Installation Instructions

604D

SINGLE--PACKAGED HEAT PUMP UNITS

WITH PURON

R

(R--410A) REFRIGERANT

2--5 NOMINAL TONS (SIZES 018--060) 1 & 3 PHASE

NOTE

: Read the entire instruction manual before starting the

installation.

NOTE

: Installer: Make sure the Owner’s Manual and Service

Instructions are left with the unit after installation.

TABLE OF CONTENTS

PAGE

SAFETY CONSIDERATIONS

1

. . . . . . . . . . . . . . . . . . . . . . . .

INTRODUCTION

2

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

RECEIVING AND INSTALLATION

2--16

. . . . . . . . . . . . . . . .

Check Equipment

2

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Identify Unit

2

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Inspect Shipment

2

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Provide Unit Support

2

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Roof Curb

2

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Slab Mount

2

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Ground Mount

2

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Provide Clearances

2

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Rig and Place Unit

2

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Inspection

2

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Use of Rigging Bracket

5

. . . . . . . . . . . . . . . . . . . . . . . . . . .

Select and Install Ductwork

7

. . . . . . . . . . . . . . . . . . . . . . . . . .

Converting Horizontal Discharge Units to Downflow
(Vertical) Discharge Units

7

. . . . . . . . . . . . . . . . . . . . . . . . .

Provide for Condensate Disposal

7

. . . . . . . . . . . . . . . . . . . . .

Install Electrical Connections

8

. . . . . . . . . . . . . . . . . . . . . . . .

High--Voltage Connections

8

. . . . . . . . . . . . . . . . . . . . . . . .

Routing Power Leads into Unit

9

. . . . . . . . . . . . . . . . . . . . .

Connecting Ground lead to Ground Lug

9

. . . . . . . . . . . . . .

Routing Control Power Wires (24--v)

9

. . . . . . . . . . . . . . . .

Easy Select

t

9 & 13--16

. . . . . . . . . . . . . . . . . . . . . . . . . . .

604D Sequence of Operation

16

. . . . . . . . . . . . . . . . . . . . . .

Special Procedures for 208--V Operation

16

. . . . . . . . . . . . .

PRE--START--UP

16--17

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

START--UP

17--20

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Check for Refrigerant Leaks

17--18

. . . . . . . . . . . . . . . . . . . . .

Start--Up Adjustments

18

. . . . . . . . . . . . . . . . . . . . . . . . . . . .

Check Cooling & Heating Operation

18

. . . . . . . . . . . . . . . .

Checking & Adjusting Refrigerant Charge

18

. . . . . . . . . . .

Refrigerant Charge

18

. . . . . . . . . . . . . . . . . . . . . . . . . . . . .

No Charge

18

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Low Charge Cooling

19

. . . . . . . . . . . . . . . . . . . . . . . . . . . .

To Use Cooling Charging Charts

19

. . . . . . . . . . . . . . . . . . .

Indoor Airflow & Airflow Adjustments

19

. . . . . . . . . . . . .

Defrost Control

19

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Quiet Shift

19

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Defrost

19--20

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

MAINTENANCE

20--25

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Air Filter

21

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Indoor Blower and Motor

21

. . . . . . . . . . . . . . . . . . . . . . . . . .

Outdoor Coil, Indoor Coil, & Condensate Drain Pan

21

. . . . .

Outdoor Fan

23

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

A99338

Fig. 1 -- Unit 604D

Electrical Controls and Wiring

23

. . . . . . . . . . . . . . . . . . . . . .

Refrigerant Circuit

23

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Indoor Airflow

23

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Metering Devices-- TXV

23

. . . . . . . . . . . . . . . . . . . . . . . . . .

Pressure Switches

24

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Loss of Charge Switch

24

. . . . . . . . . . . . . . . . . . . . . . . . . . . .

High Pressure Switch

24

. . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Copeland Scroll compressor (Puron Refrigerant)

24

. . . . . . . .

Refrigerant System

24

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Refrigerant

24

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Compressor Oil

24

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Servicing Systems on Roofs with Synthetic Materials

24

. . .

Liquid Line Filter Drier

25

. . . . . . . . . . . . . . . . . . . . . . . . . .

Puron

R

(R--410A) Refrigerant Charging

25

. . . . . . . . . . . .

System Information

25

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Loss of Charge Switch

25

. . . . . . . . . . . . . . . . . . . . . . . . . . .

Check Defrost Thermostat

25

. . . . . . . . . . . . . . . . . . . . . . . .

TROUBLESHOOTING

25

. . . . . . . . . . . . . . . . . . . . . . . . . . . . .

START--UP CHECKLIST

25

. . . . . . . . . . . . . . . . . . . . . . . . . . .

SAFETY CONSIDERATIONS

Installation and servicing of this equipment can be hazardous due
to mechanical and electrical components. Only trained and

qualified personnel should install, repair, or service this
equipment.
Untrained personnel can perform basic maintenance functions

such as cleaning and replacing air filters. All other operations
must be performed by trained service personnel. When working

on this equipment, observe precautions in the literature, on tags,
and on labels attached to or shipped with the unit and other safety

precautions that may apply.
Follow all safety codes. Installation must be in compliance with

local and national building codes. Wear safety glasses, protective

clothing, and work gloves. Have fire extinguisher available. Read

Содержание 604D024

Страница 1: ...rflow Airflow Adjustments 19 Defrost Control 19 Quiet Shift 19 Defrost 19 20 MAINTENANCE 20 25 Air Filter 21 Indoor Blower and Motor 21 Outdoor Coil Indoor Coil Condensate Drain Pan 21 Outdoor Fan 23...

Страница 2: ...roof curb Improperly applied gasketing also can result in air leaks and poor unit performance Curb should be level to within 1 4 in 6 mm See Fig 6 This is necessary for unit drain to function properl...

Страница 3: ...00 355 6 BOTTOM OF UNIT 0 50 12 7 NEC REQUIRED CLEARANCES INCHES mm BETWEEN UNITS POWER ENTRY SIDE 42 00 1066 8 UNIT AND UNGROUNDED SURFACES POWER ENTRY SIDE 36 00 914 0 UNIT AND BLOCK OR CONCRETE WA...

Страница 4: ...IT 0 50 12 7 NEC REQUIRED CLEARANCES INCHES mm BETWEEN UNITS POWER ENTRY SIDE 42 00 1066 8 UNIT AND UNGROUNDED SURFACES POWER ENTRY SIDE 36 00 914 0 UNIT AND BLOCK OR CONCRETE WALLS AND OTHER GROUNDED...

Страница 5: ...et if not already installed 1 Remove unit from shipping carton Leave top shipping skid on the unit for use as a spreader bar to prevent the rigging straps from damagingthe unit If theskid isnot availa...

Страница 6: ...also be used A BTyp Supply opening B x C Long Support D 445 16 Return opening B X C Insulate d deck pan Short Support CTyp C00076 UNIT SIZE ODS CATALOG NUMBER A IN MM B IN MM C IN MM D IN MM 604D024 0...

Страница 7: ...allation standards for residential heating and air conditioning systems OPTIONAL RETURN AIR OPENING OPTIONAL SUPPLY AIR OPENING EVAP COIL COND COIL 2 C99096 Fig 7 Slab Mounting Detail 5 Secure all duc...

Страница 8: ...rection of improper voltage and or phase imbalance 4 Insulate low voltage wires for highest voltage contained within conduit when low voltage control wires are in same conduit as high voltage wires 5...

Страница 9: ...high voltage raceway to the line wiring splice box See Fig 12 through 16 For singlephase units connect leads to the black and yellow wires for 3 phase units connect the leads to the black yellow and b...

Страница 10: ...NNECT PER NEC FROM POWER SOURCE RETURN AIR TOP COVER NEC NATIONAL ELECTRICAL CODE C00063 Fig 9 Typical Installation Duct Covers C00092 Fig 10 604D with Duct Covers On 1 MIN 2 MIN TRAP OUTLET C99013 Fi...

Страница 11: ...11 A07021 Fig 12 Wiring Schematics 604D Single Phase 604D...

Страница 12: ...12 A07014 Fig 13 Wiring Schematics 604D Three Phase 604D...

Страница 13: ...hat airflow delivered falls within proper range for the size unit installed This applies to all operational modes with the exception of electric heat modes See Fig 18 B as indicated c SYSTEM TYPE SELE...

Страница 14: ...N The following basic configuration of the indoor motor will provide ARI rated performance of the System This BASIC CONFIGURATION should be used when the rated ARI performance is required or if system...

Страница 15: ...is energized See Fig 18 During Super dehumidify mode the G signal is not present and the auxiliary terminals are not energized If the installation includes the use of the operating mode do not use the...

Страница 16: ...pump is also operating in either heating or defrost modes the motor will modify its airflow output if necessary to provide an airflow which is defined as safe for the operation of the electric heater...

Страница 17: ...nd G These completed circuits through the thermostat connect contactor coil C through unit wire Y and ECM board through unit wire G across the 24 v secondary of transformer TRAN Thermidistat or Thermo...

Страница 18: ...oper compressor 3 phase power lead orientation If not corrected within 5 minutes the internal protector will shut off the compressor The 3 phase power leads to the unit must be reversed to correct rot...

Страница 19: ...g the set up pins on the Easy Select board Unit 604D utilizes state of the art ECM Electronic Computated Motor ID Blower Motors Step 3 Defrost Control QUIET SHIFT Quiet Shift is a field selectable def...

Страница 20: ...5 0 039 0 043 048 0 027 0 032 0 036 0 041 0 046 0 052 0 057 0 063 0 068 060 0 029 0 032 0 036 0 040 0 045 0 049 0 053 again turn off for an additional 30 sec and the outdoor fan for 40 sec When the Qu...

Страница 21: ...necessary 4 Check electrical connections for tightness and controls for proper operation each cooling season Service when necessary Step 1 Air Filter IMPORTANT Never operate the unit without a suitabl...

Страница 22: ...41 39 36 33 30 384 108 103 98 93 88 2647 42 40 37 34 31 394 110 105 100 95 90 2716 44 41 38 35 32 404 112 107 102 97 92 2785 45 42 39 36 33 414 114 109 104 99 94 2854 46 43 40 37 34 424 116 111 106 1...

Страница 23: ...curely After inspecting the electrical controls and wiring replace all the panels Start the unit and observe at least one complete cooling cycle to ensure proper operation If discrepancies are observe...

Страница 24: ...pumps refrigerant throughout the system by the interaction of a stationary and an orbiting scroll The scroll compressor has no dynamic suction or discharge valves and it is more tolerant of stresses...

Страница 25: ...nder in upright position and a commercial metering device in manifold hose Charge refrigerant into suction line Step 14 System Information LOSS OF CHARGE SWITCH The loss of charge switch is a protecti...

Страница 26: ...driers with rated working pressures less than 600 psig S Do not leave Puron suction line filter driers in line longer than 72 hours S Do not install a suction line filter drier in liquid line S POE o...

Страница 27: ...utdoor unit Cooling Size C SYSTEM TYPE Select AC for Gas Package Units D AC HP CFM ADJUST Select NOM E ON OFF DELAY Do not use ENH for this unit F CONTINUOUS FAN Select desired speed 2 Remove Jumper J...

Страница 28: ...ne cause and correct Defective run start capacitor overload or start relay Determine cause and replace Defective thermostat Replace thermostat Faulty condenser fan motor or capacitor Replace Restricti...

Страница 29: ...r Purge as necessary NOTE After purging gas line of air wait at least 5 minutes for any gas to dissipate before attempting to light unit 2 Check gas valve Inadequate heating Dirty air filter Clean or...

Страница 30: ...PUMP SUPPLY AIR ___________ GAS HEAT SUPPLY AIR ___________ ELECTRIC HEAT SUPPLY AIR ___________ PRESSURES GAS INLET PRESSURE ___________IN WG GAS MANIFOLD PRESSURE ___________IN WG REFRIGERANT SUCTI...

Отзывы: