Unit Front Panel

. . . . . . . . . . . . . 13

VI. To Clean Indoor Coil

. . . . . . . . . . . . . . . . . . . . . . . 13

VII. To Clean Outdoor Coil

. . . . . . . . . . . . . . . . . . . . . . 13

VIII. To Clean Condensate Drains

. . . . . . . . . . . . . . . . 14

SERVICE

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14

I. Diagnostic Codes

. . . . . . . . . . . . . . . . . . . . . . . . . . 14

II. System Tests

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14

III. System Safeties and Interlocks

. . . . . . . . . . . . . . 14

TROUBLESHOOTING

. . . . . . . . . . . . . . . . . . . . . . . . . . . 15-17

START-UP CHECKLIST

. . . . . . . . . . . . . . . . . . . . CL-1, CL-2

SAFETY CONSIDERATIONS

Recognize safety information. This is the safety-alert symbol
(

). When you see this symbol on the unit and in instruc-

tions or manuals, be alert to the potential for personal
injury.

Understand the signal words — DANGER, WARNING, and
CAUTION. These words are used with the safety-alert sym-
bol. Danger identifies the most serious hazards which will
result in severe personal injury or death. Warning indicates
a situation that could result in personal injury. Caution is
used to identify unsafe practices which would result in minor
personal injury or product and property damage.

WARNING:

Before performing service or mainte-

nance operations on unit, turn off main power switch
to unit. Electrical shock could cause personal injury.

GENERAL

The new 619E heat pump high wall fan coil units (Fig. 1) DO
NOT have electric heaters. These new heat pump fan coil units
have been specifically designed to improve system efficiency
in both heating and cooling modes when matched with a 538B
outdoor heat pump unit. If your application requires heat-
ing, heat pump units must be used, both outdoors and in-
doors. See Table 1 for recommended system combinations.

INSTALLATION

The 619E cooling only high wall fan coil unit is installed with
either the 538A condensing or 538S multi-split condensing
outdoor unit, and the 619E heat pump fan coil unit is in-
stalled with the 538B heat pump outdoor unit. Refer to
Table 1 to make sure the correct indoor unit(s) is installed
with the correct outdoor unit.

Installation instructions for the 619E fan coil units are con-
tained in this manual. Refer to this manual for proper instal-
lation of the complete system. Note that the 538A, 538B, and
538S outdoor units are shipped with installation and service
instructions for basic installation of the outdoor section. Be
sure to make the modifications in Make Connections to Out-
door Unit section on page 8 of this literature so that the out-
door unit will operate properly with the 619E control system.
Be sure the unit will be operated within the application guide-
lines shown in Table 2. When installing the 538A, 538B, or

Fig. 1 — 619E High Wall Fan Coil Unit

installation, start-up and
service instructions

HIGH WALL FAN COIL UNITS

619E

Sizes 018 and 024

1

1

2

and 2 Tons

Cancels: New

II 619E-18-1

4/15/96

Содержание 619E Series

Страница 1: ...Danger identifies the most serious hazards which will result in severe personal injury or death Warning indicates a situation that could result in personal injury Caution is used to identify unsafe pr...

Страница 2: ...in indicate quantities of more than 1 Table 2 Application Ranges COOLING MODE Maximum Minimum Indoor Unit Outdoor Unit Indoor Unit Outdoor Unit 95 F DB 71 F WB 115 F DB 67 F DB 57 F WB 55 F DB 0 F DB...

Страница 3: ...ons may be made in unit rear bottom left side or right side 4 Refrigerant is metered by AccuRater device in the fan coil unit on 538A and 538B applications A thermostatic expan sion valve is used in t...

Страница 4: ...l be mounted unevenly and con densate drainage water may drip onto the floor Also a gap between the bracket and the wall may result in vi bration and noise from the indoor section 5 Mark and cut conde...

Страница 5: ...d slide insulation over the piping Insulation can also be cut and placed over piping 2 Run liquid and gas refrigerant piping a Run pipes as directly as possible and avoid any un necessary turns and be...

Страница 6: ...at a downward slope of at least 1 4 in per foot Refer to Fig 12 IMPORTANT Be sure the drain piping has no slack which might form a trap Do not insert a trap in the drain line the drain is internally...

Страница 7: ...x strain relief clamp see Fig 13 3 Remove any factory test leads still connected to the power terminal box These leads are for factory testing only and cannot be used for power connections 4 Route the...

Страница 8: ...ERMISTOR CABLE IN THE SAME CONDUIT AS THE POWER WIRING 1 One thermistor connection cord with a lead length of 24 ft is shipped with the 619E heat pump fan coil unit Run the connection cord from the lo...

Страница 9: ...system operation to the owner I 619E CONTROL SYSTEM The 619E unit is equipped with a microprocessor control which operates the system This control is located in the control box of the fan coil unit wi...

Страница 10: ...in the green UNIT ON light will flash an error code IX MICROPROCESSOR CONTROL OPERATION This system is controlled by a microprocessor designed to give optimum levels of comfort and operating efficienc...

Страница 11: ...operate at the selected speed if the speed is high medium or low unless overridden by the coil temperature to pre vent cold drafts If the indoor fan is in auto mode the fan will change operating spee...

Страница 12: ...visable to remove the batteries Consult distributor if any other equipment is turned on or shows signs of disrupted operation if you use the wireless re mote controller or if the system is turned on o...

Страница 13: ...not use abrasive or petroleum based cleaners damage to unit appearance will result VI TO CLEAN INDOOR COIL To clean the coil remove indoor unit front panel and vacuum the coil fins Use care not to ben...

Страница 14: ...ndicated then the system allows only limited operation until the problem is resolved If the problem resolves itself then the code is cleared and opera tion resumes A Thermistor Tests Each thermistor i...

Страница 15: ...e replaced with type 90 C wire or its equivalent 2 Wire in accordance with National Electrical Code NEC and local codes 3 The CLO locks out the compressor to prevent short cy cling on compressor overl...

Страница 16: ...ling Only System 538A Shown RELAY CHART Compressor K13 THERMISTOR EQUIVALENCE Temperature Resistance F C V 95 35 6 500 72 22 11 400 32 0 32 500 All thermistors in the 619E systems are identical to eac...

Страница 17: ...ystem RELAY CHART Compressor K13 Rev Valve K11 Outdoor Fan K12 THERMISTOR EQUIVALENCE Temperature Resistance F C V 95 35 6 500 72 22 11 400 32 0 32 500 All thermistors in the 619E systems are identica...

Страница 18: ...Copyright 1996 Carrier Corporation CATALOG NO BDP 3361 904...

Страница 19: ...AS GROUND WIRE BEEN CONNECTED HAS THE CORRECT SIZE FUSE OR HACR BREAKER BEEN PROVIDED ARE POWER WIRES TO THE UNIT SIZED AND INSTALLED PROPERLY IS THE DISCONNECT SWITCH INSTALLED IN SIGHT FROM THE UNIT...

Страница 20: ...UNIT WITH UNIT OPERATING OUTDOOR INDOOR START UP IF UNIT HAS A CRANKCASE HEATER HAS IT BEEN ON FOR 24 HOURS MEASURE AND RECORD THE AIR ENTERING OUTDOOR UNIT F AIR ENTERING INDOOR UNIT F DISCHARGE LIN...

Отзывы: