Using plotted operating point:
If plotted operating condition is --
Adjust charge by --
BELOW the curve
REDUCE charge
ABOVE the curve
ADD charge
Final Checks —
Ensure that all safety controls are operating, control panel
covers are on, and the service panels are in place.