background image

Model

kW

Volts

Phase

Amp Draw

Breaker or

Copper

Conduit

L1

L2

L3

Fuse Size

Wire Size

Size

LI663CFC

6

208

1

29

29

-

40

8

1/2" (13 mm)

LI663CFD

6

208

3

14

25

14

40

8

1/2" (13 mm)

LI663CFE

6

240

1

25

25

-

40

8

1/2" (13 mm)

LI663CFF

6

240

3

13

22

13

30

10

1/2" (13 mm)

LI663CFM

6

480

3

6

11

6

15

14

1/2" (13 mm)

LI693CFC

9

208

1

43

43

-

60

6

1/2" (13 mm)

LI693CFD

9

208

3

22

38

22

50

8

1/2" (13 mm)

LI693CFE

9

240

1

38

38

-

50

8

1/2" (13 mm)

LI693CFF

9

240

3

19

33

19

50

8

1/2" (13 mm)

LI693CFM

9

480

3

9

16

9

20

12

1/2" (13 mm)

LI6123CFC

12

208

1

58

58

-

90

3

1" (25 mm)

LI6123CFD

12

208

3

33

33

33

50

8

1/2" (13 mm)

LI6123CFE

12

240

1

50

50

-

70

6

1/2" (13 mm)

LI6123CFF

12

240

3

29

29

29

40

8

1/2" (13 mm)

LI6123CFM

12

480

3

14.5

14.5

14.5

20

12

1/2" (13 mm)

LI6153CFC

15

208

1

72

72

-

90

3

1" (25 mm)

LI6153CFD

15

208

3

41.7

41.7

41.7

60

6

3/4" (19 mm)

LI6153CFE

15

240

1

62.5

62.5

-

90

3

1" (25 mm)

LI6153CFF

15

240

3

36.1

36.1

36.1

50

8

1/2" (13 mm)

LI6153CFM

15

480

3

18.1

18.1

18.1

30

10

1/2" (13 mm)

LI6183CFC

18

208

1

86.5

86.5

-

125

1

1-1/4" (32 mm)

LI6183CFE

18

240

1

75

75

-

100

3

1" (25 mm)

LI6183CFF

18

240

3

43.4

43.4

43.4

60

6

3/4" (19 mm)

LI6183CFM

18

480

3

21.7

21.7

21.7

30

10

1/2" (13 mm)

LI6243CFC

24

208

1

115.4

115.4

-

150

1/0

1-1/4" (32 mm)

LI6243CFD

24

208

3

66.7

66.7

66.7

90

3

1" (25 mm)

LI6243CFE

24

240

1

100

100

-

125

1

1-1/4" (32 mm)

LI6243CFF

24

240

3

57.8

57.8

57.8

90

3

1-1/4" (32 mm)

LI6243CFM

24

480

3

29.9

29.9

29.9

40

8

1/2" (13 mm)

LI6303CFC

30

208

1

144

144

-

200

3/0

1-1/2" (38 mm)

LI6303CFD

30

208

3

83.3

83.3

83.3

125

1

1-1/4" (32 mm)

LI6303CFE

30

240

1

125

125

-

175

2/0

1-1/2" (38 mm)

LI6303CFF

30

240

3

72.3

72.3

72.3

100

3

1" (25 mm)

LI6303CFM

30

480

3

36

36

36

50

8

1/2" (13 mm)

SPECIFICATIONS

Form No. EBOOSTERBWM-1009

4

Circuit Breaker and Fused Disconnect Switch Sizes — 6 to 30 kW

Wire size is based on THHN wire for branch circuit protection at .91 derate factor. Circuit breakers and fused disconnects are to

be mounted remote and wired by contractor. Sizes are based on the 2002 NEC table 310-16. Conduit size based on conductors

plus ground wire sizing per Table C1 from Appendix C.
Only 6 and 9 kW models can be field converted to single- or three-phase (open delta on 3-phase). Check wiring diagram supplied

with the unit when converting the phase of a unit. Larger branch circuit required than for balanced 3-phase of equal kW. Balanced

3-phase available, consult factory.

NOTE: 250 kcmil maximum wire size for terminal block.

WARNING! Consult a licensed electrical contractor for proper electrical installation conforming to local electrical codes
and the National Electrical Code (N.E.C.).

Содержание LI6123CFC

Страница 1: ...sted no puede entender el contenido de este manual por favor pregunte a su supervisor Almacenar este manual en una localizaci n segura para la referencia futura Do not operate this equipment unless yo...

Страница 2: ...could result in death or serious injury CAUTION indicates a hazardous situation which if not avoided could result in minor or moderate injury NOTICE is used to address practices not related to person...

Страница 3: ...N TEMPERATURE PRESSURE RELIEF VALVES IN ACCORDANCE WITH AMERICAN NATIONAL STD Z21 22 1979 Combination temperature pressure relief valves with extension thermostats must be installed so that the temper...

Страница 4: ...WARNING CAUTION Do not store any materials or items on or against the housing of the booster water heater Bradford White requires that two temperature pressure gauges be installed to assure proper ope...

Страница 5: ...ure gauges and a high temperature limit safety switch Magnum Series models feature a Castone tank with a 5 year limited warranty an ON OFF switch an indicator light and either 6 152 mm legs or slide m...

Страница 6: ...0 1 0 1 1 4 32 mm LI6243CFD 24 208 3 66 7 66 7 66 7 90 3 1 25 mm LI6243CFE 24 240 1 100 100 125 1 1 1 4 32 mm LI6243CFF 24 240 3 57 8 57 8 57 8 90 3 1 1 4 32 mm LI6243CFM 24 480 3 29 9 29 9 29 9 40 8...

Страница 7: ...0 kcmil 2 51 mm LI6453CFF 45 240 3 108 108 108 150 1 0 1 1 4 32 mm LI6453CFM 45 480 3 54 54 54 70 4 1 25 mm LI6543CFD 54 208 3 150 150 150 200 3 0 2 51 mm LI6543CFF 54 240 3 130 130 130 175 2 0 1 1 2...

Страница 8: ...nder dish table DO NOT mount on walls or in ceiling Unit must be accessible for service Improper installation could create an unsafe condition Booster Heaters are shipped with most components pre asse...

Страница 9: ...uges are supplied with all booster water heaters One temperature pressure relief valve supplied with all booster heaters Pressure Reducing Valve Shock Absorber Blended Phosphate Water Treatment System...

Страница 10: ...terways are clear This device is designated for emergency safety relief and shall not be used as an operating control The valves are set to relieve at 150 psi 1034 kPa or when water temperature reache...

Страница 11: ...nd reduce the operating life of the unit through increased lime build up Product failure caused by liming or sediment buildup is not covered under warranty Do not use deionized or reverse osmosis R O...

Страница 12: ...er Drain Valve 3 4 Union Floor Drain Outlet Inlet Discharge from T P relief valve Air gap must comply with plumbing code Blended Phosphate Water Treatment System Optional accessory Not supplied with b...

Страница 13: ...O A MINIMUM OF 40 INCH POUNDS NOTE Due to the rigors of transportation all connections should be checked for tightness before booster water heater is put into operation 4 A grounding lug is provided n...

Страница 14: ...unit will get hot Avoid unnecessary contact with unit 6 Turn on the electrical supply to the booster heater 7 Move the Power ON OFF switch to the ON position The indicator light will turn on Figure 1...

Страница 15: ...clockwise to raise the set point NOTE 1 6 turn of the inner screw equals 8 F 4 4 C Temperature Pressure Relief Valve The temperature pressure relief valve lever must be operated at least once a year t...

Страница 16: ...alled properly 8 A check valve should not be installed ahead of the booster NOTE If a check valve is installed and cannot be removed install a back pressure relief valve set at 125 psi 862 kPa on the...

Страница 17: ...be reset contact an Authorized Service Agent Low water cutoff inoperable contacts do not close Contact Authorized Service Agent or Bradford White for assistance Transformer not working properly Contac...

Страница 18: ...ew valve with built in bypass Check valve or anti siphon valve installed in the feed line Remove check valve or anti siphon valve to allow for water expansion or install a back pressure relief valve o...

Страница 19: ...e floor Shock Absorber The shock absorber installed between the booster and the commercial dish machine reduces water hammer induced by rapidly operating valves The water hammer can cause damage to th...

Страница 20: ...WIRING DIAGRAMS Form No EBOOSTERBWM 1009 18 10 01 454 6 9 kW Wiring Diagram All Voltages Single or Three Phase 10 01 448 12 18 kW Wiring Diagram All Voltages Three Phase...

Страница 21: ...WIRING DIAGRAMS Form No EBOOSTERBWM 1009 19 10 01 452 12 15 kW Wiring Diagram 208 and 240 V Single Phase 10 01 447 18 kW Wiring Diagram 208 and 240 V Single Phase...

Страница 22: ...WIRING DIAGRAMS Form No EBOOSTERBWM 1009 20 10 01 432 24 30 kW Wiring Diagram 240 V Single Phase 10 01 433 24 36 kW Wiring Diagram 208 and 240 V Three Phase...

Страница 23: ...WIRING DIAGRAMS Form No EBOOSTERBWM 1009 21 10 01 435 24 36 kW Wiring Diagram 480 V Three Phase 10 01 436 36 kW Wiring Diagram 240 V Single Phase...

Страница 24: ...WIRING DIAGRAMS Form No EBOOSTERBWM 1009 22 10 01 434 45 57 kW Wiring Diagram 480 V Three Phase 10 01 437 36 57 kW Wiring Diagram 208 and 240 V Three Phase...

Страница 25: ...ank only WHAT IS THE DURATION OF THE IMPLIED WARRANTY ANY IMPLIED WARRANTIES INCLUDING THE WARRANTY OF MERCHANTABILITY IMPOSED ON THE SALE OF THE WATER HEATER UNDER THE LAWS OF THE STATE OF SALE ARE L...

Страница 26: ...ecessary allow us or our chosen representative to inspect the unit 5 For your reference fill in the Model and Serial Number found on the units Rating Plate Model Number _______________________________...

Страница 27: ...NOTES Form No EBOOSTERBWM 1009 25...

Страница 28: ...rinted in U S A October 2009 Part No 07 04 474 00 Form No EBOOSTERBWM 1009 Ambler PA 19002 Technical Service 800 334 3393 Service Parts 800 538 2020 Warranty Service 800 531 2111 www bradfordwhite com...

Отзывы: