14
Table 7 – 569J*12F HGBP Piping Recommendations (Two-Circuit Unit)
NOTE
: 569J*12F units require TWO sets of refrigeration piping
Linear Length
Ft
0-25
25-50
50-75
75-100
100-125
m
0-8
8-15
15-23
23-30
30-38
Equivalent
Length
Ft
0-38
38-75
75-113
113-150
150-188
m
0-12
12-23
23-34
34-46
46-57
Model
569J*12F
Liquid Line
3
/
8
3
/
8
3
/
8
3
/
8
1
/
2
3
/
8
1
/
2
Pressure Drop
1.8
3.5
5.2
8.7
1.2
8.7
1.5
Max Lift
25
50
75
65
100
62
125
Pressure Drop
3.8
7.5
11.3
12.2
9.4
13.7
11.7
Suction Line
Circuit 1:
VAPOR RISER REQUIRED, NOT GREATER THAN 20 FT (6.1 M) --- See Fig. 5)
Tube S
5
/
8
1-
1
/
8
1-
3
/
8
1-
3
/
8
1-
3
/
8
Tube A
5
/
8
5
/
8
5
/
8
5
/
8
5
/
8
Pressure Drop
2.0
2.0
1.9
2.0
2.0
Circuit 1:
VAPOR RISER GREATER THAN 20 FT (6.1 M) --- See Fig. 6)
Tube S
5
/
8
7
/
8
7
/
8
1-
1
/
8
1-
1
/
8
Tube A
5
/
8
5
/
8
5
/
8
5
/
8
5
/
8
Tube B
NR
1
/
2
5
/
8
5
/
8
5
/
8
Pressure Drop
2.0
1.6
1.7
1.7
2.1
Circuit 1:
NO VAPOR RISER REQUIRED
7
/
8
7
/
8
1-
1
/
8
1-
1
/
8
1-
1
/
8
Circuit 2:
7
/
8
7
/
8
1-
1
/
8
1-
1
/
8
1-
1
/
8
Pressure Drop
1.1
2.1
0.9
1.2
1.5
Charge (lbs) 1/2
13.3
14.3
15.8
16.9
20.0
18.1
22.0
Legend:
Equivalent Length
Equivalent tubing length, including effects of refrigeration specialties devices
Linear Length
Typical linear tubing length (50% added to linear to define Equivalent Length for this table)
Liquid Line
Tubing size, inches OD.
Max Lift
Maximum liquid lift (indoor unit ABOVE outdoor unit only), at maximum permitted liquid line pressure drop —
S
Linear Length Less than 75 ft (23 m): Minimum 2.0° F subcooling entering TXV
S
Linear Length Greater than 75 ft (23m): Minimum 0.5° F subcooling entering TXV
Suction Line
Tube size, inches OD
Charge
Charge Quantity, lbs. Calculated for both liquid line sizes (where applicable), but only with larger suction line size (where applicable)
NOTE:
For applications with equivalent length greater than 188 ft (57 m) and/or linear length greater than 125 ft (38 m), contact your local
Bryant representative.
569J
Содержание 569J Series
Страница 34: ...34 C10925 Fig 29 Typical Single Circuit Single Stage 569J A B Wiring Diagram 569J ...
Страница 35: ...35 C150339 Fig 30 Typical Single Circuit Two Stage 569J 07G H Wiring Diagram 569J ...
Страница 36: ...36 C12547 Fig 31 Typical Dual Circuit Two Stage 569J D E F Wiring Diagram 569J ...
Страница 51: ...51 569J 07 08A B 569J 12A B 569J 14A B C11098 Fig 42 569J 07 14A B Motormaster Sensor Locations RTPF 569J ...
Страница 52: ...52 569J 12D E F 569J 14D E C12551 Fig 43 569J 12 14D E F Motormaster Sensor Locations RTPF 569J ...
Страница 53: ...53 D K J H G F E C B A C10800 Fig 44 Wind Baffles 569J ...