INSTALLATION

Form No. EBOOSTERBWM-1009

11

DO NOT turn on power to the booster water heater until
tank has been filled with water and all air has been vented
through dish machine rinse nozzle. The heating elements
will burn out in seconds if operated when they are not
immersed in water.

Electrical — All Sizes and Voltages

General

Bradford White Electric Booster Water Heaters are available for

operation on standard power systems. Check the identification

decal for the proper power supply.

ELECTRIC SHOCK HAZARD:

• Turn power OFF at disconnect switch/circuit breaker

and allow unit to cool before performing any
maintenance or cleaning.

• Consult a licensed electrical contractor for proper

electrical installation conforming to local electrical
codes and the National Electrical Code (N.E.C.).

Connect electric booster water heater to the same power
supply as indicated on the specification decal only. Units
connected to an incorrect power supply voids the product
warranty and will damage the equipment.

All internal electrical connections have been made at the

factory. See the “Circuit Breaker and Fused Disconnect Switch

Sizes” charts in the SPECIFICATIONS section for supply wire

size, fuse, breaker, and conduit recommendations. Consult local

codes for verification and compliance.

Electrical Connections

1. Remove the front jacket cover screws. Ease the cover

forward and upward. The control box is under the front

hinged jacket cover.

2. Locate the heater terminal or fuse block(s) inside the unit.

NOTE: See the

“Circuit Breaker and Fused Disconnect Switch

Sizes”

charts for proper connections and wire size.

3. Bring power leads from a

properly sized disconnect

switch or circuit breaker

through the knockout provided

on the unit, and connect to the

terminal or fuse block(s).

USE

COPPER

WIRE

ONLY.

TIGHTEN

CONNECTIONS

PROPERLY TO A MINIMUM
OF 40 INCH POUNDS.

NOTE: Due

to

the

rigors

of

transportation

all

connections should be

checked for tightness before booster water heater is

put into operation.

4. A grounding lug is provided near the supply terminals. An

equipment grounding conductor must be properly

connected to it.

5. Replace and secure the front jacket cover.

Knockout

Locations

NOTICE

WARNING

CAUTION

Outlet

1. Using a 3/4″ union and piping, connect the booster water

heater outlet to the commercial dish machine sanitizing

rinse pipe connection.

NOTE: The red mark on the inlet and outlet water pipes of

Magnum Series units must remain in the top most

position.

NOTE: Make sure the connection is made to the final rinse

and not to the wash tank.

2. Install a temperature/pressure gauge in the outlet line. The

temperature sensing element must be in the water stream

and the gauge must be mounted upright. Water

temperature at the outlet should be 185°–190°F

(85°–88°C).

Figure 8. Recommended Temperature/Pressure Gauge Installation

Figure 9. Alternate Temperature/Pressure Gauge Installation

NOTE: Bradford White recommends installing an optional

shock absorber in the outlet line as close as possible

to the commercial dish machine solenoid rinse valve.

The shock absorber softens the water hammer caused

by automatic dish machine valves.

Plumbing Installation Inspection

1. Close drain pipe shut-off valve and fill booster water heater

with water.

2. Check all pipe connections for leaks.
3. Make sure the temperature/pressurerelief valve discharge

is not blocked.

4. Vent air from the booster tank before turning on the unit by

opening the temperature/pressure relief valve as well as

running the dish machine through several cycles.

Temperature/

Pressure Gauge

w/1/2″ pipe thread

1/2″ Copper

Female Fitting

Adapter

Temperature

Sensing

Element

Bottom of sensor

centered in

copper pipe.

3/4″ Nominal

Copper Pipe

3/4″ Copper Tee

Temperature/Pressure

Gauge

3/4″ Nominal

Copper Pipe

1/2″ pipe thread

1/2″ Copper Female

Fitting Adapter

Temperature

Sensing

Element

Содержание LI6123CFC

Страница 1: ...sted no puede entender el contenido de este manual por favor pregunte a su supervisor Almacenar este manual en una localizaci n segura para la referencia futura Do not operate this equipment unless yo...

Страница 2: ...could result in death or serious injury CAUTION indicates a hazardous situation which if not avoided could result in minor or moderate injury NOTICE is used to address practices not related to person...

Страница 3: ...N TEMPERATURE PRESSURE RELIEF VALVES IN ACCORDANCE WITH AMERICAN NATIONAL STD Z21 22 1979 Combination temperature pressure relief valves with extension thermostats must be installed so that the temper...

Страница 4: ...WARNING CAUTION Do not store any materials or items on or against the housing of the booster water heater Bradford White requires that two temperature pressure gauges be installed to assure proper ope...

Страница 5: ...ure gauges and a high temperature limit safety switch Magnum Series models feature a Castone tank with a 5 year limited warranty an ON OFF switch an indicator light and either 6 152 mm legs or slide m...

Страница 6: ...0 1 0 1 1 4 32 mm LI6243CFD 24 208 3 66 7 66 7 66 7 90 3 1 25 mm LI6243CFE 24 240 1 100 100 125 1 1 1 4 32 mm LI6243CFF 24 240 3 57 8 57 8 57 8 90 3 1 1 4 32 mm LI6243CFM 24 480 3 29 9 29 9 29 9 40 8...

Страница 7: ...0 kcmil 2 51 mm LI6453CFF 45 240 3 108 108 108 150 1 0 1 1 4 32 mm LI6453CFM 45 480 3 54 54 54 70 4 1 25 mm LI6543CFD 54 208 3 150 150 150 200 3 0 2 51 mm LI6543CFF 54 240 3 130 130 130 175 2 0 1 1 2...

Страница 8: ...nder dish table DO NOT mount on walls or in ceiling Unit must be accessible for service Improper installation could create an unsafe condition Booster Heaters are shipped with most components pre asse...

Страница 9: ...uges are supplied with all booster water heaters One temperature pressure relief valve supplied with all booster heaters Pressure Reducing Valve Shock Absorber Blended Phosphate Water Treatment System...

Страница 10: ...terways are clear This device is designated for emergency safety relief and shall not be used as an operating control The valves are set to relieve at 150 psi 1034 kPa or when water temperature reache...

Страница 11: ...nd reduce the operating life of the unit through increased lime build up Product failure caused by liming or sediment buildup is not covered under warranty Do not use deionized or reverse osmosis R O...

Страница 12: ...er Drain Valve 3 4 Union Floor Drain Outlet Inlet Discharge from T P relief valve Air gap must comply with plumbing code Blended Phosphate Water Treatment System Optional accessory Not supplied with b...

Страница 13: ...O A MINIMUM OF 40 INCH POUNDS NOTE Due to the rigors of transportation all connections should be checked for tightness before booster water heater is put into operation 4 A grounding lug is provided n...

Страница 14: ...unit will get hot Avoid unnecessary contact with unit 6 Turn on the electrical supply to the booster heater 7 Move the Power ON OFF switch to the ON position The indicator light will turn on Figure 1...

Страница 15: ...clockwise to raise the set point NOTE 1 6 turn of the inner screw equals 8 F 4 4 C Temperature Pressure Relief Valve The temperature pressure relief valve lever must be operated at least once a year t...

Страница 16: ...alled properly 8 A check valve should not be installed ahead of the booster NOTE If a check valve is installed and cannot be removed install a back pressure relief valve set at 125 psi 862 kPa on the...

Страница 17: ...be reset contact an Authorized Service Agent Low water cutoff inoperable contacts do not close Contact Authorized Service Agent or Bradford White for assistance Transformer not working properly Contac...

Страница 18: ...ew valve with built in bypass Check valve or anti siphon valve installed in the feed line Remove check valve or anti siphon valve to allow for water expansion or install a back pressure relief valve o...

Страница 19: ...e floor Shock Absorber The shock absorber installed between the booster and the commercial dish machine reduces water hammer induced by rapidly operating valves The water hammer can cause damage to th...

Страница 20: ...WIRING DIAGRAMS Form No EBOOSTERBWM 1009 18 10 01 454 6 9 kW Wiring Diagram All Voltages Single or Three Phase 10 01 448 12 18 kW Wiring Diagram All Voltages Three Phase...

Страница 21: ...WIRING DIAGRAMS Form No EBOOSTERBWM 1009 19 10 01 452 12 15 kW Wiring Diagram 208 and 240 V Single Phase 10 01 447 18 kW Wiring Diagram 208 and 240 V Single Phase...

Страница 22: ...WIRING DIAGRAMS Form No EBOOSTERBWM 1009 20 10 01 432 24 30 kW Wiring Diagram 240 V Single Phase 10 01 433 24 36 kW Wiring Diagram 208 and 240 V Three Phase...

Страница 23: ...WIRING DIAGRAMS Form No EBOOSTERBWM 1009 21 10 01 435 24 36 kW Wiring Diagram 480 V Three Phase 10 01 436 36 kW Wiring Diagram 240 V Single Phase...

Страница 24: ...WIRING DIAGRAMS Form No EBOOSTERBWM 1009 22 10 01 434 45 57 kW Wiring Diagram 480 V Three Phase 10 01 437 36 57 kW Wiring Diagram 208 and 240 V Three Phase...

Страница 25: ...ank only WHAT IS THE DURATION OF THE IMPLIED WARRANTY ANY IMPLIED WARRANTIES INCLUDING THE WARRANTY OF MERCHANTABILITY IMPOSED ON THE SALE OF THE WATER HEATER UNDER THE LAWS OF THE STATE OF SALE ARE L...

Страница 26: ...ecessary allow us or our chosen representative to inspect the unit 5 For your reference fill in the Model and Serial Number found on the units Rating Plate Model Number _______________________________...

Страница 27: ...NOTES Form No EBOOSTERBWM 1009 25...

Страница 28: ...rinted in U S A October 2009 Part No 07 04 474 00 Form No EBOOSTERBWM 1009 Ambler PA 19002 Technical Service 800 334 3393 Service Parts 800 538 2020 Warranty Service 800 531 2111 www bradfordwhite com...

Отзывы: