Section 2 Installation
14
Figure 2-1 Typical Installation
A - Inlet Valve
B - O utlet Valve
C - Bypass Valve
D - Control Valve
E - Drain Valve
HO RIZO NTAL
LINE
D
A
E
C
VERTICAL
LINE
B
B
A
E
FLO W M ETER
C
D
FLO W M ETER
A. For intrinsically safe operation (recognized by a BLUE COVER),
intrinsic safety barrier selection, cable parameters and power supply
limits must be in accordance with the entity parameters shown on
drawing.
B. If the area classification is a Division 2 or Zone 2, a barrier is not
required. Note however when intrinsic safe apparatus is used without
barrier, this apparatus may
NOT
be considered as intrinsically safe.
This is because input protection diodes may be damaged without
affecting normal operation. It is the customers’ responsibility to clearly
mark the apparatus when intrinsic safety is no longer valid.
C. Connect the IS Alarm as shown in Figures 2-2 and 2-3.
Figure 2-2 Inductive Switch Wiring Diagram
DUAL SWITCH:
RELAY SHOWN P.&F. TYPE KF**-SR2-EX2.W
Brooks
®
Ar-Mite
TM
MT3750C
Brooks
®
Ar-Mite
TM
MT3750C
Содержание Ar-Mite MT3750
Страница 15: ...Section 1 Introduction 11 Figure 1 10 Dimensions for MT3750C Panel Mounting Brooks Ar MiteTM MT3750C...
Страница 19: ...Section 2 Installation 15 Figure 2 3 Inductive Switch Wiring Brooks Ar MiteTM MT3750C...
Страница 24: ...Section 2 Installation 20 Figure 2 7 Transmitter Wiring Diagram for I S Systems Brooks Ar MiteTM MT3750C...
Страница 25: ...Section 2 Installation 21 Figure 2 8 Transmitter Wiring Diagram for XP Systems Brooks Ar MiteTM MT3750C...
Страница 26: ...Section 2 Installation Brooks Ar MiteTM MT3750C 22 Figure 2 9 Transmitter Wiring Diagram...
Страница 30: ...Section 3 Operation Brooks Ar MiteTM MT3750C 26 Figure 3 1 Reed Switch Alarm...
Страница 34: ...Section 5 Parts List 30 Figure 5 1 Model MT3750 Exploded View Brooks Ar MiteTM MT3750C...