JB-QB-5Ei Users’ Manual
39
JB-QB-5Ei
Fire Alarm Control Panel
7) Control panel will be in time delay status, if the time delay finish, the YA1/YA2 contacts
of fire alarm delay relay will be short.
Attention
: press the silence key during the fire
delay, the time delay will be canceled and fire alarm delay relay will not be activated.
The fire alarm status of fire alarm control panel can only be reset by manually pressing the reset
key. In fire alarm status, the display will return to the last fire alarm page if no operating occur
during 30 second
6.3 supervisory alarm
Supervisory signal is the input signals connected to the fire alarm control panel . they are not the
signal in the fire alarm control panel. Such as: water level detect, pressure, temperature, air
condition, and so on. The fire alarm control panel will be in supervisory alarm status if these
signals activated. Then the control panel will enforce the following actions:
1) Send out supervisory alarm sound, light the supervisory indicator in the front panel.
2) Display current supervisory alarm message detail in LCD screen, update the supervisory
alarm sum, and so on.
3) If the control panel is in auto status, control panel will control the relative devices
according to the logic setting in the menu.
4) Record the supervisory alarm message to the black box.
5) Send out supervisory alarm message to fire alarm repeater and VDR(if the relative item
is enable in the setting )
If the item “system manage>>supervisory alarm auto reset” is set to “Yes”, the supervisory alarm
status will be reset if the supervisory signal is canceled. If that item is set to “No”, the supervisory
alarm status can only be reset by manually pressing the reset key.
6.4 Fire alarm control (association control)
If the fire alarm device or other fire fighting association control device are started, the control
panel will enforce the following operations:
1
)
send out association control sound, light the association indicator in the front panel.
2
)
Current association message detail will be displayed in LCD screen, update the
association sum, started sum and feedback sum, and so on.
3
)
If started device’s feedback signal is received, control panel will control the relative
devices according to the logic setting in the menu (in manual status, the setting is “start
only in auto status” in “system manage” ).
4
)
Record the association message to black box(if enable).
5
)
Send out association message to fire alarm repeater and VDR(if enable)
6.5 fault alarm
Fire alarm control panel will send out fault alarm if the following conditions are occurred.:
1) The wires between control panel and detector are broken, short, the detector is
disconnected from the base and detector’s bad
2) The communication lines between control panel and fire alarm repeater are broken or
short
3) The wires between control panel and fire alarm device or fire fighting control device are
broken or short .