Bosch Rexroth Corp.
, USL00010, 01.2015
11 Limit Values (continued)
11.2 Configure torque/force limit values
11.2.1 Steps for configuring torque/force limit values:
1. In the Explorer tree, select Torque / Force Limits
2. Based on application requirements, enter torque/force limit values (factory default is
400% of the nominal continuous torque/force, see motor datasheet)
NOTE: Per parameter S-0-0086, for linear kit motors, the reference value (100% value) also
corresponds to the continuous torque at standstill or the continuous force at standstill.
In this case, the cooling factor is “1.0” because the cooling type is invariable (P-0-0640
is inactive).
20
Limit Values