TROUBLESHOOTING GUIDE

Form No. EBOOSTERBWM-1009

15

Symptom

Probable Cause

Corrective Action

Water reaches 180°F (82°C) but

does not last through the entire

dishwasher operation.

Low incoming water temperature.

Incoming water temperature must be adequate

for booster size. Increase incoming water

temperature.

Incoming water temperature drops.

Primary water supply is not adequate to provide

correct temperature in sufficient quantities.

Increase supply of primary hot water.

Temperature

setting

out

of

calibration or inoperable.

Temperature setting should be maximum

of 190°F (88°C).

Incorrect voltage.

Check voltage on heater serial plate and make

sure supplied voltage matches. A 240 V booster

water heater operating on 208 V reduces wattage

to 76% of the normal output.

High limit switch may be tripped or

defective.

Reset switch. If switch continues to trip or cannot

be reset contact an Authorized Service Agent.

Low water cutoff inoperable,

contacts do not close.

Contact Authorized Service Agent or Bradford

White for assistance.

Transformer not working properly.

Contact Authorized Service Agent or Bradford

White for assistance.

Contactors do not pull in.

Contact Authorized Service Agent or Bradford

White for assistance.

Fuses may be blown or circuit

breaker tripped.

Check for proper fuse sizing. Replace fuses.

Check/reset circuit breaker.

Over-current fuses may be blown.

Contact Authorized Service Agent or Bradford

White for assistance.

The booster heater does not heat

at all or only delivers water at

120°–150°F (49°–66°C).

Flow pressure is too high.

Higher pressure uses an excessive quantity of hot

water. Adjust flow pressure to 20 psi (138 kPa).

Booster water heater may be

undersized.

Booster water heater must be sized properly for

incoming water temperature and rinse

requirements of the dish machine.

Unit may have been energized

without water (dry fired).

This will cause the elements to burn out quickly.

Replace the element(s).

Содержание LI6123CFC

Страница 1: ...sted no puede entender el contenido de este manual por favor pregunte a su supervisor Almacenar este manual en una localizaci n segura para la referencia futura Do not operate this equipment unless yo...

Страница 2: ...could result in death or serious injury CAUTION indicates a hazardous situation which if not avoided could result in minor or moderate injury NOTICE is used to address practices not related to person...

Страница 3: ...N TEMPERATURE PRESSURE RELIEF VALVES IN ACCORDANCE WITH AMERICAN NATIONAL STD Z21 22 1979 Combination temperature pressure relief valves with extension thermostats must be installed so that the temper...

Страница 4: ...WARNING CAUTION Do not store any materials or items on or against the housing of the booster water heater Bradford White requires that two temperature pressure gauges be installed to assure proper ope...

Страница 5: ...ure gauges and a high temperature limit safety switch Magnum Series models feature a Castone tank with a 5 year limited warranty an ON OFF switch an indicator light and either 6 152 mm legs or slide m...

Страница 6: ...0 1 0 1 1 4 32 mm LI6243CFD 24 208 3 66 7 66 7 66 7 90 3 1 25 mm LI6243CFE 24 240 1 100 100 125 1 1 1 4 32 mm LI6243CFF 24 240 3 57 8 57 8 57 8 90 3 1 1 4 32 mm LI6243CFM 24 480 3 29 9 29 9 29 9 40 8...

Страница 7: ...0 kcmil 2 51 mm LI6453CFF 45 240 3 108 108 108 150 1 0 1 1 4 32 mm LI6453CFM 45 480 3 54 54 54 70 4 1 25 mm LI6543CFD 54 208 3 150 150 150 200 3 0 2 51 mm LI6543CFF 54 240 3 130 130 130 175 2 0 1 1 2...

Страница 8: ...nder dish table DO NOT mount on walls or in ceiling Unit must be accessible for service Improper installation could create an unsafe condition Booster Heaters are shipped with most components pre asse...

Страница 9: ...uges are supplied with all booster water heaters One temperature pressure relief valve supplied with all booster heaters Pressure Reducing Valve Shock Absorber Blended Phosphate Water Treatment System...

Страница 10: ...terways are clear This device is designated for emergency safety relief and shall not be used as an operating control The valves are set to relieve at 150 psi 1034 kPa or when water temperature reache...

Страница 11: ...nd reduce the operating life of the unit through increased lime build up Product failure caused by liming or sediment buildup is not covered under warranty Do not use deionized or reverse osmosis R O...

Страница 12: ...er Drain Valve 3 4 Union Floor Drain Outlet Inlet Discharge from T P relief valve Air gap must comply with plumbing code Blended Phosphate Water Treatment System Optional accessory Not supplied with b...

Страница 13: ...O A MINIMUM OF 40 INCH POUNDS NOTE Due to the rigors of transportation all connections should be checked for tightness before booster water heater is put into operation 4 A grounding lug is provided n...

Страница 14: ...unit will get hot Avoid unnecessary contact with unit 6 Turn on the electrical supply to the booster heater 7 Move the Power ON OFF switch to the ON position The indicator light will turn on Figure 1...

Страница 15: ...clockwise to raise the set point NOTE 1 6 turn of the inner screw equals 8 F 4 4 C Temperature Pressure Relief Valve The temperature pressure relief valve lever must be operated at least once a year t...

Страница 16: ...alled properly 8 A check valve should not be installed ahead of the booster NOTE If a check valve is installed and cannot be removed install a back pressure relief valve set at 125 psi 862 kPa on the...

Страница 17: ...be reset contact an Authorized Service Agent Low water cutoff inoperable contacts do not close Contact Authorized Service Agent or Bradford White for assistance Transformer not working properly Contac...

Страница 18: ...ew valve with built in bypass Check valve or anti siphon valve installed in the feed line Remove check valve or anti siphon valve to allow for water expansion or install a back pressure relief valve o...

Страница 19: ...e floor Shock Absorber The shock absorber installed between the booster and the commercial dish machine reduces water hammer induced by rapidly operating valves The water hammer can cause damage to th...

Страница 20: ...WIRING DIAGRAMS Form No EBOOSTERBWM 1009 18 10 01 454 6 9 kW Wiring Diagram All Voltages Single or Three Phase 10 01 448 12 18 kW Wiring Diagram All Voltages Three Phase...

Страница 21: ...WIRING DIAGRAMS Form No EBOOSTERBWM 1009 19 10 01 452 12 15 kW Wiring Diagram 208 and 240 V Single Phase 10 01 447 18 kW Wiring Diagram 208 and 240 V Single Phase...

Страница 22: ...WIRING DIAGRAMS Form No EBOOSTERBWM 1009 20 10 01 432 24 30 kW Wiring Diagram 240 V Single Phase 10 01 433 24 36 kW Wiring Diagram 208 and 240 V Three Phase...

Страница 23: ...WIRING DIAGRAMS Form No EBOOSTERBWM 1009 21 10 01 435 24 36 kW Wiring Diagram 480 V Three Phase 10 01 436 36 kW Wiring Diagram 240 V Single Phase...

Страница 24: ...WIRING DIAGRAMS Form No EBOOSTERBWM 1009 22 10 01 434 45 57 kW Wiring Diagram 480 V Three Phase 10 01 437 36 57 kW Wiring Diagram 208 and 240 V Three Phase...

Страница 25: ...ank only WHAT IS THE DURATION OF THE IMPLIED WARRANTY ANY IMPLIED WARRANTIES INCLUDING THE WARRANTY OF MERCHANTABILITY IMPOSED ON THE SALE OF THE WATER HEATER UNDER THE LAWS OF THE STATE OF SALE ARE L...

Страница 26: ...ecessary allow us or our chosen representative to inspect the unit 5 For your reference fill in the Model and Serial Number found on the units Rating Plate Model Number _______________________________...

Страница 27: ...NOTES Form No EBOOSTERBWM 1009 25...

Страница 28: ...rinted in U S A October 2009 Part No 07 04 474 00 Form No EBOOSTERBWM 1009 Ambler PA 19002 Technical Service 800 334 3393 Service Parts 800 538 2020 Warranty Service 800 531 2111 www bradfordwhite com...

Отзывы: