JB-QB-5Ei Users’ Manual
29
JB-QB-5Ei
Fire Alarm Control Panel
5 Installation, debugging
5.1 External wiring terminal layout diagram
L
OO
P2
O
UT
L
OO
P2
IN
IN
L
OO
P1
T+
T-
T-
T+
T+
T-
L
OO
P1
O
UT
Fault output(DC30V 1A)
Out2_NC
Out2_NO
Out2_C
Power fault output(DC30V 1A)
Out1_NC
Out1_NO
Out1_C
Fire alarm delay output(DC30V 3A)
YA1
YA2
KA1
KA2
FB
FA
MB
MA
Fire alarm output(DC30V 3A)
Fire alarm repeater communication line(RS485)
VDR interface(RS485)
Loop2
Loop 1
GND
24V
DC24V output(0.5A)
DC24V Backup
input(0.75A)
AC220V Main power
input(0.5A)
T-
T+
DC+
DC-
N
L
Figure 4 fire alarm control panel external wiring terminal layout diagram
Note:
1) only open dry contacts for fault output and power fault output in flushing mounting type control
panel, their output logic can be set in system setting menu;
2) the VDR interface output real marks may be different, for example: VDR+,VDR-
5.2 Installation Technical Requirement
Fire alarm control panel should be in good earth protection. There is earth symbol inside
the panel.
Fire alarm control panel should be installed in the room or location where there is person
in charge. The distance from the panel bottom side to the floor should be 1.5 meters.
Both sides should have more than 0.5 meters space to make operation and maintenance
as easy as possible.
24V power supply line adopts fire resistant multi-core plastic flexible cable whose size
is no less than 2.5mm
2
. When the transmit distance is less than 1000 meters, the signal
line can be RVS-2×1.0mm
2
twin-color twisted multi-core plastic flexible wire. When the
transmit distance is less than 1500 meters, the signal line can
be RVS-2×1.5mm
2
twin-color twisted multi-core plastic flexible wire.
Before debugging, construction side should install bus devices into proper positions and
connect them into alarm bus based on construction blueprint and various bus device
operation manuals.