ELECTRICAL CONNECTIONS
8.1 Installation Warnings
CAUTION
The supply voltage to the MagnaTech unit
must not be disconnected, except for service
or isolation, or unless otherwise instructed by
procedures outlined in this manual. To signal
a call for heat, use the 24V field interlock, as
shown in the wiring diagram.
DO NOT MAKE AND BREAK THE LINE
VOLTAGE TO THE MagnaTech UNIT TO
SIGNAL A CALL FOR HEAT. A call for heat/
end call for heat MUST be connected to the
field interlock terminals. Some MagnaTech
components are designed to have constant
voltage during normal operation. If the
MagnaTech’s supply voltage is toggled as a
call for heat signal, premature failure of these
components may result.
The MagnaTech unit does not recognize 4mA
as a signal to shut off. If the call for heat is not
connected between the field interlock terminals,
the MagnaTech will remain in low fire when it
sees 4mA as a modulating signal.
8.2 Main Power Connections
MagnaTech is provided with an electrical junction
box in the rear panel for easy connections and all
wires are factory installed between this junction box
and the Main High Voltage Box. The MagnaTech
line is equipped with multiple voltage packages to
adapt to customer needs ranging from 120-600 volts
with single or 3 phase versions. Refer to the rating
plate for appropriate voltage and current ratings. As
a common industry practice, Bradford White has
color coded the single and three phase wires.
WARNING
The appliance must be electrically grounded in
accordance with the requirements of the authority
having jurisdiction or, in the absence of such
requirements, with the latest edition of the National
Electrical Code, ANSI/NFPA 70, in the U.S. and
with the latest edition of CSA C22.1 Canadian
Electrical Code, Part 1, in Canada. Do not rely
on the gas or water piping to ground the metal
parts of the boiler. Plastic pipe or dielectric unions
may isolate the boiler electrically. Service and
maintenance personnel, who work on or around
the boiler, may be standing on wet floors and
could be electrocuted by an ungrounded boiler.
Electrocution can result in severe injury or death.
Single pole switches, including those of safety
controls and protective devices, must not be wired
in a grounded line.
All electrical connections are made on the terminal
blocks that are located inside the control panel.
Wiring connections are shown in Figure 34.
All internal electrical components have been
prewired. No attempt should be made to connect
electrical wires to any other location except the
terminal blocks.
Three Phase
Single Phase
600
480
208
120
240
L1
P
BR
Blk
L1
Blk
Blk
L2
V
O
R
L2
Wht
R
L3
T
Y
BL
Table 12.
Phase Voltage Color Identification
On three phase models a step down transformer
(which is protected using an appropriate din rail
mounted circuit breaker) generates 120 volt single
phase to power the 24 Volt Transformer. The 120
volt and 24 volt outputs of either transformer are
protected with resettable fuses mounted in the top
of the high voltage box. The 24 volt transformer is
also redundantly protected by its integrated 4 amp
resettable fuse.
Содержание MagnaTech BMGH1600
Страница 4: ...BRADFORD WHITE ...
Страница 35: ...Page 31 MagnaTech BOILERS AND VOLUME WATER HEATERS ...
Страница 98: ...Page 94 BRADFORD WHITE 1 13 12 4 3 5 13 2 15 Final Assembly DETAIL A 9 10 8 Final Assembly ...
Страница 110: ...Page 106 BRADFORD WHITE 6 2 7 11 1 5 4 12 10 3 3 8 9 6 Control Panel Assembly ...
Страница 114: ...Page 110 BRADFORD WHITE 7 8 15 14 9 4 16 12 5 1 6 2 11 AC DISTRIBUTION BOX ASSEMBLY PART NUMBERS MODELS 2500 AND 3500 ...