![Bryant 569J Series Скачать руководство пользователя страница 24](http://html.mh-extra.com/html/bryant/569j-series/569j-series_installation-start-up-and-service-instructions-manual_2822095024.webp)
24
Table 11 – Electrical Data — 569J*07--14A/B/G/H 60 Hz Units
WITHOUT POWERED CONVENIENCE OUTLET
UNIT
V---Ph---Hz
VOLTAGE
RANGE
}
COMPRESSOR 1
OFM (ea)
POWER
SUPPLY
DISCONNECT SIZE
MIN
MAX
RLA
LRA
QTY
FLA
MCA
Fuse or
HACR
Brkr
FLA
LRA
569J*07A/B
Units produced
on or after
02/09/2015
208/230---3---60
187
253
19.6
136
2
1.5
28/28
45/45
26/26
142/142
460---3---60
414
506
8.2
66
2
0.8
12
20
11
70
575---3---60
518
633
6.6
55
2
0.7
10
15
9
59
569J*07A/B
Units produced
on or prior to
02/08/2015
208/230---3---60
187
253
19.0
123
2
1.5
26.8/26.8
45/45
25/25
129/129
460---3---60
414
506
9.7
62
2
0.8
13.7
20
13
66
575---3---60
518
633
7.4
50
2
0.7
10.4
15
10
54
569J*07G/H
208/230---3---60
187
253
17.5
136
2
1.5
25/25
30/30
24/24
142/142
460---3---60
414
506
8.4
66
2
0.8
13
20
12
70
575---3---60
518
633
6.6
55
2
0.7
10
15
9
59
569J*08A/B
208/230---3---60
187
253
25.0
164
2
1.5
35/35
50/50
32/32
170/170
460---3---60
414
506
12.2
100
2
0.8
17
25
16
104
575---3---60
518
633
9.0
78
2
0.7
13
20
12
82
569J*12A/B
208/230---3---60
187
253
30.1
225
2
1.5
41/41
60/60
38/38
231/231
460---3---60
414
506
16.7
114
2
0.8
23
30
21
118
575---3---60
518
633
12.2
80
2
0.7
17
25
16
84
569J*14A/B
208/230---3---60
187
253
48.1
245
2
1.5
64/64
80/80
59/59
251/251
460---3---60
414
506
18.6
125
2
0.8
25
30
23
129
575---3---60
518
633
14.7
100
2
0.7
20
30
19
104
WITH POWERED CONVENIENCE OUTLET
UNIT
V---Ph---Hz
VOLTAGE
RANGE
}
COMPRESSOR 1
OFM (ea)
POWER
SUPPLY
DISCONNECT SIZE
MIN
MAX
RLA
LRA
QTY
FLA
MCA
Fuse or
HACR
Brkr
FLA
LRA
569J*07A/B
Units produced
on or after
02/09/2015
208/230---3---60
187
253
19.6
136
2
1.5
33/33
50/50
32/32
147/147
460---3---60
414
506
8.2
66
2
0.8
15
20
14
72
575---3---60
518
633
6.6
55
2
0.7
12
15
11
61
569J*07A/B
Units produced
on or prior to
02/08/2015
208/230---3---60
187
253
19.0
123
2
1.5
31.6/31.6
50/50
31/31
134/134
460---3---60
414
506
9.7
62
2
0.8
15.9
25
16
68
575---3---60
518
633
7.4
50
2
0.7
12.1
15
12
56
569J*07G/H
208/230---3---60
187
253
17.5
136
2
1.5
30/30
45/45
29/29
147/147
460---3---60
414
506
8.4
66
2
0.8
15
20
14
72
575---3---60
518
633
6.3
55
2
0.7
11
15
11
61
569J*08A/B
208/230---3---60
187
253
25.0
164
2
1.5
40/40
60/60
38/38
175/175
460---3---60
414
506
12.2
100
2
0.8
20
30
18
106
575---3---60
518
633
9.0
78
2
0.7
15
20
14
84
569J*12A/B
208/230---3---60
187
253
30.1
225
2
1.5
46/46
60/60
44/44
236/236
460---3---60
414
506
16.7
114
2
0.8
25
30
24
120
575---3---60
518
633
12.2
80
2
0.7
19
30
18
86
569J*14A/B
208/230---3---60
187
253
48.1
245
2
1.5
68/68
80/80
64/64
256/256
460---3---60
414
506
18.6
125
2
0.8
28
45
26
131
575---3---60
518
633
14.7
100
2
0.7
22
30
20
106
NOTE
: See “Legend and Notes for Tables 11 and 12” on page 25.
569J
Содержание 569J Series
Страница 34: ...34 C10925 Fig 29 Typical Single Circuit Single Stage 569J A B Wiring Diagram 569J ...
Страница 35: ...35 C150339 Fig 30 Typical Single Circuit Two Stage 569J 07G H Wiring Diagram 569J ...
Страница 36: ...36 C12547 Fig 31 Typical Dual Circuit Two Stage 569J D E F Wiring Diagram 569J ...
Страница 51: ...51 569J 07 08A B 569J 12A B 569J 14A B C11098 Fig 42 569J 07 14A B Motormaster Sensor Locations RTPF 569J ...
Страница 52: ...52 569J 12D E F 569J 14D E C12551 Fig 43 569J 12 14D E F Motormaster Sensor Locations RTPF 569J ...
Страница 53: ...53 D K J H G F E C B A C10800 Fig 44 Wind Baffles 569J ...