background image

17

Use the Start--Up Checklist supplied at the end of this book and
proceed as follows to inspect and prepare the unit for initial

start--up:

1. Remove all access panels.
2. Read and follow instructions on all DANGER,

WARNING, CAUTION, and INFORMATION labels

attached to, or shipped with, unit.

3. Make the following inspections:

a. Inspect for shipping and handling damages such as

broken lines, loose parts, disconnected wires, etc.

b. Inspect for oil at all refrigerant tubing connections and

on unit base. Detecting oil generally indicates a
refrigerant leak. Leak--test all refrigerant tubing

connections using electronic leak detector, or
liquid--soap solution. If a refrigerant leak is detected,
see following Check for Refrigerant Leaks section.

c. Inspect all field and factory--wiring connections. Be

sure that connections are completed and tight.

d. Inspect coil fins. If damaged during shipping and

handling, carefully straighten fins with a fin comb.

4. Verify the following conditions:

a. Make sure that outdoor--fan blade is correctly

positioned in fan orifice.

b. Make sure that air filter(s) is in place.

c. Make sure that condensate drain pan and trap are filled

with water to ensure proper drainage.

d. Make sure that on the 060 size, only the 2 wire ties

fastened to the outdoor coils and reversing

valve/accumulator have been removed.

e. Make sure that all tools and miscellaneous loose parts

have been removed.

5. Compressors are internally spring mounted. Do not loosen

or remove compressor hold--down bolts.

6. Each unit system has 2 Schrader--type ports, one low--side

Schrader fitting located on the suction line, and one

high--side Schrader fitting located on the compressor
discharge line. Be sure that caps on the ports are tight.

FAN GRILLE

MOTOR

1/8" MAX BETWEEN

MOTOR AND FAN HUB

MOTOR SHAFT

C99009

Fig. 21 -- Fan Blade Clearance

START--UP

CHECKING COOLING AND HEATING CONTROL
OPERATION

Start and check the unit for proper control operation as follows:

(1.) Place room thermostat SYSTEM switch or

MODE control in OFF position. Observe that

blower motor starts when FAN mode is placed in
FAN ON position and shuts down according to

time delay selected on the Easy Select board (See
Easy Select Section) when FAN MODE switch is
placed in AUTO position.

(2.) Thermostat:

When the room temperature rises to a point that is

slightly above the cooling control setting of the
thermostat, the thermostat completes the circuit
between thermostat terminal R to terminals Y, O

and G.These completed circuits through the
thermostat connect contactor coil (C) (through

unit wire Y) and ECM board (through unit wire
G) across the 24--v. secondary of transformer
(TRAN).

Thermidistat or Thermostat and Humidistat:
When the room temperature rises to a point that is

slightly above the cooling control setting of the
thermostat, the thermostat completes the circuit
between thermostat terminal R to terminals Y, O,

DH, and G. These completed circuits through the
thermostat connect contactor coil (C) (through

unit wire Y) and ECM board (though unit wire
G) across the 24--v. secondary of transformer

(TRANS).

(3.) Place system switch or MODE control in HEAT

position. Set control above room temperature.

Observe that compressor, outdoor fan, and indoor
blower motors start. Observe that heating cycle

shuts down according to time delay selected on
the Easy Select board (See Easy Select Section)
when control setting is satisfied.

(4.) When using an automatic changeover room

thermostat place both SYSTEM or MODE

control and FAN mode switches in AUTO
positions. Observe that unit operates in Cooling

mode when temperature control is set to “call for
Cooling” (below room temperature), and unit
operates in Heating mode when temperature

control is set to “call for Heating” (above room
temperature).

NOTE

: Once the compressor has started and then has stopped, it

should not be started again until 5 minutes have elapsed. The
cooling cycle remains “on” until the room temperature drops to
point that is slightly below the cooling control setting of the room
thermostat. At this point, the thermostat “breaks” the circuit
between thermostat terminal R to terminals Y and G. These open
circuits de--energize contactor coil C and ECM board. The
condenser and compressor motors stop. After the time delay
setting selected on the Easy Select board (See Easy Select
Section) , the blower motor stops. The unit is in a “standby”
condition, waiting for the next “call for cooling” from the room
thermostat. The 5 minute compressor delay also applies to heat
pump heating mode.

Step 1 — Check for Refrigerant Leaks

Locate and repair refrigerant leaks and charge the unit as follows:

1. 1. Use both high-- and low--pressure ports to relieve

system pressure and reclaim remaining refrigerant.

2. Repair leak following accepted practices.

NOTE

: Install a bi--flow filter drier whenever the system has

been opened for repair.

3. Check system for leaks using an approved method.
4. Evacuate refrigerant system and reclaim refrigerant if no

additional leaks are found.

5. Charge unit with R--410A refrigerant, using a

volumetriccharging cylinder or accurate scale. Refer to

unit rating plate for required charge.

604D

Содержание 604D024

Страница 1: ...rflow Airflow Adjustments 19 Defrost Control 19 Quiet Shift 19 Defrost 19 20 MAINTENANCE 20 25 Air Filter 21 Indoor Blower and Motor 21 Outdoor Coil Indoor Coil Condensate Drain Pan 21 Outdoor Fan 23...

Страница 2: ...roof curb Improperly applied gasketing also can result in air leaks and poor unit performance Curb should be level to within 1 4 in 6 mm See Fig 6 This is necessary for unit drain to function properl...

Страница 3: ...00 355 6 BOTTOM OF UNIT 0 50 12 7 NEC REQUIRED CLEARANCES INCHES mm BETWEEN UNITS POWER ENTRY SIDE 42 00 1066 8 UNIT AND UNGROUNDED SURFACES POWER ENTRY SIDE 36 00 914 0 UNIT AND BLOCK OR CONCRETE WA...

Страница 4: ...IT 0 50 12 7 NEC REQUIRED CLEARANCES INCHES mm BETWEEN UNITS POWER ENTRY SIDE 42 00 1066 8 UNIT AND UNGROUNDED SURFACES POWER ENTRY SIDE 36 00 914 0 UNIT AND BLOCK OR CONCRETE WALLS AND OTHER GROUNDED...

Страница 5: ...et if not already installed 1 Remove unit from shipping carton Leave top shipping skid on the unit for use as a spreader bar to prevent the rigging straps from damagingthe unit If theskid isnot availa...

Страница 6: ...also be used A BTyp Supply opening B x C Long Support D 445 16 Return opening B X C Insulate d deck pan Short Support CTyp C00076 UNIT SIZE ODS CATALOG NUMBER A IN MM B IN MM C IN MM D IN MM 604D024 0...

Страница 7: ...allation standards for residential heating and air conditioning systems OPTIONAL RETURN AIR OPENING OPTIONAL SUPPLY AIR OPENING EVAP COIL COND COIL 2 C99096 Fig 7 Slab Mounting Detail 5 Secure all duc...

Страница 8: ...rection of improper voltage and or phase imbalance 4 Insulate low voltage wires for highest voltage contained within conduit when low voltage control wires are in same conduit as high voltage wires 5...

Страница 9: ...high voltage raceway to the line wiring splice box See Fig 12 through 16 For singlephase units connect leads to the black and yellow wires for 3 phase units connect the leads to the black yellow and b...

Страница 10: ...NNECT PER NEC FROM POWER SOURCE RETURN AIR TOP COVER NEC NATIONAL ELECTRICAL CODE C00063 Fig 9 Typical Installation Duct Covers C00092 Fig 10 604D with Duct Covers On 1 MIN 2 MIN TRAP OUTLET C99013 Fi...

Страница 11: ...11 A07021 Fig 12 Wiring Schematics 604D Single Phase 604D...

Страница 12: ...12 A07014 Fig 13 Wiring Schematics 604D Three Phase 604D...

Страница 13: ...hat airflow delivered falls within proper range for the size unit installed This applies to all operational modes with the exception of electric heat modes See Fig 18 B as indicated c SYSTEM TYPE SELE...

Страница 14: ...N The following basic configuration of the indoor motor will provide ARI rated performance of the System This BASIC CONFIGURATION should be used when the rated ARI performance is required or if system...

Страница 15: ...is energized See Fig 18 During Super dehumidify mode the G signal is not present and the auxiliary terminals are not energized If the installation includes the use of the operating mode do not use the...

Страница 16: ...pump is also operating in either heating or defrost modes the motor will modify its airflow output if necessary to provide an airflow which is defined as safe for the operation of the electric heater...

Страница 17: ...nd G These completed circuits through the thermostat connect contactor coil C through unit wire Y and ECM board through unit wire G across the 24 v secondary of transformer TRAN Thermidistat or Thermo...

Страница 18: ...oper compressor 3 phase power lead orientation If not corrected within 5 minutes the internal protector will shut off the compressor The 3 phase power leads to the unit must be reversed to correct rot...

Страница 19: ...g the set up pins on the Easy Select board Unit 604D utilizes state of the art ECM Electronic Computated Motor ID Blower Motors Step 3 Defrost Control QUIET SHIFT Quiet Shift is a field selectable def...

Страница 20: ...5 0 039 0 043 048 0 027 0 032 0 036 0 041 0 046 0 052 0 057 0 063 0 068 060 0 029 0 032 0 036 0 040 0 045 0 049 0 053 again turn off for an additional 30 sec and the outdoor fan for 40 sec When the Qu...

Страница 21: ...necessary 4 Check electrical connections for tightness and controls for proper operation each cooling season Service when necessary Step 1 Air Filter IMPORTANT Never operate the unit without a suitabl...

Страница 22: ...41 39 36 33 30 384 108 103 98 93 88 2647 42 40 37 34 31 394 110 105 100 95 90 2716 44 41 38 35 32 404 112 107 102 97 92 2785 45 42 39 36 33 414 114 109 104 99 94 2854 46 43 40 37 34 424 116 111 106 1...

Страница 23: ...curely After inspecting the electrical controls and wiring replace all the panels Start the unit and observe at least one complete cooling cycle to ensure proper operation If discrepancies are observe...

Страница 24: ...pumps refrigerant throughout the system by the interaction of a stationary and an orbiting scroll The scroll compressor has no dynamic suction or discharge valves and it is more tolerant of stresses...

Страница 25: ...nder in upright position and a commercial metering device in manifold hose Charge refrigerant into suction line Step 14 System Information LOSS OF CHARGE SWITCH The loss of charge switch is a protecti...

Страница 26: ...driers with rated working pressures less than 600 psig S Do not leave Puron suction line filter driers in line longer than 72 hours S Do not install a suction line filter drier in liquid line S POE o...

Страница 27: ...utdoor unit Cooling Size C SYSTEM TYPE Select AC for Gas Package Units D AC HP CFM ADJUST Select NOM E ON OFF DELAY Do not use ENH for this unit F CONTINUOUS FAN Select desired speed 2 Remove Jumper J...

Страница 28: ...ne cause and correct Defective run start capacitor overload or start relay Determine cause and replace Defective thermostat Replace thermostat Faulty condenser fan motor or capacitor Replace Restricti...

Страница 29: ...r Purge as necessary NOTE After purging gas line of air wait at least 5 minutes for any gas to dissipate before attempting to light unit 2 Check gas valve Inadequate heating Dirty air filter Clean or...

Страница 30: ...PUMP SUPPLY AIR ___________ GAS HEAT SUPPLY AIR ___________ ELECTRIC HEAT SUPPLY AIR ___________ PRESSURES GAS INLET PRESSURE ___________IN WG GAS MANIFOLD PRESSURE ___________IN WG REFRIGERANT SUCTI...

Отзывы: