Section 3 Operation
Brooks
®
Ar-Mite
TM
MT3750C
25
low alarm circuits. In the first of these configurations, an alarm is
always active. If the flow rate is under the set point, the low alarm
circuit
is closed. If the flow exceeds the set point, the low alarm
circuit opens and the hi alarm circuit closes. There is hysteresis
associated with reed switches, so the flow rates at which the alarm
switches between HI and
LO will be slightly different depending on
whether the flow rate is
increasing or decreasing.
The second “Dual” alarm option allows separately adjusting the set
points for low flow alarm and high flow alarm within a limited range of
the maximum flow rate of the meter.
The dual setpoint alarm is set in the same manner as described in
Section 3-4. Simply use two ohmmeters to observe the behavior of
both circuits.
Table 3-1 Interior Label MT 3750 Ar-Mite Alarm.
Alarm Programming Table
Alarm
Jumper
Adjust Upper
Lower
Flow
Positions
Sensor in
Sensor
Range
Region (2)
Position
High, 60-100%
J-2,5,7
B
Bottom
of Slot
High, 40-75%
J-1,4,6
A
Bottom
of Slot
High, 0-40%
J-1,3,5
B
Bottom
of Slot
Low, 55-100%
J-2,3,7
B
Bottom
of Slot
Low, 40-75%
J-1,4,6
A
Bottom
of Slot
Low, 0-40%
J-1,5,7
B
Bottom
of Slot
Dual:
High, 40-75%
J-1,4,6
A
Bottom
Low, 30-60%
of Slot
Dual:
High, 40-75%
J-1,6,8
A
Region B
Low, 10-45%
(High Set)
(Low Set)
(1) These ranges for reference only.
(2) Final sensor position may be slightly outside of these ranges.
Содержание Ar-Mite MT3750
Страница 15: ...Section 1 Introduction 11 Figure 1 10 Dimensions for MT3750C Panel Mounting Brooks Ar MiteTM MT3750C...
Страница 19: ...Section 2 Installation 15 Figure 2 3 Inductive Switch Wiring Brooks Ar MiteTM MT3750C...
Страница 24: ...Section 2 Installation 20 Figure 2 7 Transmitter Wiring Diagram for I S Systems Brooks Ar MiteTM MT3750C...
Страница 25: ...Section 2 Installation 21 Figure 2 8 Transmitter Wiring Diagram for XP Systems Brooks Ar MiteTM MT3750C...
Страница 26: ...Section 2 Installation Brooks Ar MiteTM MT3750C 22 Figure 2 9 Transmitter Wiring Diagram...
Страница 30: ...Section 3 Operation Brooks Ar MiteTM MT3750C 26 Figure 3 1 Reed Switch Alarm...
Страница 34: ...Section 5 Parts List 30 Figure 5 1 Model MT3750 Exploded View Brooks Ar MiteTM MT3750C...