background image

The high limit control will not

reset until the water temperature has
dropped below the set point of the high limit.

reset multiple times.

The source of the problem

must be found and corrected to insure proper
operation.  The limit  control is covered with an
insulation blanket which must be removed to
push the red reset button.  The blanket of
insulation must be replaced before the power is
turned on and the water heater is returned to
service. 

The heating input to this commercial electric
water heater is provide by low watt density
immersion heating elements. The heating
elements are constructed from an incoloy sheath
with a tin plate on the exterior surface.  Three

element blades are mounted on a single hex-head
screw-in mounting flange.  The element flange
mounts into a 1 1/2” NPT threaded connection
welded to the storage tank.  The hex-head screw-
in mounting flange seals to the tank with an “O”
ring gasket at the base of the threaded portion of
the flange.  The tank flange has a matching recess
for the “O” ring gasket to insure a proper water
tight seal. . The “O” ring element gasket must be
replaced with a new gasket when an element is
removed for inspection, cleaning or replacement.

The optional safety door interlock is an
electrically operated locking pawl that is
energized when main power to the water heater is
turned  “ON.” The interlock is mounted to the
inside of the electrical control panel door and
extends behind a locking flange when energized.
Main power may be turned off and the electrical
access door may be opened for service.

With the door open, main power may be
energized if required to service or troubleshoot
the operation of selected components.

19

SAFETY DOOR INTERLOCK (Optional)

FIG. 22 Immersion Heating Element

NOTE:

IMMERSION HEATING ELEMENT

HAZARD OF ELECTRICAL SHOCK –
Before opening the access panel to remove or
service the immersion heating elements,
make sure the electrical supply to the water
heater is turned “OFF”. Failure to do this
could result in death, serious bodily injury
or property damage.

WARNING: 

Disconnect the main power

to the heater before opening the element
access panel to reset the high limit control.

CAUTION:

FIG. 23

Safety Door Interlock

HAZARD OF ELECTRICAL SHOCK –
Full power is present whenever the cabinet
door is opened and main power is turned
“ON”, even with the pilot switch(es) turned off.

DANGER: 

Содержание CHP-I&S-01

Страница 1: ...acturer s warranty Follow start up procedure in the manual Water heater corrosion and component failure caused by air borne chemical vapors is not covered under the manufacturer s warranty Corrosion d...

Страница 2: ...on 8 Relief Valve 8 Thermal Expansion 8 Cathodic Protection 9 Electrical Service Electrical Connection 9 Wire Sizing 9 Fusing 9 Electrical Connection 9 Jacket Assembly 10 Standard and Optional Control...

Страница 3: ...3 FIG 2 Front View Vertical Square Models FIG 1 Front View Vertical Round Models FIG 3 Front View Horizontal Models...

Страница 4: ...t must conform to the CAE C22 1 Canadian Electrical Code Part 1 and or local Electrical Codes This complete appliance is design certified and Listed by Underwriters Laboratories as a commercial storag...

Страница 5: ...ture of the space where the appliance is installed must not go below 32 F 0 C or above 104 F 40 C The lower pan of the horizontal water heater jacket or vertical square water heater jacket is speciall...

Страница 6: ...d heating elements Top 12 30cm for service access to electrical service water connections and piping Water Pipes 1 25 4mm 6 FIG 5 Clearances from Combustible Construction 12 36 6 FIG 4 Clearances from...

Страница 7: ...oor following applicable architectural and local code requirements or accepted standards for the specific site and model purchased In areas prone to seismic activity it is recommended that the water h...

Страница 8: ...ater heater is supplied with a temperature and pressure relief valve s sized in accordance with ASME Boiler and Pressure Vessel Code Section IV Some water heaters may be supplied with an optional pres...

Страница 9: ...NFPA No 70 When the appliance is installed in Canada it must conform to the CAE C22 1 Canadian Electrical Code Part 1 and or local Electrical Codes 1 Use copper conductors only All wiring between the...

Страница 10: ...sity immersion heating elements with an incoloy sheath Internal fusing of all elements in a maximum of 48 amp increments provides additional safety Fuse cartridges are related at 1 000 000 amps interr...

Страница 11: ...of various control failures Time clock to control off on cycles of the heater as programmed by the owner or electric utility requirements Low water pressure switch High water pressure switch A main po...

Страница 12: ...l circuit supplying power to the immersion heating elements When the thermostat is satisfied the contactor coil is de energized and power to the heating elements is turned off CONTROL CIRCUIT TRANSFOR...

Страница 13: ...has an adjustable thermostat to control water temperature The thermostat is factory pre set at approximately 125 F 51 7 C or less Households with small children or invalids may require a 120 F 48 9 C...

Страница 14: ...scalds Children disabled and elderly are at highest risk of being scalded See instruction manual before setting temperature at heating appliance If this appliance is used to produce water that could...

Страница 15: ...arrow Down arrow and Enter Select Key Sequentially prompts the user as to what parameter is being displayed set point differential stage energized operation mode heat indication of assigned stage 1 2...

Страница 16: ...rential 8o F Output Energized Stage One Energized at 152o F Output De energized Stage One De energized at 160o F Each available stage of operation must be programmed with a set point and a differentia...

Страница 17: ...r Down Arrow key to decrease to the desired set point 8 Press Enter to enter the displayed value into memory 9 Press Select to display the current stage switching differential 10 Press Up Arrow key to...

Страница 18: ...or cannot be field repaired Replace the water heater s electronic temperature control OE ROM Error The internal ROM of the microprocessor in the boiler s electronic temperature control is defective Th...

Страница 19: ...ment gasket must be replaced with a new gasket when an element is removed for inspection cleaning or replacement The optional safety door interlock is an electrically operated locking pawl that is ene...

Страница 20: ...eater storage tank If the water pressure drops below an adjustable set point the control circuit is opened and operation of the water heater is shut down The low water pressure switch may be specified...

Страница 21: ...schedule is maintained in periods where there may be power interruptions The time clock works by making and breaking the 120 VAC control circuit to the contactor coils to shut down operation of the h...

Страница 22: ...expansion The system must make allowance for this expansion If an expansion tank is not provided in the system water pressure may increase to the point where the water heater s temperature and pressu...

Страница 23: ...starts heating check the contactors for buzzing or chattering during operation If noise is detected turn off main power open the control panel and clean the contact points of the magnetic contactor s...

Страница 24: ...ng and start up procedure to place the water heater back into service Listed below are items that must be checked to insure safe reliable operations Verify proper operation after servicing The tempera...

Страница 25: ...in the hot water system because heated water increases the rate of corrosive chemical reactions 25 Water heater maintenance includes periodic tank flushing cleaning and removal of lime scale from the...

Страница 26: ...e exposed ends of the elements which are not accessible through the front element access door 3 Disconnect the wires attached to the element terminals Try not to disturb the wiring unnecessarily and r...

Страница 27: ...contactor or thermostat may be malfunctioning 4 The capacity of the heater may have been exceeded by a large demand for hot water Large demands require a recovery period to restore water temperature 5...

Страница 28: ...encountered local codes or inspection agency should be consulted to determine which of the following procedures is acceptable in your area Installation of an expansion tank Removal of the check valve...

Отзывы: