INSTALLATION

Form No. EBOOSTERBWM-1009

8

Temperature/Pressure Relief Valves

For protection against excessive pressures and temperatures in

the booster heater, install temperature/pressure protective

equipment required by local codes. The temperature/pressure

relief valve supplied with this booster water heater is

constructed with brass working parts and heat resistant silicone

seat discs.

Temperature/pressure protective equipment should not be
less than a combination temperature/pressure relief valve
certified by a nationally recognized testing laboratory that
maintains periodic inspection of the production of this
equipment and meets the requirements for Relief Valves
and Automatic Shutoff Devices for Hot Water Supply
Systems, ANSI Z21.22-1979. The temperature/pressure
relief valve must be marked with a minimum set pressure
not to exceed the marked hydrostatic test pressure of the
booster heater as noted on the unit specifications.

FOR

INSTALLING

COMBINATION

TEMPERATURE/

PRESSURE RELIEF VALVES IN ACCORDANCE WITH
AMERICAN NATIONAL STD. Z21.22-1979. Combination
temperature/pressure

relief

valves

with

extension

thermostats must be installed so that the temperature-
sensing element is immersed in the water within the top 6"
(152 mm) of the tank. They must be installed either in the
hot outlet service line or directly in a tank tapping.
Combination temperature/pressure relief valves that do
not have extension elements must be mounted directly in
a tank tapping located within the top 6" (152 mm) of the
tank, and shall be adequately insulated and located so as
to assure isolation from the flue gas heat or other ambient
conditions that are not indicative of stored water
temperature. TO AVOID WATER DAMAGE OR SCALDING
DUE TO VALVE OPERATION, DRAIN PIPE MUST BE
CONNECTED TO VALVE OUTLET AND RUN TO A SAFE
PLACE OF DISPOSAL. Discharge line must be as short as
possible and be the same size as the valve discharge
connection throughout its entire length. Drain line must
pitch downward from the valve and must terminate
between 1-1/2" (38 mm) and 6" (152 mm) above the floor
drain where any discharge will be clearly visible. The drain
line shall terminate plain, not threaded, with material
serviceable for temperatures up to 250°F (121°C) or
greater. Excessive length, over 30' (9144 mm), or use of
more than four elbows can cause a restriction and reduce
the discharge capacity of the valve. No shut-off valve shall
be installed between the relief valve and tank, or in the
drain line. Valve lever must be tripped periodically to
assure that waterways are clear. This device is designated
for emergency safety relief and shall not be used as an
operating control. The valves are set to relieve at 150 psi
(1034 kPa) or when water temperature reaches 210°F
(99°C). Read tag on valve for additional information.

BURN HAZARD: Valves supplied with this booster water
heater are designed for high temperature commercial
operation. Do not substitute these valves with valves
designed for domestic water heaters.

Do not use an anti-siphon or check valves on incoming
water line.

CAUTION

WARNING

Pressure Reducing Valve

If water supply pressure to the booster water heater inlet
is over 20 psi (138 kPa) during flow, install a commercial-
grade pressure reducing valve with built-in bypass for
proper operation of dish machine rinse nozzles.

NOTE: The pressure reducing valve must be the type

equipped with a high pressure bypass like the valve

supplied with this booster water heater.

Proper operation of the commercial dish machine rinse nozzles

requires that available water pressure at the rinse nozzle be

between 15 and 25 psi (103 and 172 kPa) when the nozzle is

operated. 20 psi (138 kPa) is recommended. If water pressure

available to the booster water heater inlet is over 20 psi

(138 kPa), a pressure reducing valve must be installed in the hot

water supply line to the booster water heater and adjusted to

deliver 20 psi (138 kPa) flow pressure.
The valve supplied with the unit has a built-in high pressure

bypass that prevents excessive pressure build-up as the

booster heats up. Final adjustment is required at the time of

installation.

Temperature/Pressure Gauges

Bradford White requires that two temperature/pressure
gauges be installed to assure proper operation. Install one
in the supply line before the pressure reducing valve and
one in the outlet line as close to the booster water heater
as possible. This provides a visual check of the water
temperature and pressure before and after the water
heater.

NOTE: If a check valve is installed and cannot be removed

install a back pressure relief valve set at 125 psi (862

kPa) on the incoming line between the pressure

reducing valve and the inlet to the booster water

heater. Discharge must be to open site drain (see

Figure 7).

Blended Phosphate Water Treatment
System (optional)

Bradford White recommends that the Blended Phosphate Water

Treatment System be installed with unions on the incoming 3/4"

water supply line after the pressure reducing valve and before

the booster water heater.
Cartridges supplied have a usage rating of 100,000 gallons

(378,541 liters) of water. To assure proper operation the

cartridges must be replaced when expired.

NOTE: Product failure caused by liming or sediment buildup is

not covered under warranty.

CAUTION

CAUTION

Содержание LI6123CFC

Страница 1: ...sted no puede entender el contenido de este manual por favor pregunte a su supervisor Almacenar este manual en una localizaci n segura para la referencia futura Do not operate this equipment unless yo...

Страница 2: ...could result in death or serious injury CAUTION indicates a hazardous situation which if not avoided could result in minor or moderate injury NOTICE is used to address practices not related to person...

Страница 3: ...N TEMPERATURE PRESSURE RELIEF VALVES IN ACCORDANCE WITH AMERICAN NATIONAL STD Z21 22 1979 Combination temperature pressure relief valves with extension thermostats must be installed so that the temper...

Страница 4: ...WARNING CAUTION Do not store any materials or items on or against the housing of the booster water heater Bradford White requires that two temperature pressure gauges be installed to assure proper ope...

Страница 5: ...ure gauges and a high temperature limit safety switch Magnum Series models feature a Castone tank with a 5 year limited warranty an ON OFF switch an indicator light and either 6 152 mm legs or slide m...

Страница 6: ...0 1 0 1 1 4 32 mm LI6243CFD 24 208 3 66 7 66 7 66 7 90 3 1 25 mm LI6243CFE 24 240 1 100 100 125 1 1 1 4 32 mm LI6243CFF 24 240 3 57 8 57 8 57 8 90 3 1 1 4 32 mm LI6243CFM 24 480 3 29 9 29 9 29 9 40 8...

Страница 7: ...0 kcmil 2 51 mm LI6453CFF 45 240 3 108 108 108 150 1 0 1 1 4 32 mm LI6453CFM 45 480 3 54 54 54 70 4 1 25 mm LI6543CFD 54 208 3 150 150 150 200 3 0 2 51 mm LI6543CFF 54 240 3 130 130 130 175 2 0 1 1 2...

Страница 8: ...nder dish table DO NOT mount on walls or in ceiling Unit must be accessible for service Improper installation could create an unsafe condition Booster Heaters are shipped with most components pre asse...

Страница 9: ...uges are supplied with all booster water heaters One temperature pressure relief valve supplied with all booster heaters Pressure Reducing Valve Shock Absorber Blended Phosphate Water Treatment System...

Страница 10: ...terways are clear This device is designated for emergency safety relief and shall not be used as an operating control The valves are set to relieve at 150 psi 1034 kPa or when water temperature reache...

Страница 11: ...nd reduce the operating life of the unit through increased lime build up Product failure caused by liming or sediment buildup is not covered under warranty Do not use deionized or reverse osmosis R O...

Страница 12: ...er Drain Valve 3 4 Union Floor Drain Outlet Inlet Discharge from T P relief valve Air gap must comply with plumbing code Blended Phosphate Water Treatment System Optional accessory Not supplied with b...

Страница 13: ...O A MINIMUM OF 40 INCH POUNDS NOTE Due to the rigors of transportation all connections should be checked for tightness before booster water heater is put into operation 4 A grounding lug is provided n...

Страница 14: ...unit will get hot Avoid unnecessary contact with unit 6 Turn on the electrical supply to the booster heater 7 Move the Power ON OFF switch to the ON position The indicator light will turn on Figure 1...

Страница 15: ...clockwise to raise the set point NOTE 1 6 turn of the inner screw equals 8 F 4 4 C Temperature Pressure Relief Valve The temperature pressure relief valve lever must be operated at least once a year t...

Страница 16: ...alled properly 8 A check valve should not be installed ahead of the booster NOTE If a check valve is installed and cannot be removed install a back pressure relief valve set at 125 psi 862 kPa on the...

Страница 17: ...be reset contact an Authorized Service Agent Low water cutoff inoperable contacts do not close Contact Authorized Service Agent or Bradford White for assistance Transformer not working properly Contac...

Страница 18: ...ew valve with built in bypass Check valve or anti siphon valve installed in the feed line Remove check valve or anti siphon valve to allow for water expansion or install a back pressure relief valve o...

Страница 19: ...e floor Shock Absorber The shock absorber installed between the booster and the commercial dish machine reduces water hammer induced by rapidly operating valves The water hammer can cause damage to th...

Страница 20: ...WIRING DIAGRAMS Form No EBOOSTERBWM 1009 18 10 01 454 6 9 kW Wiring Diagram All Voltages Single or Three Phase 10 01 448 12 18 kW Wiring Diagram All Voltages Three Phase...

Страница 21: ...WIRING DIAGRAMS Form No EBOOSTERBWM 1009 19 10 01 452 12 15 kW Wiring Diagram 208 and 240 V Single Phase 10 01 447 18 kW Wiring Diagram 208 and 240 V Single Phase...

Страница 22: ...WIRING DIAGRAMS Form No EBOOSTERBWM 1009 20 10 01 432 24 30 kW Wiring Diagram 240 V Single Phase 10 01 433 24 36 kW Wiring Diagram 208 and 240 V Three Phase...

Страница 23: ...WIRING DIAGRAMS Form No EBOOSTERBWM 1009 21 10 01 435 24 36 kW Wiring Diagram 480 V Three Phase 10 01 436 36 kW Wiring Diagram 240 V Single Phase...

Страница 24: ...WIRING DIAGRAMS Form No EBOOSTERBWM 1009 22 10 01 434 45 57 kW Wiring Diagram 480 V Three Phase 10 01 437 36 57 kW Wiring Diagram 208 and 240 V Three Phase...

Страница 25: ...ank only WHAT IS THE DURATION OF THE IMPLIED WARRANTY ANY IMPLIED WARRANTIES INCLUDING THE WARRANTY OF MERCHANTABILITY IMPOSED ON THE SALE OF THE WATER HEATER UNDER THE LAWS OF THE STATE OF SALE ARE L...

Страница 26: ...ecessary allow us or our chosen representative to inspect the unit 5 For your reference fill in the Model and Serial Number found on the units Rating Plate Model Number _______________________________...

Страница 27: ...NOTES Form No EBOOSTERBWM 1009 25...

Страница 28: ...rinted in U S A October 2009 Part No 07 04 474 00 Form No EBOOSTERBWM 1009 Ambler PA 19002 Technical Service 800 334 3393 Service Parts 800 538 2020 Warranty Service 800 531 2111 www bradfordwhite com...

Отзывы: