11
NOTE
: If vibration isolators are required for a particular
installation, use the data in Fig. 3 to make the proper
selection.
Step 3 — Prepare Unit Mounting Support
Slab Mount —
Provide a level concrete slab that extends a minimum of 6
in. (150 mm) beyond unit cabinet. Install a gravel apron in
front of condenser coil air inlet to prevent grass and
foliage from obstructing airflow.
Step 4 — Rig and Mount the Unit
UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment
damage.
All panels must be in place when rigging. Unit is not
designed for handling by fork truck.
CAUTION
!
Rigging
: These units are designed for overhead rigging.
Refer to the rigging label for preferred rigging method.
Spreader bars are not required if top crating is left on the
unit. All panels must be in place when rigging. As further
protection for coil faces, plywood sheets may be placed
against the sides of the unit, behind cables. Run cables to
a central suspension point so that the angle from the
horizontal is not less than 45 degrees. Raise and set the
unit down carefully.
If it is necessary to roll the unit into position, mount the
unit on longitudinal rails, using a minimum of 3 rollers.
Apply force to the rails, not the unit. If the unit is to be
skidded into position, place it on a large pad and drag it
by the pad. Do not apply any force to the unit.
Raise from above to lift the unit from the rails or pad
when unit is in its final position.
After the unit is in position, remove all shipping materials
and top crating.
Step 5 — Determine Refrigerant Line Sizes
Select the recommended line sizes for 569J***A/B/G/H
and 569J***D/E/F unit from the appropriate tables.
Determine the linear length of interconnecting piping
required between the outdoor unit and indoor unit
(evaporator). Consider and identify also the arrangement
of the tubing path (quantity and type of elbows in both
lines), liquid line solenoid size, filter drier and any other
refrigeration specialties located in the liquid line. Refer to
the indoor unit installation instructions for additional
details on refrigeration specialties devices.
Determine equivalent line length adjustments for path and
components and add to linear line lengths. See Table 4,
Equivalent Lengths for Common Fittings, for usual fitting
types. Also identify adjustments for refrigeration
specialties. Contact Bryant Applications Engineering for
additional data and information on equivalent lengths.
Table 4 – Equivalent Lengths for Common Fittings (ft)
Nominal
Tube OD
Elbows
90
Std
90
Lrad 90
Street
45
Std
45
Street
3
/
8
1.3
0.8
2.2
0.6
1
1
/
2
1.4
0.9
2.3
0.7
1.1
5
/
8
1.6
1
2.5
0.8
1.3
3
/
4
1.8
1.2
2.9
0.9
1.5
7/8
2
1.4
3.2
0.9
1.6
1
1
/
8
2.6
1.7
4.1
1.3
2.1
1
3
/
8
3.3
2.3
5.6
1.7
3
1
5
/
8
4
2.6
6.3
2.1
3.4
2
1
/
8
5
3.3
8.2
2.6
4.5
Nominal
Tube OD
Tees
Branch
Flow
Straight-Thru
No Reduct
Reduce 25% Reduce 50%
3
/
8
2.6
0.8
1.1
1.3
1
/
2
2.7
0.9
1.2
1.4
5
/
8
3
1
1.4
1.6
3
/
4
3.5
1.2
1.7
1.8
7/8
4
1.4
1.9
2
1
1
/
8
5
1.7
2.3
2.6
1
3
/
8
7
2.3
3.1
3.3
1
5
/
8
8
2.6
3.7
4
2
1
/
8
10
3.3
4.7
5
NOTE
: Equivalent line lengths will vary based on tube
diameter. Calculate equivalent line length for each pipe by
adding equivalent length adjustments to linear lengths for
each pipe.
Enter the appropriate table to select the recommended line
sizes.
Model/
Position #8
Table
Quantity of Line Sets
569J***A/B/G/H
5
1
569J***D/E
6
2
569J*12F
7
2
Liquid Lift —
A liquid lift condition exists when the outdoor unit is located
below the indoor (evaporator) unit and liquid flows vertically
up in a portion of the liquid line. The vertical column of
liquid reduces the available state point subcooling at the
evaporator coil’s thermal expansion valve. This effect
reduces the length of liquid lift (feet of elevation) that a
liquid line size can accommodate. Longer linear tube lengths
will also reduce the amount of liquid lift possible.
Check Tables 5 (569J***A/B/G/H), 6 (569J***D/E) and 7
(569J*12F) for maximum liquid lift capabilities for line
sizes. Reselect the liquid line tube size if necessary. If
maximum available tube size cannot provide the required lift
distance on this installation, relocate the outdoor unit to
reduce the equivalent line length or the lift requirement.
569J
Содержание 569J Series
Страница 34: ...34 C10925 Fig 29 Typical Single Circuit Single Stage 569J A B Wiring Diagram 569J ...
Страница 35: ...35 C150339 Fig 30 Typical Single Circuit Two Stage 569J 07G H Wiring Diagram 569J ...
Страница 36: ...36 C12547 Fig 31 Typical Dual Circuit Two Stage 569J D E F Wiring Diagram 569J ...
Страница 51: ...51 569J 07 08A B 569J 12A B 569J 14A B C11098 Fig 42 569J 07 14A B Motormaster Sensor Locations RTPF 569J ...
Страница 52: ...52 569J 12D E F 569J 14D E C12551 Fig 43 569J 12 14D E F Motormaster Sensor Locations RTPF 569J ...
Страница 53: ...53 D K J H G F E C B A C10800 Fig 44 Wind Baffles 569J ...