background image

24

C99097

Fig. 27 -- Refrigerant Circuit

Step 9 — Pressure Switches

Pressure switches are protective devices wired into control circuit
(low voltage). They shut off compressor if abnormally high or

low pressures are present in the refrigeration circuit. These

pressure switches are specifically designed to operate with Puron
(R--410A) systems. R--22 pressure switches must not be used as

replacements for the Puron (R--410A) system.

Step 10 — Loss of Charge Switch

This switch is located on the liquid line and protects against low
suction pressures caused by such events as loss of charge, low
airflow across indoor coil, dirty filters, etc. It opens on a pressure
drop at about 20 psig. If system pressure is above this, switch
should be closed. To check switch:

1. Turn off all power to unit.
2. Disconnect leads on switch.
3. Apply ohm meter leads across switch. You should have

continuity on a good switch.

NOTE

: Because these switches are attached to refrigeration

system under pressure, it is not advisable to remove this device
for troubleshooting unless you are reasonably certain that a
problem exists. If switch must be removed, remove and recover
all system charge so that pressure gauges read 0 psi. Never open
system without breaking vacuum with dry nitrogen.

Step 11 — High--Pressure Switch

The high--pressure switch is located in the discharge line and
protects against excessive condenser coil pressure. It opens at 610
psig.
High pressure may be caused by a dirty outdoor coil, failed fan
motor, or outdoor air recirculation.
To check switch:

1. Turn off all power to unit.
2. Disconnect leads on switch.
3. Apply ohm meter leads across switch. You should have

continuity on a good switch.

Step 12 — Copeland Scroll Compressor (Puron

Refrigerant)

The compressor used in this product is specifically designed to

operate with Puron (R--410A) refrigerant and cannot be
interchanged.

EXPLOSION HAZARD

Failure to follow this warning could result in personal injury,

death or property damage.
Wear safety glasses and gloves when handling refrigerants.

Keep torches and other ignition sources away from refrigerant

and oils.

!

WARNING

The scroll compressor pumps refrigerant throughout the system
by the interaction of a stationary and an orbiting scroll. The scroll

compressor has no dynamic suction or discharge valves, and it is
more tolerant of stresses caused by debris, liquid slugging, and

flooded starts. The compressor is equipped with an

anti--rotational device and an internal pressure relief port. The
anti--rotational device prevents the scroll from turning backwards

and replaces the need for a cycle protector. The pressure relief
port is a safety device, designed to protect against extreme high

pressure. The relief port has an operating range between 550 and
625 psi differential pressure.
The Copeland scroll compressor uses Mobil 3MAF POE oil.

Copeland Ultra 22 CC should be used if additional oil is needed
in the field. Mobil Artic EAL22CC or ICI Emkarate RL22 or

32CF oil may be used to recharge these compressors if Ultra 22
is not available.

Step 13 — Refrigerant System

This step covers the refrigerant system of the 604D, including the

compressor oil needed, servicing systems on roofs containing
synthetic materials, the filter drier and refrigerant charging.

REFRIGERANT

PROPERTY HAZARD OR PERSONAL INJURY

HAZARD

Failure to follow this warning could result in property damage

or personal injury or death.

This system uses Puron (R--410A) refrigerant which has

higher operating pressures than R--22 and other refrigerants.

No other refrigerant may be used in this system. Gauge set,

hoses, and recovery system must be designed to handle Puron.

If you are unsure consult the equipment manufacturer.

!

WARNING

COMPRESSOR OIL

The compressor in this system uses a polyolester (POE) oil,

Mobil 3MAF POE. This oil is extremely hygroscopic, meaning it
absorbs water readily. POE oils can absorb 15 times as much

water as other oils designed for HCFC and CFC refrigerants.

Take all necessary precautions to avoid exposure of the oil to the
atmosphere.

SERVICING SYSTEMS ON ROOFS WITH SYNTHETIC
MATERIALS

POE (polyolester) compressor lubricants are known to cause long

term damage to some synthetic roofing materials. Exposure, even

if immediately cleaned up, may cause embrittlement (leading to
cracking) to occur in one year or more. When performing any

service that may risk exposure of compressor oil to the roof, take
appropriate precautions to protect roofing. Procedures which risk

604D

Содержание 604D024

Страница 1: ...rflow Airflow Adjustments 19 Defrost Control 19 Quiet Shift 19 Defrost 19 20 MAINTENANCE 20 25 Air Filter 21 Indoor Blower and Motor 21 Outdoor Coil Indoor Coil Condensate Drain Pan 21 Outdoor Fan 23...

Страница 2: ...roof curb Improperly applied gasketing also can result in air leaks and poor unit performance Curb should be level to within 1 4 in 6 mm See Fig 6 This is necessary for unit drain to function properl...

Страница 3: ...00 355 6 BOTTOM OF UNIT 0 50 12 7 NEC REQUIRED CLEARANCES INCHES mm BETWEEN UNITS POWER ENTRY SIDE 42 00 1066 8 UNIT AND UNGROUNDED SURFACES POWER ENTRY SIDE 36 00 914 0 UNIT AND BLOCK OR CONCRETE WA...

Страница 4: ...IT 0 50 12 7 NEC REQUIRED CLEARANCES INCHES mm BETWEEN UNITS POWER ENTRY SIDE 42 00 1066 8 UNIT AND UNGROUNDED SURFACES POWER ENTRY SIDE 36 00 914 0 UNIT AND BLOCK OR CONCRETE WALLS AND OTHER GROUNDED...

Страница 5: ...et if not already installed 1 Remove unit from shipping carton Leave top shipping skid on the unit for use as a spreader bar to prevent the rigging straps from damagingthe unit If theskid isnot availa...

Страница 6: ...also be used A BTyp Supply opening B x C Long Support D 445 16 Return opening B X C Insulate d deck pan Short Support CTyp C00076 UNIT SIZE ODS CATALOG NUMBER A IN MM B IN MM C IN MM D IN MM 604D024 0...

Страница 7: ...allation standards for residential heating and air conditioning systems OPTIONAL RETURN AIR OPENING OPTIONAL SUPPLY AIR OPENING EVAP COIL COND COIL 2 C99096 Fig 7 Slab Mounting Detail 5 Secure all duc...

Страница 8: ...rection of improper voltage and or phase imbalance 4 Insulate low voltage wires for highest voltage contained within conduit when low voltage control wires are in same conduit as high voltage wires 5...

Страница 9: ...high voltage raceway to the line wiring splice box See Fig 12 through 16 For singlephase units connect leads to the black and yellow wires for 3 phase units connect the leads to the black yellow and b...

Страница 10: ...NNECT PER NEC FROM POWER SOURCE RETURN AIR TOP COVER NEC NATIONAL ELECTRICAL CODE C00063 Fig 9 Typical Installation Duct Covers C00092 Fig 10 604D with Duct Covers On 1 MIN 2 MIN TRAP OUTLET C99013 Fi...

Страница 11: ...11 A07021 Fig 12 Wiring Schematics 604D Single Phase 604D...

Страница 12: ...12 A07014 Fig 13 Wiring Schematics 604D Three Phase 604D...

Страница 13: ...hat airflow delivered falls within proper range for the size unit installed This applies to all operational modes with the exception of electric heat modes See Fig 18 B as indicated c SYSTEM TYPE SELE...

Страница 14: ...N The following basic configuration of the indoor motor will provide ARI rated performance of the System This BASIC CONFIGURATION should be used when the rated ARI performance is required or if system...

Страница 15: ...is energized See Fig 18 During Super dehumidify mode the G signal is not present and the auxiliary terminals are not energized If the installation includes the use of the operating mode do not use the...

Страница 16: ...pump is also operating in either heating or defrost modes the motor will modify its airflow output if necessary to provide an airflow which is defined as safe for the operation of the electric heater...

Страница 17: ...nd G These completed circuits through the thermostat connect contactor coil C through unit wire Y and ECM board through unit wire G across the 24 v secondary of transformer TRAN Thermidistat or Thermo...

Страница 18: ...oper compressor 3 phase power lead orientation If not corrected within 5 minutes the internal protector will shut off the compressor The 3 phase power leads to the unit must be reversed to correct rot...

Страница 19: ...g the set up pins on the Easy Select board Unit 604D utilizes state of the art ECM Electronic Computated Motor ID Blower Motors Step 3 Defrost Control QUIET SHIFT Quiet Shift is a field selectable def...

Страница 20: ...5 0 039 0 043 048 0 027 0 032 0 036 0 041 0 046 0 052 0 057 0 063 0 068 060 0 029 0 032 0 036 0 040 0 045 0 049 0 053 again turn off for an additional 30 sec and the outdoor fan for 40 sec When the Qu...

Страница 21: ...necessary 4 Check electrical connections for tightness and controls for proper operation each cooling season Service when necessary Step 1 Air Filter IMPORTANT Never operate the unit without a suitabl...

Страница 22: ...41 39 36 33 30 384 108 103 98 93 88 2647 42 40 37 34 31 394 110 105 100 95 90 2716 44 41 38 35 32 404 112 107 102 97 92 2785 45 42 39 36 33 414 114 109 104 99 94 2854 46 43 40 37 34 424 116 111 106 1...

Страница 23: ...curely After inspecting the electrical controls and wiring replace all the panels Start the unit and observe at least one complete cooling cycle to ensure proper operation If discrepancies are observe...

Страница 24: ...pumps refrigerant throughout the system by the interaction of a stationary and an orbiting scroll The scroll compressor has no dynamic suction or discharge valves and it is more tolerant of stresses...

Страница 25: ...nder in upright position and a commercial metering device in manifold hose Charge refrigerant into suction line Step 14 System Information LOSS OF CHARGE SWITCH The loss of charge switch is a protecti...

Страница 26: ...driers with rated working pressures less than 600 psig S Do not leave Puron suction line filter driers in line longer than 72 hours S Do not install a suction line filter drier in liquid line S POE o...

Страница 27: ...utdoor unit Cooling Size C SYSTEM TYPE Select AC for Gas Package Units D AC HP CFM ADJUST Select NOM E ON OFF DELAY Do not use ENH for this unit F CONTINUOUS FAN Select desired speed 2 Remove Jumper J...

Страница 28: ...ne cause and correct Defective run start capacitor overload or start relay Determine cause and replace Defective thermostat Replace thermostat Faulty condenser fan motor or capacitor Replace Restricti...

Страница 29: ...r Purge as necessary NOTE After purging gas line of air wait at least 5 minutes for any gas to dissipate before attempting to light unit 2 Check gas valve Inadequate heating Dirty air filter Clean or...

Страница 30: ...PUMP SUPPLY AIR ___________ GAS HEAT SUPPLY AIR ___________ ELECTRIC HEAT SUPPLY AIR ___________ PRESSURES GAS INLET PRESSURE ___________IN WG GAS MANIFOLD PRESSURE ___________IN WG REFRIGERANT SUCTI...

Отзывы: