INSTALLATION

Form No. EBOOSTERBWM-1009

9

Plumbing Connections

Use the following procedures to connect the inlet and outlet

water lines as well as inspect the system once the plumbing

connections are complete.

Do not connect an expansion tank of any type to booster
water heater lines.

Use only plumbing material suitable for a minimum water
temperature of 200°F (93°C). Materials used must meet
National Sanitation Foundation (NSF) specifications and
all local plumbing codes and regulations.

Do not connect booster water heater directly to a boiler or
furnace coil or any other uncontrolled temperature
source. The booster heater thermostat could be damaged
causing unit to overheat.

Do not connect booster water heater to domestic
(consumer) dish machines or other domestic utilized
equipment. Hot water from booster heater may damage
domestic equipment resulting in a hazardous condition.

Use dielectric couplings when connecting dissimilar
metals, such as galvanized to copper. This will prevent
electrolysis or premature plumbing damage.

DO NOT turn or adjust inlet water connection on Magnum
Series booster water heaters. Doing so will change the
internal water flow.

Do not back out or loosen any pipe fittings. Doing so may
cause leaks.

Do not lay unit on the side with the control panel. Damage
to the unit could occur.

Incoming water in excess of 3 grains of hardness per
gallon (GPG) (0.75 grains of hardness per liter [GPL]) must
be treated and softened before being supplied to booster
heater(s). Water containing over 3 GPG (0.75 GPL) will
decrease efficiency, increase energy use, and reduce the
operating life of the unit through increased lime build-up.
Product failure caused by liming or sediment buildup is
not covered under warranty.

Do not use deionized or reverse osmosis (R.O.) treated
water in booster water heaters. Damage to booster heater
may occur.

NOTE: Product failure caused by liming or sediment buildup is

not covered under warranty.

NOTICE

CAUTION

WARNING

Inlet

(Refer to Figure 5, 6, or 7)

1. Connect the booster water heater inlet to a hot water

supply line from the regular water heater. Water

temperature from the regular water heater should be 110°

or 140°F (43° or 60°C) and

should not exceed 160°F

(71°C).

Minimum temperature differential between inlet and

outlet should never be less than 20°F (11°C).

NOTE: The red mark on the inlet and outlet water pipes of

Magnum Series units must remain in the top most

position.

2. Provide the inlet line with a shut-off valve, (a full opening

gate or ball type), one temperature/pressure gauge, and

the pressure reducing valve. Set pressure reducing valve

at 20 psi (138 kPa) flow pressure.

NOTE: A 3/4" union and a drain valve are required

for easy servicing.

NOTE: Be sure water flows through the pressure reducing

valve in the proper direction. Check directional arrow.

Valve will reduce pressure only during flow conditions.

NOTE: An optional back pressure relief valve is available for

installation on the water inlet line when local plumbing

codes require a check valve.

3. Install a temperature/pressure gauge in both the inlet and

outlet lines. Install the temperature sensing bulb in the

water stream. The gauge must be mounted upright (see

Figures 8 and 9).

NOTE: Tighten gauge during installation by only turning the

1/2" brass nut. DO NOT turn the face of the gauge.

Turning the face will cause inaccurate measurements.

Содержание LI6123CFC

Страница 1: ...sted no puede entender el contenido de este manual por favor pregunte a su supervisor Almacenar este manual en una localizaci n segura para la referencia futura Do not operate this equipment unless yo...

Страница 2: ...could result in death or serious injury CAUTION indicates a hazardous situation which if not avoided could result in minor or moderate injury NOTICE is used to address practices not related to person...

Страница 3: ...N TEMPERATURE PRESSURE RELIEF VALVES IN ACCORDANCE WITH AMERICAN NATIONAL STD Z21 22 1979 Combination temperature pressure relief valves with extension thermostats must be installed so that the temper...

Страница 4: ...WARNING CAUTION Do not store any materials or items on or against the housing of the booster water heater Bradford White requires that two temperature pressure gauges be installed to assure proper ope...

Страница 5: ...ure gauges and a high temperature limit safety switch Magnum Series models feature a Castone tank with a 5 year limited warranty an ON OFF switch an indicator light and either 6 152 mm legs or slide m...

Страница 6: ...0 1 0 1 1 4 32 mm LI6243CFD 24 208 3 66 7 66 7 66 7 90 3 1 25 mm LI6243CFE 24 240 1 100 100 125 1 1 1 4 32 mm LI6243CFF 24 240 3 57 8 57 8 57 8 90 3 1 1 4 32 mm LI6243CFM 24 480 3 29 9 29 9 29 9 40 8...

Страница 7: ...0 kcmil 2 51 mm LI6453CFF 45 240 3 108 108 108 150 1 0 1 1 4 32 mm LI6453CFM 45 480 3 54 54 54 70 4 1 25 mm LI6543CFD 54 208 3 150 150 150 200 3 0 2 51 mm LI6543CFF 54 240 3 130 130 130 175 2 0 1 1 2...

Страница 8: ...nder dish table DO NOT mount on walls or in ceiling Unit must be accessible for service Improper installation could create an unsafe condition Booster Heaters are shipped with most components pre asse...

Страница 9: ...uges are supplied with all booster water heaters One temperature pressure relief valve supplied with all booster heaters Pressure Reducing Valve Shock Absorber Blended Phosphate Water Treatment System...

Страница 10: ...terways are clear This device is designated for emergency safety relief and shall not be used as an operating control The valves are set to relieve at 150 psi 1034 kPa or when water temperature reache...

Страница 11: ...nd reduce the operating life of the unit through increased lime build up Product failure caused by liming or sediment buildup is not covered under warranty Do not use deionized or reverse osmosis R O...

Страница 12: ...er Drain Valve 3 4 Union Floor Drain Outlet Inlet Discharge from T P relief valve Air gap must comply with plumbing code Blended Phosphate Water Treatment System Optional accessory Not supplied with b...

Страница 13: ...O A MINIMUM OF 40 INCH POUNDS NOTE Due to the rigors of transportation all connections should be checked for tightness before booster water heater is put into operation 4 A grounding lug is provided n...

Страница 14: ...unit will get hot Avoid unnecessary contact with unit 6 Turn on the electrical supply to the booster heater 7 Move the Power ON OFF switch to the ON position The indicator light will turn on Figure 1...

Страница 15: ...clockwise to raise the set point NOTE 1 6 turn of the inner screw equals 8 F 4 4 C Temperature Pressure Relief Valve The temperature pressure relief valve lever must be operated at least once a year t...

Страница 16: ...alled properly 8 A check valve should not be installed ahead of the booster NOTE If a check valve is installed and cannot be removed install a back pressure relief valve set at 125 psi 862 kPa on the...

Страница 17: ...be reset contact an Authorized Service Agent Low water cutoff inoperable contacts do not close Contact Authorized Service Agent or Bradford White for assistance Transformer not working properly Contac...

Страница 18: ...ew valve with built in bypass Check valve or anti siphon valve installed in the feed line Remove check valve or anti siphon valve to allow for water expansion or install a back pressure relief valve o...

Страница 19: ...e floor Shock Absorber The shock absorber installed between the booster and the commercial dish machine reduces water hammer induced by rapidly operating valves The water hammer can cause damage to th...

Страница 20: ...WIRING DIAGRAMS Form No EBOOSTERBWM 1009 18 10 01 454 6 9 kW Wiring Diagram All Voltages Single or Three Phase 10 01 448 12 18 kW Wiring Diagram All Voltages Three Phase...

Страница 21: ...WIRING DIAGRAMS Form No EBOOSTERBWM 1009 19 10 01 452 12 15 kW Wiring Diagram 208 and 240 V Single Phase 10 01 447 18 kW Wiring Diagram 208 and 240 V Single Phase...

Страница 22: ...WIRING DIAGRAMS Form No EBOOSTERBWM 1009 20 10 01 432 24 30 kW Wiring Diagram 240 V Single Phase 10 01 433 24 36 kW Wiring Diagram 208 and 240 V Three Phase...

Страница 23: ...WIRING DIAGRAMS Form No EBOOSTERBWM 1009 21 10 01 435 24 36 kW Wiring Diagram 480 V Three Phase 10 01 436 36 kW Wiring Diagram 240 V Single Phase...

Страница 24: ...WIRING DIAGRAMS Form No EBOOSTERBWM 1009 22 10 01 434 45 57 kW Wiring Diagram 480 V Three Phase 10 01 437 36 57 kW Wiring Diagram 208 and 240 V Three Phase...

Страница 25: ...ank only WHAT IS THE DURATION OF THE IMPLIED WARRANTY ANY IMPLIED WARRANTIES INCLUDING THE WARRANTY OF MERCHANTABILITY IMPOSED ON THE SALE OF THE WATER HEATER UNDER THE LAWS OF THE STATE OF SALE ARE L...

Страница 26: ...ecessary allow us or our chosen representative to inspect the unit 5 For your reference fill in the Model and Serial Number found on the units Rating Plate Model Number _______________________________...

Страница 27: ...NOTES Form No EBOOSTERBWM 1009 25...

Страница 28: ...rinted in U S A October 2009 Part No 07 04 474 00 Form No EBOOSTERBWM 1009 Ambler PA 19002 Technical Service 800 334 3393 Service Parts 800 538 2020 Warranty Service 800 531 2111 www bradfordwhite com...

Отзывы: