5.3 the steps in debugging
5.3.1 Wiring
1)
Based on construction blueprint, check and make sure that all input output lead lines
specifications which are connected to this panel will meet design drawing requirement.
2)
Use 500V mega-meter to check all input output terminal wires, whose earth resistor
value should be equal or great than 20MΩ. If the terminal wires cannot meet this
requirement, please solve this problem , then start next step.
3)
Connect the wire to the terminals based on “external wiring terminal layout diagram”.
5.3.2 Power on machine
Open fire alarm control panel front door, simultaneously power on main power supply and
back-up power supply switch. The fire alarm control panel is initialized, indicator LEDs and
sounders will be in self-testing and in normal operating mode showed in Figure 5. The power
supply LED flashes. At this time, press the
【
menu
】
key and control panel enters debugging status.
Input the correct password (Figure 6) and the control panel will be in debugging menu (Figure 7).
Attention! The number in the debugging menu can’t mean debugging steps or sequence.
Figure 5 FACP normal operating mode
Please entry supervisor password
★★★★
Security
Please entry supervisor password
★★★★
Security
Figure 6 input password