JB-QB-5Ei Users’ Manual
35
JB-QB-5Ei
Fire Alarm Control Panel
Record select
MENU-status,ENTER-save,ESC-return
Record supervisory signal
Yes
01/05
Record select
MENU-status,ENTER-save,ESC-return
Record supervisory signal
Yes
01/05
Figure 17 Record select function setting
System management
,
in debugging menu, press
【
6
】
key to enter system management function
(Figure 18), there are several important operation parameters shown as below in the system
management
:
7.System
ENTER-save,ESC-return
Fire repeater ConnectLine Fault
Yes
MENU-status
7.System
ENTER-save,ESC-return
Fire repeater ConnectLine Fault
Yes
02/13
MENU-status
Figure 18 system management function setting
1)
Fire repeater Connectline fault: whether to permit poll fire alarm repeater, if yes, when
there is communication fault between the panel and fire repeater, it will send out fault
information.
2)
This panel number
:
to be used to set up this panel number.
3)
Link-done only Autostatus: if yes, the controller can only auto start when it is in
auto-status.
4)
Send alarm information to VDR
:
whether to send alarm information to VDR or not.
5)
This panel capacity
:
each loop can connect 250 addressable bus devices. But due to
customer consideration, maybe we will reduce the addressable device points for each
loop to meet specific project addressable points requirement. The panel loop capacity is
fixed in our factory and the user cannot modify the capacity by themselves.
6)
Shut down LCD backlight in spare time: if the “Yes” selected, the fire alarm control
panel will shut down LCD backlight if no alarm occur(except main power and backup
power fault). When the control panel is supplied by
backup power, it can make the
using time longer.
7)
System language: Chinese or English
8)
Alarm output delay: 0~250 seconds
9)
Supervisory auto cancel: if “Yes” set in the menu, supervisory alarm can auto be
canceled if the supervisory signal cancel.
10) Fault output close: if “Yes” set in the menu, the output contact is close in normal
condition. If the fault alarm occur or the fire alarm control panel is powered off, the
output contact will be changed to open.