16
en | System Installation and Configuration
Easy Series
F01U087835 | 02 | 2008.10
System Reference Guide
Bosch Security Systems, Inc.
2.2.6
Install the DX2010 Input Expander
The control panel supports up to three DX2010 Input Expanders for Points 9 to 32.
Refer to the
DX2010 Installation Instructions
(P/N: 49533) for more information.
1.
Set the DX2010's DIP switches.
2.
Mount the DX2010 into the control panel's enclosure (back wall or either side wall), or
other suitable enclosure.
3.
Connect the DX2010 to the control panel. Refer to
Figure 1.1
, Page 6.
Connect a wire jumper to the TMPR and COM terminals to disable the DX2010's tamper
input. For point wiring options, refer to
Section 2.2.8 Connect Supervised Points
, Page 16.
To disable the tamper input on the DX2010, connect a wire jumper between the TMPR
and COM terminals.
2.2.7
Connect the Conettix DX4020 Network Interface Module
The control panel supports one DX4020 for wired network communication.
Refer to the
DX4020 Installation Instructions
(P/N: F01U045288) for more information.
1.
Set the DX4020's DIP switches to Address 134 for network communication.
2.
Mount the DX4020 into the control panel's enclosure using the back wall or side wall
mounting location.
3.
Connect the DX4020 to the control panel. Refer to
Figure 1.1
, Page 6.
2.2.8
Connect Supervised Points
For wiring diagrams, refer to
Figure 1.1
, Page 6.
Fire Point Wiring
Supervised Point 1 supports two- and four-wire smoke detectors.
Supervised Points 2 to 32 support only four-wire smoke detectors.
To program supervised points as fire points, refer to
Section 5.1.2 Points
, page 39.
For intrusion point configuration, refer to
Section Intrusion Point Wiring
, Page 16.
When using an output to supply power to a four-wire smoke detector, program the output
function for System Reset. Refer to
Section 5.1.4 Outputs
, page 41.
Intrusion Point Wiring
You can wire Supervised Points 1 to 32 as wired or wireless intrusion points.
To program Supervised Points 1 to 32 as intrusion points, refer to
Section 5.1.2 Points
,
page 39.
i
NOTICE!
In an NF A2P certified installation, mount the DX2010 module on one side of the panel
housing, or on one side of the auxiliary power supply IPP-PSU-2A5).