background image

4. Close and lock the electrical control panel door.

5. Turn on the main electrical power to the

water heater.

6. Temperature control and contactor operation 

should be checked by allowing the water 
heater to come up to temperature and shut off 
automatically.

7. The water heater is now ready continuous 

normal operation.

Draining the Water Heater

1. Turn off the main electrical power to the 

water heater.  If the power disconnect point is 
out of sight, lock it in the open (“OFF”) 
position and tag to prevent unexpected 
application of power.

2. Turn the valve in the water heater’s cold water 

supply to the closed or “OFF” position.

3. Turn the valve in the water heater’s hot water 

outlet to the closed or “OFF” position.

4. Manually open the temperature and pressure 

relief valve to remove any pressure from the 
storage tank.

5. Allow the system to cool and then open the 

drain valve to empty the storage tank.  It will 
be necessary to manually hold the 
temperature and pressure relief valve in the 
open position to break the vacuum in the tank 
and allow it to vent and drain.  Insure that the 
water heater drain is routed to a properly sized
floor drain to allow the water to be removed 
from the tank.  If a floor drain is not available, 
a hose may be attached to the water heater 
drain to take the water outdoors. 

6. The water heater is now shut down and ready 

for service or maintenance.

7. Follow the filling and start up procedure to 

place the water heater back into service.   

Listed below are items that must be checked to
insure safe reliable operations.  Verify proper
operation after servicing.

The temperature and pressure relief valve(s)
should be manually operated at least once a year.
A relief valve that fails to completely reseat after
manual operation and continues to discharge
water must be immediately replaced with a new,
properly sized, temperature and pressure relief
valve.

The relief valve(s) should be installed in the
vertical position and mounted in the tapping
provided in the storage tank.  No valve should be
placed between the relief valve, and the water
heater.  To prevent water damage, the discharge
from the relief valve must be piped to a suitable
floor drain for disposal when relief occurs.  No
reducing couplings or other restrictions shall be
installed in the discharge line.  The discharge line
shall allow complete drainage of the valve and
line.  The discharge line from the relief valve

24

SHUTDOWN PROCEDURE

Any water discharged from

the manually opened relief valve may be hot
and cause a scald injury.

CAUTION:

MAINTENANCE

WARNING: 

HAZARD OF ELECTRICAL SHOCK –
Before opening the access panel to perform
service on any electrical component, make
sure the electrical supply to the water
heater is turned “OFF”. Failure to do this
could result in death, serious bodily injury
or property damage.

Label all wires prior to

disconnection when servicing controls.
Wiring errors can cause improper and
dangerous  operation.

CAUTION:

TEMPERATURE AND PRESSURE

RELIEF VALVE OPERATION

Содержание CHP-I&S-01

Страница 1: ...acturer s warranty Follow start up procedure in the manual Water heater corrosion and component failure caused by air borne chemical vapors is not covered under the manufacturer s warranty Corrosion d...

Страница 2: ...on 8 Relief Valve 8 Thermal Expansion 8 Cathodic Protection 9 Electrical Service Electrical Connection 9 Wire Sizing 9 Fusing 9 Electrical Connection 9 Jacket Assembly 10 Standard and Optional Control...

Страница 3: ...3 FIG 2 Front View Vertical Square Models FIG 1 Front View Vertical Round Models FIG 3 Front View Horizontal Models...

Страница 4: ...t must conform to the CAE C22 1 Canadian Electrical Code Part 1 and or local Electrical Codes This complete appliance is design certified and Listed by Underwriters Laboratories as a commercial storag...

Страница 5: ...ture of the space where the appliance is installed must not go below 32 F 0 C or above 104 F 40 C The lower pan of the horizontal water heater jacket or vertical square water heater jacket is speciall...

Страница 6: ...d heating elements Top 12 30cm for service access to electrical service water connections and piping Water Pipes 1 25 4mm 6 FIG 5 Clearances from Combustible Construction 12 36 6 FIG 4 Clearances from...

Страница 7: ...oor following applicable architectural and local code requirements or accepted standards for the specific site and model purchased In areas prone to seismic activity it is recommended that the water h...

Страница 8: ...ater heater is supplied with a temperature and pressure relief valve s sized in accordance with ASME Boiler and Pressure Vessel Code Section IV Some water heaters may be supplied with an optional pres...

Страница 9: ...NFPA No 70 When the appliance is installed in Canada it must conform to the CAE C22 1 Canadian Electrical Code Part 1 and or local Electrical Codes 1 Use copper conductors only All wiring between the...

Страница 10: ...sity immersion heating elements with an incoloy sheath Internal fusing of all elements in a maximum of 48 amp increments provides additional safety Fuse cartridges are related at 1 000 000 amps interr...

Страница 11: ...of various control failures Time clock to control off on cycles of the heater as programmed by the owner or electric utility requirements Low water pressure switch High water pressure switch A main po...

Страница 12: ...l circuit supplying power to the immersion heating elements When the thermostat is satisfied the contactor coil is de energized and power to the heating elements is turned off CONTROL CIRCUIT TRANSFOR...

Страница 13: ...has an adjustable thermostat to control water temperature The thermostat is factory pre set at approximately 125 F 51 7 C or less Households with small children or invalids may require a 120 F 48 9 C...

Страница 14: ...scalds Children disabled and elderly are at highest risk of being scalded See instruction manual before setting temperature at heating appliance If this appliance is used to produce water that could...

Страница 15: ...arrow Down arrow and Enter Select Key Sequentially prompts the user as to what parameter is being displayed set point differential stage energized operation mode heat indication of assigned stage 1 2...

Страница 16: ...rential 8o F Output Energized Stage One Energized at 152o F Output De energized Stage One De energized at 160o F Each available stage of operation must be programmed with a set point and a differentia...

Страница 17: ...r Down Arrow key to decrease to the desired set point 8 Press Enter to enter the displayed value into memory 9 Press Select to display the current stage switching differential 10 Press Up Arrow key to...

Страница 18: ...or cannot be field repaired Replace the water heater s electronic temperature control OE ROM Error The internal ROM of the microprocessor in the boiler s electronic temperature control is defective Th...

Страница 19: ...ment gasket must be replaced with a new gasket when an element is removed for inspection cleaning or replacement The optional safety door interlock is an electrically operated locking pawl that is ene...

Страница 20: ...eater storage tank If the water pressure drops below an adjustable set point the control circuit is opened and operation of the water heater is shut down The low water pressure switch may be specified...

Страница 21: ...schedule is maintained in periods where there may be power interruptions The time clock works by making and breaking the 120 VAC control circuit to the contactor coils to shut down operation of the h...

Страница 22: ...expansion The system must make allowance for this expansion If an expansion tank is not provided in the system water pressure may increase to the point where the water heater s temperature and pressu...

Страница 23: ...starts heating check the contactors for buzzing or chattering during operation If noise is detected turn off main power open the control panel and clean the contact points of the magnetic contactor s...

Страница 24: ...ng and start up procedure to place the water heater back into service Listed below are items that must be checked to insure safe reliable operations Verify proper operation after servicing The tempera...

Страница 25: ...in the hot water system because heated water increases the rate of corrosive chemical reactions 25 Water heater maintenance includes periodic tank flushing cleaning and removal of lime scale from the...

Страница 26: ...e exposed ends of the elements which are not accessible through the front element access door 3 Disconnect the wires attached to the element terminals Try not to disturb the wiring unnecessarily and r...

Страница 27: ...contactor or thermostat may be malfunctioning 4 The capacity of the heater may have been exceeded by a large demand for hot water Large demands require a recovery period to restore water temperature 5...

Страница 28: ...encountered local codes or inspection agency should be consulted to determine which of the following procedures is acceptable in your area Installation of an expansion tank Removal of the check valve...

Отзывы: